AMED75-12SNZ [AIMTEC]
Power Supply Module;型号: | AMED75-12SNZ |
厂家: | AIMTEC |
描述: | Power Supply Module |
文件: | 总4页 (文件大小:661K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
AMED75-NZ
AC-DC Converter
Click to
ORDER
AMED75-NZ
samples
The AMED75-NZ is whole new DIN rail bracket AC-DC converter featuring a cost
effective, energy efficient solution. The products offer a high level of stability and
immunity to noise, compliant with international IEC/EN/UL62368, IEC/EN/UL60335,
GB4943 and UL508 standards. These lightweight AC-DC converters also have an
extremely compact design for space saving and are ideal for applications such as
industrial control
equipment machinery and numerous applications for harsh environments.
This new series offers great operating temperatures, from -40℃ to 70℃ and an
isolation of 4000VAC for improved reliability and system safety. Furthermore, a high
MTBF of 300,000h, output short circuit protection (OSCP), output over-current
protection (OCP) and an output over-voltage protection (OVP) come standard with
the series.
Picture coming soon
DIN Rail
Features
Summary
AMED75-NZ
•
•
•
•
•
Universal Input: 90 - 264VAC/120 - 373VDC
Operating Temp: -30 °C to +70 °C
High isolation voltage: 4000VAC
Low ripple & noise, 150mV(p-p), max.
Output short circuit, over-current, over-voltage,
over-temperature protection
528
48
120
4000
70
45
85
70
75
264
12
90
0
1000
3.3
1
-10
-30
-30
-40
Input voltage Output voltage Isolation
Power
(W)
Temp. range
(°C)
Derating
(°C)
(VAC)
(V)
(VAC)
Applications
Training
Press Release
Coming Soon!
Industrial
Telecom
Instrumentation
Power Grid
Application Notes
Product Training Video
(click to open)
F 052e R4
www.Aimtec.com
1
AMED75-NZ
AC-DC Converter
Models & Specifications
Single Output
Input
Voltage
(VDC)
Max Output
wattage
(W)
Output
Voltage
(V)
Output
Current max
(A)
Maximum
capacitive
load (µF)
Efficiency
@ 230VAC
Typ. (%)
Input Voltage
(VAC/Hz)
Model
AMED75-12SNZ
AMED75-24SNZ
AMED75-48SNZ
90~264/47~63
90~264/47~63
90~264/47~63
120~373
120~373
120~373
75
75
75
12
24
48
6.3
3.2
1.6
6000
1500
1000
86
89
90
Input Specifications
Parameters
Conditions
Typical
Maximum
Units
115VAC
230VAC
115VAC
230VAC
2000
1000
Input Current
mA
25
45
Inrush Current
A
Leakage Current
240VAC / 50Hz
3.5
mA RMS
Output Specifications
Parameters
Conditions
Typical
Maximum
Units
12 VDC Output
24,48 VDC Output
Rated load
0 - 100% load
12 VDC Output
± 2
± 1
± 0.5
± 1
%
%
%
%
Voltage accuracy
0 - 100% load
Line regulation
Load regulation
80
Ripple & Noise
20MHz bandwidth
24 VDC Output
48 VDC Output
120
150
mV p-p
115VAC
230VAC
12
60
ms
ms
Hold up time
12 VDC Output
24 VDC Output
48 VDC Output
12 – 14
24 - 28
48 - 53
Voltage adjustable range
V
Isolation Specifications
Parameters
Conditions
Typical
Maximum
Units
Tested I/O voltage
4000
2000
500
Tested Input to GND voltage
Tested Output to GND voltage
Insulation resistance
60 sec, Leakage current < 10mA
500VDC
VAC
>50
MΩ
F 052e R4
www.Aimtec.com
2
AMED75-NZ
AC-DC Converter
General Specifications
Parameters
Conditions
Typical
Maximum
Units
Over Current protection
Self- recovery
105 - 150
≤ 17
% of Iout
12 VDC Output, manual-recovery
24 VDC Output, manual-recovery
48 VDC Output, manual-recovery
Over voltage protection
≤ 33
≤ 60
VDC
Over temperature protection
Short circuit protection
Switching Frequency
Operating temperature
Storage temperature
Output voltage turn off, manual-recovery
Hiccup, Continuous, Self-recovery(Recovery time < 3S)
65
KHz
°C
°C
-30 to +70
-40 to +85
-30 °C to -10°C
45 °C to 70 °C
90 to 100 VAC
2.0
2.0
2.0
% / °C
% / °C
% / VAC
% / °C
Power derating
Temperature coefficient
Protection Class
Cooling
± 0.03
Class I
Free air convection
Storage Humidity
Case material
Weight
95
% RH
g
Metal (AL5052, SGCC) and Plastic( PC940)
370
Dimensions (L x W x H)
MTBF
1.18 x 5.04 x 4.72 inches (30.00 x 128.00 x 120.00 mm)
> 300 000 hrs (MIL-HDBK -217F, t=+25oC)
NOTE: All specifications in this datasheet are measured at an ambient temperature of 25°C, humidity<75%, nominal input voltage and at rated
output load unless otherwise specified.
Safety Specifications
Parameters
Designed to meet IEC/EN/UL 62368, IEC/EN/UL 60335, GB4943, UL508
EMC - Conducted and radiated emission
Harmonic current
CISPR32 / EN55032, Class B
IEC/EN 61000-3-2, Class A
Electrostatic Discharge Immunity
Standards RF, Electromagnetic Field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
IEC 61000-4-2 Contact ±4KV, Air ±6KV, Criteria A
IEC 61000-4-3 10V/m, Criteria A
IEC 61000-4-4 ±2KV, Criteria A
IEC 61000-4-5 L-L ±2KV, L-G ±4KV, Criteria A
IEC 61000-4-6 10V r.m.s, Criteria A
CS, Conducted Disturbance Immunity
Voltage dips, Short Interruptions Immunity IEC 61000-4-11 0%, 70%, Criteria B
F 052e R4
www.Aimtec.com
3
AMED75-NZ
AC-DC Converter
Derating
Temperature Derating
Input Voltage Derating
100
80
100
80
60
60
Safe Operating Area
50
Safe Operating Area
40
40
Input Voltage :
Ambient temperature 25°C
90 ~ 264VAC
120 ~ 373 VDC
20
0
20
0
90
120
0
45
50
100
140
264
373
-30
-10
10
30
70
90
110
(º C)
Ambient Temperature
Input Voltage (VAC/VDC)
Dimensions
Pin Output Specifications
120.00
(4.72)
Pin
1
2
3
4
5
6
7
Function
+V Output
+V Output
-V Output
-V Output
GND
19.05
(0.75)
6.35
(0.25)
1
2
3
4
DC_ON
Input (N)
Input (L)
ADJ
ADJ Voltage adjustment
Note:
Unit: mm (inch)
General tolerance : ±1.0 (0.04)
Wire gauge : 26 - 10AWG
Tightening torque : 0.4N·m Max.
5
6
7
Mounting rail : TS35, rail need to connect safety ground
7.62
(0.30)
15.24
(0.60)
NOTE: 1. Datasheets are updated as needed and as such, specifications are subject to change without notice. Once printed or downloaded, datasheets are no longer controlled by Aimtec; refer to
www.aimtec.com for the most current product specifications. 2. Product labels shown, including safety agency certifications on labels, may vary based on the date manufactured. 3. Mechanical
drawings and specifications are for reference only. 4. All specifications are measured at an ambient temperature of 25°C, humidity<75%, nominal input voltage and at rated output load unless
otherwise specified. 5. Aimtec may not have conducted destructive testing or chemical analysis on all internal components and chemicals at the time of publishing this document. CAS numbers and
other limited information are considered proprietary and may not be available for release. 6. This product is not designed for use in critical life support systems, equipment used in hazardous
environments, nuclear control systems or other such applications which necessitate specific safety and regulatory standards other the ones listed in this datasheet. 7. Warranty is in accordance with
Aimtec’s standard Terms of Sale available at www.aimtec.com.
F 052e R4
www.Aimtec.com
4
相关型号:
©2020 ICPDF网 联系我们和版权申明