AME30-5DMAZ [AIMTEC]
30 Watt | AC-DC Converter; 30瓦特| AC-DC转换器型号: | AME30-5DMAZ |
厂家: | AIMTEC |
描述: | 30 Watt | AC-DC Converter |
文件: | 总3页 (文件大小:1761K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Series AME30-MAZ
30 Watt | AC-DC Converter
FEATURES:
• 4000VAC I/O isolation
• Medical Switching power modules for PCB mounting
• Operating temperature: -40 to +85°C
•
•
•
•
Energy star compliant
RoHS compliant
Low Ripple and Noise
CE, cULus approvals
• Universal Input: 90-260VAC, 47-440Hz, or 120-370VDC
Models
Single output
CB
Output Current
Input Voltage
(VAC/Hz)
Input Voltage
Output Voltage
(V)
Efficiency
(%)
Model
max
(A)
6
6
2.5
2
(VDC)
AME30-3.3SMAZ
AME30-5SMAZ
AME30-12SMAZ
AME30-15SMAZ
AME30-24SMAZ
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
120-370
120-370
120-370
120-370
120-370
3.3
5
12
15
24
80
83
85
85
84
1.25
Models
Dual output
Output Current
Input Voltage
Input Voltage
(VDC)
Output Voltage
(V)
Efficiency
(%)
Model
max
(A)
(VAC/Hz)
AME30-5DMAZ
AME30-12DMAZ
AME30-15DMAZ
AME30-24DMAZ
90-264/47-440
90-264/47-440
90-264/47-440
90-260/47-440
120-370
120-370
120-370
120-370
±5
±12
±15
±24
±3
±1.25
±1
81
84
83
82
±0.625
NOTE: All specifications in this datasheet are measured at an ambient temperature of 25°C, humidity<75%, nominal input voltage and at
rated output load unless otherwise specified.
Input Specifications
Parameters
Conditions
115 VAC
230 VAC
115 VAC
230 VAC
Typical
Maximum
Units
mA
mA
A
740
410
25
Current
Inrush current <2ms
A
50
Leakage current
External fuse
µA
A
150
Recommended slow blow type
No load; 115VAC
3.15
<0.5
<0.8
117
Input dissipation
Start-up time
W
No load; 264VAC
ms
Output Specifications
Parameters
Voltage accuracy
Line regulation
Conditions
Typical
±2
±0.5
Maximum
Units
%
%
(LL-HL)
0-100% load single
0-100% load dual
±1
±2
±5
Load regulation
%
Cross regulation
25% load - 1st out, 100% load – 2nd out
Depending of the model
25% load Step
%
µF
% of Vout
mV p-p
ms
Maximum Capacitive load
Transient response deviation
Ripple & Noise*
Hold-up time (min)
Minimum Load Current
470-23 000
±2
50
29
0
20MHz bandwidth
115VAC
% of Max
*Ripple & Noise measured with 0.1μF M/C and 1μF E/C
www.aimtec.com
F 052e R7
Tel: +1 514 620 2722
1 of 3
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AME30-MAZ
30 Watt | AC-DC Converter
Isolation Specifications
Parameters
Tested I/O voltage
Input FG
Output FG
Conditions
3 sec
Typical
4000
1500
1500
>1000
Maximum
Units
VAC
VAC
VAC
MΩ
3 sec
3 sec
Isolation Resistance
General Specifications
Parameters
Switching frequency
Over current protection
Over voltage protection
Short circuit protection
Short Circuit restart
Operating temperature
Maximum case temperature
Storage temperature
Temperature coefficient
Cooling
Conditions
Typical
47
110
Maximum
Units
KHz
%
Auto recovery
140
110
Zener diode clamp
Hiccup mode, indefinite
Auto recovery
%
With derating above 55ºC
-40 - +85
oC
oC
100
95
-40 to +95
0.02
Free air convection
oC
% / oC
Humidity
Case material
Weight
Non condensing
% RH
g
Plastic resin + Fiberglass (flammability to UL 94V-0)
300
Dimensions (L X H X W)
MTBF
3.56 x 2.48 x 1.18 inches
90.5 x 63 x 30 mm
> 800 000 hrs (MIL-HDBK -217F, t=+25oC)
Environment Approval
Test
Parameters
Conditions
Wave form
Half sine wave
Acceleration amplitude
Bump duration
Converter operation
Number of bumps
Test mode
Displacement
Acceleration
Converter operation
5gn
30 ms
Shock
Before and after test, body mounted (on chassis)
18 (3 in each direction for every axis)
Sweep sine, 10-100Hz, speed 0.05Hz/s
1 mm
3g, 3 loops 30min one cycle, 3h total, every axis tested
Before and after test, body mounted (on chassis)
Vibration
Safety Specifications
Standards
EMI - Conducted and radiated emission
Medical Electrical Equipment
Harmonic Current Emissions
Voltage fluctuations and flicker
Electrostatic Discharge Immunity
RF, Electromagnetic Field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
EN55011, class B
EN 60601-1, CSA-C22.2 No. 601.1-M90
IEC/EN 61000-3-2, (EN60555-2)
IEC/EN 61000-3-3, (EN60555-3)
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
Safety
IEC 61000-4-5
RF, Conducted Disturbance Immunity
Power frequency Magnetic Field Immunity
Voltage dips, Short Interruptions Immunity
cULus, CE, CB
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
Agency approvals
www.aimtec.com
F 052e R7
Tel: +1 514 620 2722
2 of 3
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AME30-MAZ
30 Watt | AC-DC Converter
Pin Out Specifications
Pin
1
2
3
4
Single
AC Input (N)
AC Input (L)
+V Output
-V Output
N. C.
Dual
AC Input (N)
AC Input (L)
+V Output
Common
5
-V Output
Dimensions
Derating
Free Air Convection
º
55
C
100
80
Safe Operating Area
60
40
20
0
85
80
100
- 40 - 20
0
20
40
60
º C
Ambient Temperature
NOTE: 1. Datasheets are updated as needed and as such, specifications are subject to change without notice. Once printed or downloaded, datasheets are no longer controlled
by Aimtec; refer to www.aimtec.com for the most current product specifications. 2. Product labels shown, including safety agency certifications on labels, may vary based on the
date manufactured. 3. Mechanical drawings and specifications are for reference only. 4. All specifications are measured at an ambient temperature of 25°C, humidity<75%,
nominal input voltage and at rated output load unless otherwise specified.5..Aimtec may not have conducted destructive testing or chemical analysis on all internal components
and chemicals at the time of publishing this document. CAS numbers and other limited information are considered proprietary and may not be available for release. 5. This
product is not designed for use in critical life support systems, equipment used in hazardous environments, nuclear control systems or other such applications which necessitate
specific safety and regulatory standards other the ones listed in this datasheet.
www.aimtec.com
F 052e R7
Tel: +1 514 620 2722
3 of 3
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
相关型号: