3DU20R [ALTECH]

Thermal Magnetic Circuit Breaker,;
3DU20R
型号: 3DU20R
厂家: ALTECH CORPORATION    ALTECH CORPORATION
描述:

Thermal Magnetic Circuit Breaker,

电路保护
文件: 总8页 (文件大小:672K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
R-Series  
UL1077 Recognized  
Supplementary  
Protector  
DIN Rail Mounted  
17.5mm width per pole  
Thermal Magnetic  
480Y/277V AC, 50/60Hz  
10kA Short Circuit  
Withstand Capacity  
Positive Trip indicator  
(Green - off/tripped, Red - on)  
Applications (on the load side  
of Branch Circuit Protection)  
include: Sensitive Electronics,  
Power Supplies, Appliance  
circuits, etc.  
E301611  
Indicator  
window  
480Y/277VAC  
Voltage Rating  
0.5-6A (RC): 10kA with no back-up fuse  
8-63A (RC): 10kA with UL-listed  
Short Circuit Withstand Rating  
(UL - Ratings)  
Class J back-up fuse; 5kA with no back-up fuse  
ON  
0.5-63A (RC): 10kA  
Interrupting Capacity  
(IEC/EN60898/60947-2)  
30°C (86°F)  
Calibration Temperature  
Operating Temperature  
Storage Temperature  
Terminal Size Acceptability  
and Torque  
OFF  
-25° to 60°C (-13° to 140°F)  
-25° to 75°C (-13° to 167°F)  
14-3 AWG: 17.5 lb-in. (2.0 Nm)  
18-16 AWG: 25 lb-in. (2.8 Nm)  
IP20 at front  
Trip curve  
and amperage  
window display.  
Terminal Protection Degree  
Electrical Life  
6,000 cycles on/off  
10,000 cycles on/off  
Mechanical Life  
copper wire only 60/75°C  
3g (18-50Hz)  
Wire Connection  
Vibration Resistance  
In any plane  
Mounting Orientation  
short CirCuit WithstanD ratinGs for r-series suppleMentary proteCtor  
Backup Protection  
Trip  
Curve  
Amp  
Range  
UL-Listed  
Class J Fuse  
up to 10kA  
No Backup Fuse  
Required  
up to:  
All  
0.5 - 6A  
8 - 63A  
4xRC*  
10kA  
All  
4xRC*  
5kA  
*up to nearest rated current  
DC voltage rating: 48 VDC (self-certified).  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com  
62  
60  
40  
Time  
10  
4
versus  
1
Current Trip Curve  
10  
4
For the exact trip curve,  
please refer to page 67.  
1
0.4  
Dimensions in mm  
side view  
B
C
DD  
-1  
10  
-2  
4x10  
-2  
-3  
10  
4x10  
45 (1.77 in.)  
-3  
10  
2
3
4
6 8 101620  
Multiple of Rated Current  
6.5 (0.26 in.)  
44 (1.73 in.)  
60 (2.36 in.)  
77 (3.03 in.)  
1 POlE  
2 POlE  
3 POlE  
17.5 (0.69 in.)  
35 (1.38 in.)  
52.5 (2.07 in.)  
Trip-Characteristics*  
Applications  
Characteristic Trip Boundaries  
Lighting  
Business  
Equipment  
Wiring  
Protection  
Control  
Power  
General  
Reactive  
Load  
Thermal Trip  
Magnetic Trip  
Transformers Supplies Electronics  
Control  
Circuits  
Appliances  
Must not Must Trip Must not Must Trip  
Trip>100ms  
<1hr  
Trip>100ms at 100ms  
B-Characteristics  
1.45xRC 3xRC  
C-Characteristics  
1.45xRC 5xRC  
D-Characteristics  
1.45xRC 10xRC  
1.13xRC  
1.13xRC  
5xRC  
10xRC  
1.13xRC  
20xRC  
*The value of each characteristic is shown vertically beneath its corresponding heading.  
Warning!  
This information should only be used as a selection guide.The use of a Miniature Circuit Breaker/Supplementary Protector  
in an application with a certainTrip-Characteristic always requires prototype testing! It is the responsibility of the circuit  
design engineer to select the appropriate Miniature Circuit Breaker/Supplementary Protector for his specific application.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com  
63  
Application Examples:  
B-Trip  
Characteristic  
Business equipment, wiring protection,  
lighting, appliances, control circuits and  
some electronic applications. Relatively  
long thermal trip delay but low magnetic  
trip point.  
E301611  
Rated  
Current  
0.5A  
1.0A  
2.0A  
3.0A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
12A  
13A  
15A  
16A  
20A  
25A  
30A  
32A  
40A  
50A  
60A  
63A  
Type/  
Cat. No.  
1BU05R  
1BU1R  
1BU2R  
1BU3R  
1BU4R  
1BU5R  
1BU6R  
1BU8R  
1BU10R  
1BU12R  
1BU13R  
1BU15R  
1BU16R  
1BU20R  
1BU25R  
1BU30R  
1BU32R  
1BU40R  
1BU50R  
1BU60R  
1BU63R  
Rated  
Current  
0.5A  
1.0A  
2.0A  
3.0A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
12A  
13A  
15A  
16A  
20A  
25A  
30A  
32A  
Type/  
Cat. No.  
2BU05R  
2BU1R  
2BU2R  
2BU3R  
2BU4R  
2BU5R  
2BU6R  
2BU8R  
2BU10R  
2BU12R  
2BU13R  
2BU15R  
2BU16R  
2BU20R  
2BU25R  
2BU30R  
2BU32R  
2BU40R  
2BU50R  
2BU60R  
2BU63R  
One Pole  
Two Pole  
40A  
50A  
60A  
63A  
Standard Pack: 12  
Standard Pack: 6  
Weight:  
Weight:  
0.5A - 63A: 1.6kg (3.54 lb.)  
0.5A - 63A: 1.6kg (3.54 lb.)  
Rated  
Current  
0.5A  
1.0A  
2.0A  
3.0A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
12A  
13A  
15A  
16A  
20A  
25A  
30A  
32A  
Type/  
Cat. No.  
3BU05R  
3BU1R  
3BU2R  
3BU3R  
3BU4R  
3BU5R  
3BU6R  
3BU8R  
3BU10R  
3BU12R  
3BU13R  
3BU15R  
3BU16R  
3BU20R  
3BU25R  
3BU30R  
3BU32R  
3BU40R  
3BU50R  
3BU60R  
3BU63R  
Four Pole  
Please contact  
Altech.  
Three Pole  
40A  
50A  
60A  
63A  
Standard Pack: 4  
Weight:  
0.5A - 63A: 1.66kg (3.67 lb.)  
Non-standard current ratings available. Minimum quantities may apply. Please contact Altech for further details.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com  
64  
Application Examples:  
C-Trip  
Characteristic  
Lighting, wiring protection, appliances,  
business equipment, and control circuit  
applications. Relatively long thermal trip  
delay and medium magnetic trip point.  
E301611  
Rated  
Type/  
Rated  
Current  
0.5A  
1.0A  
2.0A  
3.0A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
12A  
13A  
15A  
16A  
20A  
25A  
30A  
32A  
Type/  
Cat. No.  
2CU05R  
2CU1R  
2CU2R  
2CU3R  
2CU4R  
2CU5R  
2CU6R  
2CU8R  
2CU10R  
2CU12R  
2CU13R  
2CU15R  
2CU16R  
2CU20R  
2CU25R  
2CU30R  
2CU32R  
2CU40R  
2CU50R  
2CU60R  
2CU63R  
Current  
0.5A  
1.0A  
2.0A  
3.0A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
12A  
13A  
15A  
16A  
20A  
25A  
30A  
32A  
Cat. No.  
1CU05R  
1CU1R  
1CU2R  
1CU3R  
1CU4R  
1CU5R  
1CU6R  
1CU8R  
1CU10R  
1CU12R  
1CU13R  
1CU15R  
1CU16R  
1CU20R  
1CU25R  
1CU30R  
1CU32R  
1CU40R  
1CU50R  
1CU60R  
1CU63R  
One Pole  
Two Pole  
40A  
50A  
60A  
63A  
40A  
50A  
60A  
63A  
Standard Pack: 12  
Standard Pack: 6  
Weight:  
Weight:  
0.5A - 63A: 1.6kg (3.54 lb.)  
0.5A - 63A: 1.6kg (3.54 lb.)  
Rated  
Current  
0.5A  
1.0A  
2.0A  
3.0A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
12A  
13A  
15A  
16A  
20A  
25A  
30A  
32A  
Type/  
Cat. No.  
3CU05R  
3CU1R  
3CU2R  
3CU3R  
3CU4R  
3CU5R  
3CU6R  
3CU8R  
3CU10R  
3CU12R  
3CU13R  
3CU15R  
3CU16R  
3CU20R  
3CU25R  
3CU30R  
3CU32R  
3CU40R  
3CU50R  
3CU60R  
3CU63R  
Four Pole  
Please contact  
Altech.  
Three Pole  
40A  
50A  
60A  
63A  
Standard Pack: 4  
Weight:  
0.5A - 63A: 1.66kg (3.67 lb.)  
Non-standard current ratings available. Minimum quantities may apply. Please contact Altech for further details.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com  
65  
Application Examples:  
D-Trip  
Characteristic  
Control transformers, power supplies and  
reactive loads. Relatively long thermal trip  
delay and very high magnetic trip point.  
E301611  
Rated  
Type/  
Cat. No.  
1DU05R  
1DU1R  
1DU2R  
1DU3R  
1DU4R  
1DU5R  
1DU6R  
1DU8R  
1DU10R  
1DU12R  
1DU13R  
1DU15R  
1DU16R  
1DU20R  
1DU25R  
1DU30R  
1DU32R  
1DU40R  
1DU50R  
1DU60R  
1DU63R  
Rated  
Current  
0.5A  
1.0A  
2.0A  
3.0A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
12A  
13A  
15A  
16A  
20A  
25A  
30A  
32A  
Type/  
Cat. No.  
2DU05R  
2DU1R  
2DU2R  
2DU3R  
2DU4R  
2DU5R  
2DU6R  
2DU8R  
2DU10R  
2DU12R  
2DU13R  
2DU15R  
2DU16R  
2DU20R  
2DU25R  
2DU30R  
2DU32R  
2DU40R  
2DU50R  
2DU60R  
2DU63R  
Current  
0.5A  
1.0A  
2.0A  
3.0A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
12A  
13A  
15A  
16A  
20A  
25A  
30A  
32A  
One Pole  
Two Pole  
40A  
50A  
60A  
63A  
40A  
50A  
60A  
63A  
Standard Pack: 12  
Standard Pack: 6  
Weight:  
Weight:  
0.5A - 63A: 1.6kg (3.54 lb.)  
0.5A - 63A: 1.6kg (3.54 lb.)  
Rated  
Current  
0.5A  
1.0A  
2.0A  
3.0A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
12A  
13A  
15A  
16A  
20A  
25A  
30A  
32A  
Type/  
Cat. No.  
3DU05R  
3DU1R  
3DU2R  
3DU3R  
3DU4R  
3DU5R  
3DU6R  
3DU8R  
3DU10R  
3DU12R  
3DU13R  
3DU15R  
3DU16R  
3DU20R  
3DU25R  
3DU30R  
3DU32R  
3DU40R  
3DU50R  
3DU60R  
3DU63R  
Four Pole  
Please contact  
Altech.  
Three Pole  
40A  
50A  
60A  
63A  
Standard Pack: 4  
Weight:  
0.5A - 63A: 1.66kg (3.67 lb.)  
Non-standard current ratings available. Minimum quantities may apply. Please contact Altech for further details.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com  
66  
R-Series Trip Curves  
B, C and D Trip  
Less than 10A  
120  
B, C and D Trip  
10A and higher  
7200  
60  
40  
3600  
2400  
20  
1200  
10  
600  
480  
360  
240  
8
6
4
2
120  
1
60  
40  
40  
20  
10  
5
20  
10  
5
1
1
0.5  
0.5  
0.1  
0.05  
0.1  
0.05  
B C D  
B C D  
0.01  
0.01  
1
2
3
4
5
6
7 8 9 10 12 1416 20  
1
2
3
4
5
6
7 8 9 10 12 1416 20  
1.13 1.45  
1.13 1.45  
Multiple of Rated Current  
Multiple of Rated Current  
Temperature and Power Loss Specifications  
Internal Impedances & Power Loss  
MCBTemperature Compensation  
Rated  
Power  
loss on  
CB  
Maximumallowable  
impedanceof  
breakdown loop(0.2/0.4s)  
current  
of MCB  
Internal  
impedance  
E!ective rated current allowing for ambient temperature.  
Z s ( Ω)  
Z (m Ω)  
P (W)  
I cor (A)  
I
n
(A)  
Ambient Temperature  
Char.  
B,C,D  
Char.  
B,C,D  
Char.B Char.C Char.D  
-20°C -10°C 0°C  
10°C  
0.55  
1.10  
2.20  
3.30  
4.40  
6.60  
8.80  
20°C  
0.53  
1.05  
2.10  
3.15  
4.20  
6.30  
8.40  
30°C  
0.50  
1.00  
2.00  
3.00  
4.00  
6.00  
8.00  
40°C  
0.47  
0.93  
1.86  
2.79  
3.72  
5.60  
7.40  
9.30  
50°C  
0.44  
0.88  
1.76  
2.64  
3.52  
5.30  
7.00  
8.80  
60°C  
0.42  
0.83  
1.67  
2.50  
3.33  
5.00  
6.70  
8.30  
0.50  
1.00  
2.00  
3.00  
4.00  
6.00  
8.00  
6600  
1650  
370  
210  
126  
51  
1.7  
1.7  
1.5  
1.9  
2.0  
1.8  
1.3  
1.5  
1.9  
1.9  
2.5  
2.8  
3.2  
4.0  
5.5  
6.4  
42.0  
46.0  
23.0  
15.3  
11.5  
7.7  
51.1  
25.6  
12.8  
8.5  
6.4  
4.3  
3.2  
2.6  
2.0  
1.6  
1.3  
1.0  
0.8  
0.6  
0.5  
0.4  
28.8  
14.4  
7.2  
4.8  
3.6  
2.4  
1.8  
1.4  
1.1  
0.9  
0.7  
0.6  
0.4  
0.4  
0.3  
0.2  
0.61  
1.21  
2.42  
3.63  
4.84  
7.30  
9.70  
12.1  
15.7  
19.4  
24.2  
30.3  
38.7  
48.4  
60.5  
76.2  
0.59  
1.18  
2.36  
3.54  
4.72  
7.10  
9.40  
11.8  
15.3  
18.9  
0.57  
1.14  
2.28  
3.42  
4.56  
6.80  
9.10  
21  
5.8  
10.00  
13.00  
16.00  
20.00  
25.00  
32.00  
40.00  
50.00  
63.00  
14.8  
11.3  
7.5  
4.6  
11.40 11.00 10.50 10.00  
3.5  
14.80 14.30 13.70 13.00 12.10 11.50 10.80  
18.20 17.60 16.80 16.00 14.90 14.10 13.30  
2.9  
6.3  
2.3  
23.60 22.80 22.00 21.00 20.00 18.60 17.60 16.70  
29.50 28.50 27.50 26.30 25.00 23.30 22.00 20.80  
37.80 36.50 35.20 33.60 32.00 29.80 28.20 26.70  
47.20 45.60 44.00 42.00 40.00 37.20 35.20 33.30  
4.4  
1.8  
3.1  
1.4  
2.5  
1.2  
2.2  
0.9  
59.0  
57.00 55.00 52.50 50.00 46.50 44.10 41.70  
1.6  
0.7  
74.30 71.80 69.30 66.20 63.00 58.60 55.50 52.50  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com  
67  
Accessories  
Accessories can be factory or field mounted on R-Series supplementary protectors for enhanced  
control and monitoring capabilities. Field mounting kits include all necessary parts and instruc-  
tions. Accessories can be gang mounted on a single controller (the Auxiliary Switch in the  
outside position). The mounting arrangement links the internal latch-pins for the tripping  
mechanisms, ensuring simultaneous trips. Handles are linked to simplify manual resetting.  
R-Series  
Supplementary  
Protector  
E301611  
Neutral  
Pole  
(63A/480Y/277 VAC)  
Description  
Type/  
Cat. No.  
ALTN2  
Cable  
Cable  
Min  
Torque  
Max  
2Nm  
Torque  
Min  
1.5Nm  
Max  
Neutral  
25mm2  
AWG 3  
2.5mm2  
AWG 12  
17.5 lb-in  
12 lb-in  
Standard Pack: 10  
Weight: 1.25kg (2.77 lb.)  
Shunt Trip and  
Undervoltage Trip  
Description  
Shunt Trip  
Type/Cat. No.  
Operational  
Voltage  
Rated  
Coil Current  
Undervoltage Trip*  
Type/Cat. No.  
AC Coil:  
12V AC  
24V AC  
48V AC  
60V AC  
110V AC  
120V AC  
230V AC  
277V AC  
400V AC  
DC Coil:  
12V DC  
24V DC  
48V DC  
110V DC  
FA12ACR  
FA24ACR  
FA48ACR  
FA60ACR  
FA110ACR  
FA120ACR  
FA230ACR  
FA277ACR  
FA400ACR  
8.4 - 13.2V  
16.8 - 26.4V  
33.6 - 52.8V  
42 - 66V  
77 - 121V  
84 - 132V  
161 - 253V  
194 - 305V  
280 - 440V  
6A  
UV12ACR  
UV24ACR  
UV48ACR  
UV60ACR  
UV110ACR  
UV120ACR  
UV230ACR  
UV277ACR  
UV400ACR  
2.8A  
0.8A  
~0.7A  
0.5A  
~0.5A  
0.6A  
~0.5A  
0.5A  
Shunt Trip  
FA12DCR  
FA24DCR  
FA48DCR  
FA110DCR  
8.4 - 13.2V  
16.8 - 26.4V  
33.6 - 52.8V  
77 - 121V  
~6A  
3A  
2A  
UV12DCR  
UV24DCR  
UV48DCR  
UV110DCR  
0.6A  
* Reset-Hold Voltage = 0.85 x V ; Drop-Out Voltage = 0.2 x V  
E
E
Undervoltage Trip  
Standard Pack: 10  
Weight: 1.1kg (2.43 lb.)  
Terminal Size - min/max  
2.5 mm2 (12 AWG) / 25mm2 (3 AWG)  
1.5 Nm (12 lb. in.) / 2 Nm (17.5 lb. in.)  
Terminal Torque - min/max  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com  
68  
Auxiliary  
Contact  
(4A/230 VAC)  
Description  
Type/  
Cat. No.  
H1COR  
Cable  
Max  
Cable  
Min  
Torque  
Max  
Torque  
Min  
1 x CO  
2 x CO  
2.5mm2  
AWG 12  
0.5mm2  
AWG 20  
0.5Nm  
4 lb-in  
0.33Nm  
3 lb-in  
H2COR  
1 x CO, 1 Signal HSTCOR  
& Test Button  
Standard Pack: 15  
Weight: H1COR: 0.5kg (1.32 lb.); H2COR, HSTCOR: 0.72kg (1.59 lb.)  
Wiring  
Diagram  
H1COR  
H2COR  
HSTCOR  
Regular  
Auxiliary Supplementary  
Auxiliary Supplementary  
Supplementary  
Protector  
Signal  
Switch  
Auxiliary  
Switch  
Switch  
Protector  
Switch  
Protector  
11  
1
95  
11  
1
95  
96  
11  
1
14 12  
98  
96  
14 12  
98  
14 12  
>
2
>
>
2
2
luggage  
lock  
Lock-out Adapter  
Description  
Type/  
Cat. No.  
EASS2  
Yellow  
Standard Pack: 10  
Weight: 50g (1.76 oz.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • P 908.806-9400 • F 908.806.9490 • www.altechcorp.com  
69  

相关型号:

3DU25L

Thermal Magnetic Circuit Breaker,
ALTECH

3DU2R

Thermal Magnetic Circuit Breaker,
ALTECH

3DU3

Thermal Magnetic Circuit Breaker,
ALTECH

3DU30L

Thermal Magnetic Circuit Breaker,
ALTECH

3DU30R

Thermal Magnetic Circuit Breaker,
ALTECH

3DU32

Thermal Magnetic Circuit Breaker,
ALTECH

3DU32L

Thermal Magnetic Circuit Breaker,
ALTECH

3DU3R

Thermal Magnetic Circuit Breaker,
ALTECH

3DU40

Thermal Magnetic Circuit Breaker,
ALTECH

3DU41

SILICON DIFFUSED TYPE (SWITCHING TYPE POWER SUPPLY APPLICATIONS)
TOSHIBA

3DU4R

Thermal Magnetic Circuit Breaker,
ALTECH

3DU5

D-TRIP CHARACTERISTICS
ALTECH