AMEOS30-24SMAZ [AIMTEC]
30 Watt | AC/DC Converter; 30瓦| AC / DC转换器型号: | AMEOS30-24SMAZ |
厂家: | AIMTEC |
描述: | 30 Watt | AC/DC Converter |
文件: | 总5页 (文件大小:388K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Series AMEOS30-MAZ
30 Watt | AC/DC Converter
FEATURES:
• 4000VAC I/O isolation
•
•
•
•
Energy star compliant
RoHS compliant
Low ripple and noise
CE, cULus, CB approvals
• Operating temperature: -40°C to +85°C
• Over load, Over voltage, Short circuit protection
• Universal Input: 90-260VAC, 47-440Hz, or 120-370VDC
Models
Single output
CB
Output Current
Input Voltage
Input Voltage
Output Voltage
Efficiency
Model
max
(A)
6
6
2.5
2
(VAC/Hz)
(VDC)
(V)
(%)
AMEOS30-3.3SMAZ
AMEOS30-5SMAZ
AMEOS30-12SMAZ
AMEOS30-15SMAZ
AMEOS30-24SMAZ
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
120-370
120-370
120-370
120-370
120-370
3.3
5
12
15
24
80
83
85
85
84
1.25
Models
Dual output
Output Current
Input Voltage
Input Voltage
Output Voltage
Efficiency
Model
max
(A)
(VAC/Hz)
(VDC)
(V)
(%)
AMEOS30-5DMAZ
AMEOS30-12DMAZ
AMEOS30-15DMAZ
AMEOS30-24DMAZ
90-264/47-440
90-264/47-440
90-264/47-440
90-260/47-440
120-370
120-370
120-370
120-370
±5
±12
±15
±24
±3
±1.25
±1
81
84
83
82
±0.625
NOTE: All specifications in this datasheet are measured at an ambient temperature of 25°C, humidity<75%, nominal input voltage and at
rated output load unless otherwise specified.
Input Specifications
Parameters
Conditions
115 VAC
230 VAC
115 VAC
230 VAC
Typical
Maximum
Units
740
410
25
Current
mA
Inrush current <2ms
A
50
Leakage current
External fuse
µA
A
150
Recommended slow blow type
No load; 115VAC
3.15
<0.5
<0.8
117
Input dissipation
Start-up time
W
No load; 264VAC
ms
Output Specifications
Parameters
Voltage accuracy
Line regulation
Conditions
Typical
±2
±0.5
Maximum
Units
%
%
(LL-HL)
0-100% load single
0-100% load dual
±1
±2
±5
Load regulation
%
Cross regulation
25% load - 1st out, 100% load – 2nd out
Depending of the model
25% load Step
%
µF
% of Vout
mV p-p
ms
Maximum Capacitive load
Transient response deviation
Ripple & Noise*
Hold-up time (min)
Minimum Load Current
470-23 000
±2
50
29
0
20MHz bandwidth
115VAC
% of Max
*Ripple & Noise measured with 0.1μF M/C and 1μF E/C
www.aimtec.com
F 052e R7.F
Tel: +1 514 620 2722
1 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AMEOS30-MAZ
30 Watt | AC/DC Converter
Isolation Specifications
Parameters
Tested I/O voltage
Conditions
Typical
Rated
4000
Units
VAC
MΩ
3 sec
Isolation Resistance
>1000
General Specifications
Parameters
Switching frequency
Over current protection
Over voltage protection
Short circuit protection
Short Circuit restart
Operating temperature
Maximum case temperature
Storage temperature
Temperature coefficient
Cooling
Conditions
Typical
47
110
Maximum
Units
KHz
%
Auto recovery
140
110
Zener diode clamp
Hiccup mode, indefinite
Auto recovery
%
With derating above 60ºC
Non condensing
-40 - +85
oC
oC
100
95
-40 to +95
0.02
Free air convection
oC
% / oC
Humidity
Weight
% RH
g
145
Dimensions (L X H X W)
MTBF
4.92 x 2.32 x 1.02 inches
/
125 x 59 x 26mm
> 800 000 hrs (MIL-HDBK -217F, t=+25oC)
Environment Approval
Test
Parameters
Conditions
Wave form
Half sine wave
Acceleration amplitude
Bump duration
Converter operation
Number of bumps
Test mode
Displacement
Acceleration
Converter operation
5gn
30 ms
Shock
Before and after test, body mounted (on chassis)
18 (3 in each direction for every axis)
Sweep sine, 10-100Hz, speed 0.05Hz/s
1 mm
3g, 3 loops 30min one cycle, 3h total, every axis tested
Before and after test, body mounted (on chassis)
Vibration
Safety Specifications
Parameters
Agency approvals
cULus, CE, CB Scheme
Medical Electrical Equipment
IEC\EN\UL 60601-1, CSA-C22.2 No. 601.1-M90
EN 60950-1:2006+A11:2009
EN55011, class B
IEC/EN 61000-3-2, (EN60555-2)
IEC/EN 61000-3-3, (EN60555-3)
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
Information technology Equipment
EMI - Conducted and radiated emission
Harmonic Current Emissions
Voltage fluctuations and flicker
Electrostatic Discharge Immunity
RF, Electromagnetic Field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
Standards
RF, Conducted Disturbance Immunity
Power frequency Magnetic Field Immunity
Voltage dips, Short Interruptions Immunity
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
www.aimtec.com
F 052e R7.F
Tel: +1 514 620 2722
2 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AMEOS30-MAZ
30 Watt | AC/DC Converter
Pin Out Specifications
Pin
1
2
3
4
Single
AC Input (L)
AC Input (N)
+V Output
-V Output
N.C.
Dual
AC Input (L)
AC Input (N)
+V Output
Common
5
Common
6
N.C.
-V Output
N.C.: Not Connected
Dimensions
59.00
(2.32)
59.00
(2.32)
52.00
(2.05)
1 2
AC Input
Screw Terminals
3.50
(0.14)
3 4 5 6
Top View
DC Output
Screw Terminals
Bottom View
www.aimtec.com
F 052e R7.F
Tel: +1 514 620 2722
3 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AMEOS30-MAZ
30 Watt | AC/DC Converter
Derating
Free Air Convection
º
60
C
100
80
Safe Operating Area
60
40
20
0
85
80
100
- 40 - 20
0
20
40
60
º C
Ambient Temperature
NOTE: 1. Datasheets are updated as needed and as such, specifications are subject to change without notice. Once printed or downloaded, datasheets are no longer
controlled by Aimtec; refer to www.aimtec.com for the most current product specifications. 2. Product labels shown, including safety agency certifications on labels, may vary
based on the date manufactured. 3. Mechanical drawings and specifications are for reference only. 4. All specifications are measured at an ambient temperature of 25°C,
humidity<75%, nominal input voltage and at rated output load unless otherwise specified. 5. Aimtec may not have conducted destructive testing or chemical analysis on all
internal components and chemicals at the time of publishing this document. CAS numbers and other limited information are considered proprietary and may not be available for
release. 6. This product is not designed for use in critical life support systems, equipment used in hazardous environments, nuclear control systems or other such applications
which necessitate specific safety and regulatory standards other the ones listed in this datasheet. 7. Warranty is in accordance with Aimtec’s standard Terms of Sale available at
www.aimtec.com.
www.aimtec.com
F 052e R7.F
Tel: +1 514 620 2722
4 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AMEOS30-MAZ
30 Watt | AC/DC Converter
www.aimtec.com
F 052e R7.F
Tel: +1 514 620 2722
5 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
相关型号: