700-SCZY2A1 [ALLEN-BRADLEY]
Solid-State Relays; 固态继电器型号: | 700-SCZY2A1 |
厂家: | Allen-Bradley |
描述: | Solid-State Relays |
文件: | 总5页 (文件大小:392K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Bulletin 700-SC
Solid-State Relays
Overview/Product Selection
Table Of Contents
Bulletin 700-SC
Product Selection . . . . . . . 37
Accessories . . . . . . . . . . . . 38
Specifications . . . . . . . . . . 39
Approximate
Dimensions . . . . . . . . . . . . 41
•
•
•
•
•
•
3 A (resistive) Max. Continuous Load (Output) Current
264V AC, 48V DC or 125V DC Max. Load Voltage Range Options
5…24V DC or 110/220V AC Control (Input) Voltage Options
LED Indicator (Optional) For Input/Logic ON/OFF Status Monitoring
700-HN103, 700-HN104, or 700-HN128 Socket Compatible
Compatible with 700-AT1 or 700-AT2 Timer Module
Product Selection
Factory-
stocked
Item
(Single
Pack)
Rated Output (Load)
Max. Current and Voltage
Range
Input-to-Output Zero Cross
LED
Indicator
Rated Input Control
Voltage
Cat. No.
Isolation Method
Function
3 A @100…240V AC
2 A @ 100…240V AC
5…24V DC
100/110V AC
200/220V AC
24V DC
700-SCZY3Z25
700-SCZY2A1
700-SCZY2A2
700-SCTY3Z24
700-SCNY3Z25
700-SCZN3Z26
700-SCTN3Z24
700-SCNN3Z26
✔
✔
✔
✔
✔
✔
✔
✔
Photocoupler
Yes
Yes
No
Phototriac
Photocoupler
Phototriac
No
No
Yes
No
3 A @100…240V AC
3 A @ 4…48V DC
5…24V DC
4…24V DC
24V DC
3 A @ 100…240V AC
3 A @ 4…48V DC
4…24V DC
Photocoupler
N/A
2 A @ 5…110V DC
5…24V DC
700-SCNN2Z25
✔
37
Bulletin 700-SC
Solid-State Relays
Accessories
Description
Pkg. Quantity
Cat. No.
Factory-stocked Item
Screw Terminal Socket — Panel or DIN Rail
Mounting; Guarded Terminal Construction
Order must be in ten or multiples of ten
1
700-HN103
✔
Cat. No. 700-HN103
Screw Terminal Socket – Panel or DIN Rail
Mounting. Guarded Terminal Construction
14-blade miniature socket for use with
Bulletin 700-SC relays. This socket has coil
and contact separation as well as the ability
to plug in optional plug in modules (700-A**
accessories: LED, Surge Suppression,
Timing Modules)
10
10
700-HN104
700-HN128
✔
✔
Cat. No. 700-HN104
Screw Terminal Base Socket — Panel or
DIN Rail Mounting; Open Style
Construction
Order must be in multiples of ten
Cat. No. 700-HN128
DIN Rail Mounting Pack
Standard 35 x 7.5 mm DIN Rail, 1 meter long,
10 rails per package. Order must be for 10
rails or multiples of 10.
10
199-DR1
✔
Cat No. 199-DR1
Pre-printed identification tags — contains
10 sheets of pre-printed and blank tags. Each
sheet contains 13 sets of the markings
CR…9CR, TR…9TR, M…9M, F, R, 1S, and
117 blank tags. Tags are peel-off with sticky
backing for easy placement on relays.
10
10
700-N40
700-N41
Blank identification tags — contains 10
sheets of blank identification tags for
customer specialized printing. Each sheet
contains 546 blank tags. Tags are peel-off
with sticky backing for easy placement on
relays.
Retainer Clip
Secures relay in socket. Order must be for
10 clips or multiples of 10.
10
700-HN114(B)✔
✔
Sample Retainer Clips
ON-Delay Time Module
Voltage Range: 12…24V AC/DC
used with 700-HN153 socket
1
1
700-AT1
700-AT2
One Shot Timing Module
Voltage Range: 12…24V AC/DC
used with 700-HN153 socket
✔ Series B retainer clip must be used with Bulletin 700-SC
38
Bulletin 700-SC
Solid-State Relays
Specifications
Control/Input Ratings
Control Voltage Levels
Rated Control
Voltage
Operating Control Voltage
Cat. No.
Impedance
Range
Pick-up Voltage
4V DC max.
Drop-out Voltage
1V DC min.
700-SCZY3Z25
700-SCZY2A1
700-SCZY2A2
700-SCTY3Z24
700-SCNY3Z25
700-SCZN3Z26
700-SCTN3Z24
700-SCNN3Z26
700-SCNN2Z25
5…24V DC
100/110V AC
200/220V AC
24V DC
4…28V DC
75…125V AC
150…250V AC
19.2…28.8V DC
4…28V DC
15 mA max. ✔
41 KΩ± 20%
75V AC max.
150V AC max.
19.2V DC max.
4V DC max.
20V AC min.
40V AC min.
72 KΩ ± 20%
2 KΩ ± 20%
5…24V DC
4…24V DC
24V DC
1.5 KΩ + 20%/–10% ✔
15 mA max. ✔
2 kΩ ± 20%
3…28V DC
3V DC max.
1V DC min.
19.2…28.8V DC
19.2V DC max.
4…24V DC
5…24V DC
3…28V DC
1.5 KΩ + 20%/–10% ✔
3V DC max.
Load/Output Ratings
Applicable Load
Rated
Load Voltage
Cat. No.
Continuous Load Current
(Resistive)
Load Voltage Range
—
Max. Inrush Current ✔
—
—
Min.
Max. ✔
—
700-SCZY3Z25
700-SCTY3Z24
700-SCZN3Z26
700-SCTN3Z24
700-SCZY2A1
700-SCZY2A2
700-SCNN3Z25
700-SCNY3Z26
700-SCNN2Z25
100…240V AC
0.1 A
3 A
75…264V AC
45 A (@50/60 Hz, 1 cycle)
100…240V AC
0.1 A
2 A
4…48V DC
3…52.8V DC
3…125V DC
0.1 A
0.1 A
3 A
2 A
18 A (10 ms)
10 A (10 ms)
5…110V DC
✔ With constant current input circuit system. SSR impedance varies with a change in input voltage.
✔ Input impedance attains its maximum at the operating voltage.
✔ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to “Inrush Current Resistivity” graphs on page 40 for details.
✔ Refer to the following "Load Current Versus Ambient Temperature Characteristics" graphs on page 40 for additional load current details.
Characteristics
Cat. No.
700-SCZ….
700-SCT
700-SCNN3…
700-SCNN2…
Load Switching Method/Device
Triac
Transistor
1/2 of load power source + 1 ms
max. (DC input)
Pick-up Time
Drop-out Time
1 ms max
0.5 ms max
0.5 ms max
3/2 of load power source + 1 ms
max. (AC input)
1/2 of load power source + 1 ms
max. (DC input)
1/2 of load power source +
1 ms max
2 ms max
2.5 ms max
1.5V max.
3/2 of load power source + 1 ms
max. (AC input)
Output ON Voltage Drop
Output Leakage Current
1.6 V (RMS) max
1.6V (RMS)
1.5 V max.
2.5 mA max
(@ 100 V AC)
5 mA max (at 200 V AC)
5 mA max (@ 100 V AC)
10 mA max (@ 200 V AC)
0.1 mA max (@ 100 V
DC)
5 mA max (@ 50 V DC)
Output VDRM, VCEO
600
600
80
80
(V)
Output di/dt (A/uS)
Output dv/dt (V/uS)
50
250
18
50
250
18
—
—
—
—
2
Output I t (A2S)
—
—
Output Tj °C Max.
Insulation Resistance
Dielectric Strength
125
125
150
150
100 MΩ min (@ 500V DC)
1,500 V AC, 50/60 Hz for 1 minute
10…55 Hz, 1.5 mm double amplitude (10 G)
1,000 m/s2 (100 G)
Vibration Resistance (max.)
Shock Resistance (max.)
Operating: -30°C…80°C (-22...176°F) with no icing or condensation
Storage: -30°C…100°C (-22...212°F) with no icing or condensation
Ambient Temperature
39
Bulletin 700-SC
Solid-State Relays
Specifications, Continued
Characteristics
UL508, CSA C 22.2,
CE, VDE
Standards
Ambient Humidity
Weight
Operating: 45%…85% (no condensation)
Approx. 50 g
Load Current Versus Ambient Temperature Characteristics
700-SC_ _3...
700-SC_ _2...
Ambient temperature (°C)
Ambient temperature (°C)
Inrush Current Resistivity✔
700-SCNN3...
700-SCNY3
700-SCZ....
700-SCT...
700-SCNN2...
10
20
Energizing time (ms)
Energizing time (ms)
Energizing time (ms)
✔ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability
once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
40
Bulletin 700-SC
Solid-State Relays
Approximate Dimensions
Note: Bulletin 700-SC is compatible with the 700-HN103, 700-HN104, and 700-HN128 sockets. All units in millimeters unless otherwise indicated. Dimensions
are not intended for manufacturing purposes.
Terminal Arrangement/
Internal Connections
(Bottom View)
1
5
4
8(+)
(+)
(–)
28 max.
Load
Load
power
supply
Load
Input
9
12(–)
13
–
14
+
36.5 max.
42.5 max.
21.5 max.
+
–
Input voltage
Cat, No 700-SC… ✔
Note: The plus and minus symbols shown
in parentheses are for DC loads.
✔ Bulletin 700-SC is compatible with cat. nos. 700-HN103, -HN104, and -HN128 socket.
Basic Application Considerations For Bulletin 700-SC
Connection
For DC Load Switching, Bulletin 700-SC will operate properly if the load is connected to either the positive or negative SSR load terminal.
High-density Mounting of Multiple SSRs
If multiple relays are mounted side by side, be aware that the outer wall of each SSR works as a radiator.
TheSSR casing servesto dissipate heat. Install the relaysso that theyareadequatelyventilated. Ifpoor ventilationisunavoidable, reducetheload currentbyhalf.
Protective Component
When controlling AC inductive loads, connect an inrush/surge absorbing device (varistor) across the SSR load terminals. If the SSR has built-in surge
suppression (Bulletins 700-SE and 700-SH) and additional surge suppression is required, connect the varistor across the terminals of the load device . Select
a varistor that meets the conditions of the load voltage outlined in the table below. Note: For additional details applying solid-state relays, refer to pub. number
700-AT001A-EN-E, "Solid-State Relay Application Guide." Document available at www.theautomationbookstore.com.
Load Voltage
100…120V AC
200…240V AC
380…480V AC
Varistor Voltage
240…270 V
Varistor Surge Resistance
440…470 V
1000 A min.
820…1000 V
41
相关型号: