MINIATURE CIRCUIT BREAKERS (MCBs)  
UL Recognized Supplementary Protectors vs. UL Listed Manual Motor Controllers  
I
I
D4A  
D 16A  
10kA  
277V AC  
277V AC  
10000  
LISTED  
4C87  
0
0
1D4.0  
1DU16  
®
UL Recognized  
UL Listed  
UL Recognized one pole supplementary protector  
UL Listed one pole manual motor controller  
General  
The UL recognized component mark on the MCB means that the  
component alone meets the requirements for a limited, specific use. These  
MCBs are not intended for separate installation in the field, they are  
intended for use as a component of complete equipment submitted for  
investigation to UL.  
The UL Listed mark on the MCB is the manufacturer’s representation that  
samples of the complete product have been tested by UL to be used for  
most common industrial applications. This superior UL mark allows for field  
installation without the need for UL investigation.  
Classifications  
UL 508  
UL 1077  
Industrial Control Equipment  
Supplementary protectors for use in electrical equipment  
Manual motor controllers suitable as motor disconnect  
Field Installations  
None  
A licensed electrician can install Manual Motor Controllers for the following uses:  
Must be submitted as component of complete equipment for  
investigation to UL  
AC Motor Starting (Across the line)  
AC General Use  
AC Resistance  
AC Discharge Lamps (Ballast)  
AC Incandescent Lamps (Tungsten)  
Motor Branch Circuit Uses (in accordance with NEC® Section 430)  
Manual Motor Controller  
None  
Disconnect Means/ Disconnect Switch  
Controller and Overload Protection Combination  
Controller and Disconnect Means Combination  
Interchangeability  
A UL Recognized supplementary protector cannot be used in place of UL  
Listed Manual Motor Controller for a specific application  
A UL Listed Manual Motor Controller can be used in place of UL Recognized  
supplementary protector, where UL allowed to use a supplementary  
protector for a specific application.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
4
Simplified Guidelines for Motor Branch Circuits  
®
as per National Electrical Code® (NEC ) Section 430  
BASIC ELEMENTS OF A  
MOTOR LOAD CIRCUIT  
SUGGESTED USES FOR  
V-EA AND MA-MCBs/  
MANUAL MOTOR CONTROLLERS  
Branch-Circuit Short Circuit (Part D) (430-(51-58))  
and Ground-Fault Protection  
(a circuit breaker or fuse)  
V-EA Series Uses:  
5
4
4
• Disconnect Means  
3
• Controller  
• Combination of Controller  
and Overload Protection  
• Combination of Controller and  
2
3
&
Disconnecting Means (430-109 (a) (6))  
(a motor-circuit switch rated in hp or a circuit breaker)  
3
4
Disconnecting Means  
&
Note:  
For Combination of Controller, Disconnecting  
2
3
,
Means and Overload Protection  
,
Controller (Part G) (430-(81-91))  
(any device normally used to start and stop a motor)  
4
&
please check with the  
3
local NEC® inspector for your area.  
Overload Protection (Part C) (430-(31-44))  
(a device with bimetallic elements or eutetic material  
unless the motor is protected by other approval means)  
MA Series Uses:  
2
1
3
• Controller  
• Combination of Controller and  
2
3
Conductors (Part B) (430-(21-29))  
(copper conductors unless identified for use with a  
different conductor)  
Overload Protection  
&
Note:  
Additional short circuit protection is  
provided by the integral magnetic trip  
feature.  
M
®
Please check if NEC will permit a combination of these  
Although these elements are shown separately, there  
are certain cases where the code will permit a single  
device to serve more than one function.  
elements for your specific applications in a single  
device.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
5
V-EA MINIATURE CIRCUIT BREAKER/MANUAL MOTOR CONTROLLER  
TRIP CURVE SELECTION GUIDE  
Warning!  
This information should only be used as a selection guide. The use of a Miniature Circuit Breaker/Manual Motor Controller  
in an application with a certain Trip-Characteristic always requires prototype testing! It is the responsibility of the circuit  
design engineer to select the appropriate Miniature Circuit Breaker/Manual Motor Controller for his specific application.  
Trip-Characteristics*  
Applications  
Characteristic Trip Boundaries  
Lighting  
Wiring  
Protection Equipment  
Business  
Appliances  
Control Transformers  
Circuits  
Power  
Supplies  
Thermal Trip  
Magnetic Trip  
Must not  
Trip>100ms  
Must Trip  
<1hr  
Must not  
Trip>100ms at 100ms  
Must Trip  
B-Characteristics  
1.45xRC 3xRC  
C-Characteristics  
1.45xRC 5xRC  
D-Characteristics  
1.45xRC 10xRC  
E-Characteristics  
1.35xRC 14xRC  
G-Characteristics  
1.35xRC 8xRC  
Z-Characteristics  
1.35xRC 2xRC  
Pages  
8-9  
Pages  
8-9  
Pages  
8-9  
Pages  
8-9  
Pages  
8-9  
1.13xRC  
1.13xRC  
5xRC  
Pages  
10-11  
Pages  
10-11  
Pages  
10-11  
Pages  
10-11  
Pages  
10-11  
10xRC  
Pages  
12-13  
Pages  
12-13  
1.13xRC  
1.05xRC  
16xRC  
18xRC  
Pages  
16-17  
Pages  
16-17  
Pages  
16-17  
Pages  
16-17  
1.05xRC  
1.05xRC  
10xRC  
3xRC  
*The value of each characteristic is shown vertically beneath its corresponding heading.  
TIME VERSUS CURRENT TRIP CURVE  
60  
40  
10  
4
1
10  
4
For the exact trip curve, please refer  
to appropriate catalog pages.  
1
0.4  
Z
B
CG D E  
-1  
-2  
10  
4x10  
-2  
-3  
10  
4x10  
-3  
10  
2
3
4
6 8 101620  
Multiple of Rated Current  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
6
Approvals/Standards:  
USA  
Canada  
Germany  
Europe  
International  
Applications  
Heaters  
General  
General  
Electronics  
High  
Solenoid  
Semi-  
conductors  
Components/  
devices with  
low surge-  
current and  
short circuit  
withstand  
Reactive  
Load  
Motors  
Low  
Inrush  
High  
Inrush  
Efficiency  
capabilities  
Pages  
8-9  
Pages  
10-11  
Pages  
12-13  
Pages  
12-13  
Pages  
12-13  
Pages  
14-15  
Pages  
16-17  
Pages  
16-17  
Pages  
16-17  
Pages  
18-19  
Pages  
18-19  
Pages  
18-19  
508 listed  
C22.2 No.14 certified  
UL file E137938  
CSA file LR104391  
Manual Motor Controller  
“Suitable as Motor Disconnect”  
AC Motor Starting, Across the Line  
AC General Use  
AC Resistance  
AC Discharge Lamps (Ballast)  
AC Incandescent Lamps (Tungsten)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
7
ONE POLE  
ONE POLE PLUS NEUTRAL  
B-TRIP  
CHARACTERISTICS  
Application Examples:  
Business  
equipment,  
wiring  
protection, lighting, appliances, control  
circuits, some motors and some  
electronic applications. Relatively long  
thermal trip delay but low magnetic trip  
point.  
1B  
2BN  
Rated  
Type/  
Type/  
Current  
Cat. No.  
Approvals  
Cat. No.  
Approvals  
U
U
L
L
0.3A  
0.5A  
0.75A  
1BU03  
1BU05  
1BU075  
NA  
2BNU03  
2BNU05  
2BNU075  
NA  
2BNU1  
2BNU1.6  
2BNU2  
2BNU2.5  
2BNU3  
2BNU3.5  
2BNU4  
2BNU5  
2BNU6  
NA  
Type Designation  
U
U
L
L
U
U
L
L
2
B
N
U
60  
0.8A  
(a) (b) (c) (d) (e)  
U
U
L
L
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
1BU1  
1BU1.6  
1BU2  
1BU2.5  
1BU3  
1BU3.5  
1BU4  
1BU5  
1BU6  
NA  
U
U
L
L
(a) = Number of Poles  
U
U
L
L
(b) = Trip Characteristic  
(c) = Blank: without neutral pole  
U
U
L
L
U
U
L
L
U
U
L
L
= N:  
(d) = U:  
= R:  
with neutral pole  
UL/CSA version  
ring tongue terminals,  
UL/CSA version  
U
U
L
L
U
U
L
L
U
U
L
L
U
U
2BNU10  
L
= Blank: European version  
L
1BU10  
NA  
NA  
NA  
(e) = Rated Current  
12A  
NA  
12.5A  
13A  
U
U
L
L
2BNU13  
2BNU15  
2BNU16  
2BNU20  
2BNU25  
2BNU30  
2BNU32  
2BNU40  
2BNU50  
2BNU60  
2BN63  
1BU13  
1BU15  
1BU16  
1BU20  
1BU25  
1BU30  
1BU32  
1BU40  
1BU50  
1BU60  
1B63  
U
U
L
L
15A  
U
U
L
L
16A  
20A  
25A  
U
U
L
L
U
U
L
L
U
U
L
L
30A  
Approvals:  
U
U
L
L
32A  
40A  
50A  
60A  
63A  
U
U
L
L
U
U
L
L
UL508 Listed  
VDE pending  
U
L
U
L
277VAC  
277VAC  
Voltage Rating  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
Interrupting Capacity  
(UL/CSA - Ratings)  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
Group Short Circuit  
(UL/CSA - Ratings)  
0.3-63A (RC): 10kA  
0.3-63A (RC): 10kA  
Interrupting Capacity (VDE - Ratings)  
10000 ON/OFF operations  
10000 ON/OFF operations  
Mechanical Endurance  
Calibration Temperature  
Standard Pack and Weight  
40°C (104°F)  
40°C (104°F)  
10/0.3A - 32A = 1.4kg (3.1 lb.)  
40A - 63A = 1.6kg (3.5 lb.)  
5/0.3A - 32A = 1.3kg (2.9 lb.)  
40A - 63A = 1.45kg (3.2 lb.)  
Terminal Size Acceptability  
Terminal Torque  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Basic Dimensions (Elevation View)  
Not European standard rating.  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
Please refer to page 21 for specific  
applications.  
DC rating (Manufacturer’s self certification):  
One pole 48VDC, two pole series 125VDC  
17.5 mm (0.69 in.)  
35 mm (1.38 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
8
TWO POLE  
THREE POLE  
Basic Dimensions (side view)  
35 mm  
(1.38 in.)  
3B  
2B  
Type/  
70 mm (2.76 in.)  
Rated  
Type/  
Current  
Cat. No.  
Approvals  
Cat. No.  
Approvals  
V-EA-B Trip  
0.3A Through 10A Rated Current  
U
U
L
1.13-1.45xIN  
L
3BU03  
3BU05  
3BU075  
NA  
0.3A  
0.5A  
0.75A  
2BU03  
2BU05  
2BU075  
NA  
60  
40  
U
U
L
L
U
U
L
L
10  
0.8A  
Thermal Overload  
“Must Trip” < 1 hr = 145% RC  
4
U
U
L
3BU1  
3BU1.6  
3BU2  
3BU2.5  
3BU3  
3BU3.5  
3BU4  
3BU5  
3BU6  
NA  
L
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
2BU1  
2BU1.6  
2BU2  
2BU2.5  
2BU3  
2BU3.5  
2BU4  
2BU5  
2BU6  
NA  
“Must Not Trip” > 1 hr = 113% RC  
U
U
L
1
L
U
U
L
L
10  
4
U
U
L
L
U
U
L
L
U
U
L
L
1
U
U
L
L
0.4  
U
U
L
L
U
10-1  
U
L
L
4x10-2  
U
U
L
L
3BU10  
10-2  
2BU10  
NA  
NA  
NA  
NA  
4x10-3  
12A  
12.5A  
13A  
10-3  
U
U
L
1
2
3
4
5 6 8 10  
20  
40  
100  
3BU13  
3BU15  
3BU16  
3BU20  
3BU25  
3BU30  
3BU32  
3BU40  
3BU50  
3BU60  
3B63  
L
2BU13  
2BU15  
2BU16  
2BU20  
2BU25  
2BU30  
2BU32  
2BU40  
2BU50  
2BU60  
2B63  
U
U
L
Multiple of Rated Current  
L
15A  
U
U
L
L
16A  
20A  
25A  
V-EA-B Trip  
U
U
L
L
13A Through 63A Rated Current  
U
U
L
L
1.13-1.45xIN  
U
60  
40  
U
L
L
30A  
U
U
L
L
32A  
40A  
50A  
10  
U
U
L
L
Thermal Overload  
Must Trip< 1 hr = 145% RC  
Must Not Trip> 1 hr = 113% RC  
4
U
U
L
L
U
60A  
U
L
1
L
63A  
10  
4
480Y/277VAC  
480Y/277VAC  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
1
0.4  
10-1  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
4x10-2  
0.3-63A (RC): 10kA  
0.3-63A (RC): 10kA  
10-2  
4x10-3  
10000 ON/OFF operations  
10000 ON/OFF operations  
10-3  
40°C (104°F)  
40°C (104°F)  
1
2
3
4
5 6 8 10  
20  
40  
100  
5/1.4kg (3.1 lb.)  
4/1.68kg (3.7 lb.)  
Multiple of Rated Current  
“B” Magnetic Trip Parameters  
Rated current 0.3A to 63A.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
1. Hold for a minimum of 100ms at surge  
of 3 times rated current.  
2. Trip in under 100ms at 5 times rated  
current.  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
NB: Trip curves shown comply with North  
American standards. For trip curves  
according to European standards please  
consult Altech.  
35 mm (1.38 in.)  
52.5 mm (2.07 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
9
C-TRIP  
ONE POLE  
ONE POLE PLUS NEUTRAL  
CHARACTERISTICS  
Application Examples:  
Low inrush motors, lighting, wiring  
protection, appliances, business  
equipment, and control circuit  
applications. Relatively long thermal  
trip delay and medium magnetic trip  
point.  
1C  
2CN  
Rated  
Type/  
Type/  
Current  
Cat. No.  
Approvals  
Cat. No.  
Approvals  
Type Designation  
U
L
U
L
0.3A  
0.5A  
0.75A  
1CU03  
1CU05  
1CU075  
NA  
2CNU03  
2CNU05  
2CNU075  
NA  
U
U
L
L
2
C
N
U
60  
U
U
L
L
(a) (b) (c) (d) (e)  
0.8A  
U
U
L
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
1CU1  
1CU1.6  
1CU2  
1CU2.5  
1CU3  
1CU3.5  
1CU4  
1CU5  
1CU6  
1CU8  
1CU10  
NA  
2CNU1  
2CNU1.6  
2CNU2  
2CNU2.5  
2CNU3  
2CNU3.5  
2CNU4  
2CNU5  
2CNU6  
2CNU8  
2CNU10  
NA  
L
(a) = Number of Poles  
U
U
L
L
(b) = Trip Characteristic  
(c) = Blank: without neutral pole  
U
U
L
L
U
U
L
L
U
U
L
L
= N:  
(d) = U:  
= R:  
with neutral pole  
UL/CSA version  
ring tongue terminals,  
UL/CSA version  
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
= Blank: European version  
U
U
L
L
(e) = Rated Current  
12A  
12.5A  
13A  
NA  
NA  
U
U
L
1CU13  
1CU15  
1CU16  
1CU20  
1CU25  
1CU30  
1CU32  
1CU40  
1CU50  
1CU60  
1C63  
L
2CNU13  
2CNU15  
2CNU16  
2CNU20  
2CNU25  
2CNU30  
2CNU32  
2CNU40  
2CNU50  
2CNU60  
2CN63  
U
U
L
15A  
16A  
20A  
25A  
30A  
32A  
40A  
50A  
60A  
63A  
L
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
Approvals:  
U
U
L
L
U
U
L
L
U
U
L
L
UL508 Listed  
VDE pending  
U
U
L
L
277VAC  
Voltage Rating  
277VAC  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
Interrupting Capacity  
(UL/CSA - Ratings)  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
Group Short Circuit  
(UL/CSA - Ratings)  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
Interrupting Capacity (VDE - Ratings)  
Mechanical Endurance  
0.3-63A (RC): 10kA  
0.3-63A (RC): 10kA  
10000 ON/OFF operations  
10000 ON/OFF operations  
Calibration Temperature  
40°C (104°F)  
40°C (104°F)  
Standard Pack and Weight  
5/0.3A - 32A = 1.3kg (2.9 lb.)  
40A - 63A = 1.45kg (3.2 lb.)  
10/0.3A - 32A = 1.4kg (3.1 lb.)  
40A - 63A = 1.6kg (3.5 lb.)  
Terminal Size Acceptability  
Terminal Torque  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Basic Dimensions (Elevation View)  
Not European standard rating.  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
Please refer to page 21 for specific  
applications.  
DC rating (Manufacturer’s self certification):  
One pole 48VDC, two pole series 125VDC  
17.5 mm (0.69 in.)  
35 mm (1.38 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
10  
TWO POLE  
THREE POLE  
Basic Dimensions (side view)  
35 mm  
(1.38 in.)  
70 mm (2.76 in.)  
2C  
3C  
V-EA-C Trip  
Rated  
Current Cat. No.  
Type/  
Type/  
Cat. No.  
0.3A Through 10A Rated Current  
Approvals  
Approvals  
1.13-1.45xIN  
60  
40  
U
L
U
L
0.3A  
0.5A  
0.75A  
2CU03  
2CU05  
2CU075  
NA  
2CU1  
2CU1.6  
2CU2  
2CU2.5  
2CU3  
2CU3.5  
2CU4  
2CU5  
2CU6  
3CU03  
3CU05  
3CU075  
NA  
3CU1  
3CU1.6  
3CU2  
3CU2.5  
3CU3  
3CU3.5  
3CU4  
3CU5  
3CU6  
U
U
L
L
10  
Thermal Overload  
Must Trip< 1 hr = 145% RC  
Must Not Trip> 1 hr = 113% RC  
U
U
L
4
L
0.8A  
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
1
U
U
L
L
U
U
L
L
10  
4
U
U
L
L
U
U
L
L
1
U
U
L
L
0.4  
U
U
L
L
U
U
L
L
10-1  
U
U
L
L
4x10-2  
U
U
L
L
U
10-2  
U
L
3CU8  
3CU10  
NA  
L
2CU8  
2CU10  
NA  
4x10-3  
U
U
L
L
12A  
10-3  
1
2
3
4
5 6 8 10  
20  
40  
100  
NA  
12.5A  
13A  
NA  
Multiple of Rated Current  
U
U
L
3CU13  
3CU15  
3CU16  
3CU20  
3CU25  
3CU30  
3CU32  
3CU40  
3CU50  
3CU60  
3C63  
L
2CU13  
2CU15  
2CU16  
2CU20  
2CU25  
2CU30  
2CU32  
2CU40  
2CU50  
2CU60  
2C63  
U
U
L
L
15A  
16A  
20A  
25A  
30A  
32A  
40A  
50A  
60A  
63A  
U
V-EA-C Trip  
U
L
L
13A Through 63A Rated Current  
U
U
L
L
1.13-1.45xIN  
U
U
L
L
60  
40  
U
U
L
L
U
U
L
L
10  
Thermal Overload  
Must Trip< 1 hr = 145% RC  
Must Not Trip> 1 hr = 113% RC  
U
U
L
L
4
U
U
L
L
1
U
U
L
L
10  
4
480Y/277VAC  
480Y/277VAC  
1
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.4  
10-1  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
4x10-2  
0.3-63A (RC): 10kA  
0.3-63A (RC): 10kA  
10-2  
4x10-3  
10000 ON/OFF operations  
10000 ON/OFF operations  
10-3  
40°C (104°F)  
40°C (104°F)  
1
2
3
4
5 6 8 10  
20  
40  
100  
5/1.4kg (3.1 lb.)  
4/1.68kg (3.7 lb.)  
Multiple of Rated Current  
CMagnetic Trip Parameters  
Rated current 0.3A to 63A.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
1. Hold for a minimum of 100ms at  
surge of 5 times rated current.  
2. Trip in under 100ms at 10 times rated  
current.  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
NB: Trip curves shown comply with North  
American standards. For trip curves  
according to European standards please  
consult Altech.  
35 mm (1.38 in.)  
52.5 mm (2.07 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
11  
D-TRIP  
ONE POLE  
ONE POLE PLUS NEUTRAL  
CHARACTERISTICS  
Application Examples:  
High inrush motors, transformers,  
power supplies, heaters and reactive  
loads. Relatively long thermal trip  
delay and very high magnetic trip  
point.  
Prototype testing is recommended in  
motor applications where the relatively  
long thermal trip delay may not  
provide adequate motor overload  
protection. Motor-integral overload  
protectors are recommended, with the  
V-EA-D providing disconnect, backup  
thermal protection and additional short  
circuit and energy let-through  
protection.  
1D  
2DN  
Rated  
Current  
Type/  
Cat. No.  
Type/  
Cat. No.  
Approvals  
Approvals  
U
L
U
0.3A  
0.5A  
0.75A  
1DU03  
1DU05  
1DU075  
NA  
1DU1  
1DU1.6  
1DU2  
1DU2.5  
1DU3  
1DU3.5  
1DU4  
1DU5  
1DU6  
2DNU03  
2DNU05  
2DNU075  
NA  
L
U
L
U
L
U
L
U
L
0.8A  
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
U
U
L
2DNU1  
2DNU1.6  
2DNU2  
2DNU2.5  
2DNU3  
2DNU3.5  
2DNU4  
2DNU5  
2DNU6  
2DNU8  
2DNU10  
NA  
L
U
U
L
L
Type Designation  
U
U
L
L
U
U
L
L
2
D
N
U
60  
U
U
L
L
(a) (b) (c) (d) (e)  
U
U
L
L
U
U
L
L
(a) = Number of Poles  
(b) = Trip Characteristic  
(c) = Blank: without neutral pole  
U
U
L
L
U
U
L
L
U
U
L
1DU8  
1DU10  
NA  
L
= N:  
(d) = U:  
= R:  
with neutral pole  
UL/CSA version  
ring tongue terminals,  
UL/CSA version  
U
U
L
L
12A  
12.5A  
13A  
NA  
NA  
U
U
L
L
1DU13  
1DU15  
1DU16  
1DU20  
1DU25  
1DU30  
1DU32  
1DU40  
1DU50  
1DU60  
1D63  
2DNU13  
2DNU15  
2DNU16  
2DNU20  
2DNU25  
2DNU30  
2DNU32  
2DNU40  
2DNU50  
2DNU60  
2DN63  
= Blank: European version  
(e) = Rated Current  
U
U
L
15A  
16A  
20A  
25A  
30A  
32A  
40A  
50A  
60A  
63A  
L
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
Approvals:  
U
U
L
L
U
U
L
L
U
U
L
L
UL508 Listed  
VDE pending  
277VAC  
277VAC  
Voltage Rating  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
Interrupting Capacity  
(UL/CSA - Ratings)  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
Group Short Circuit  
(UL/CSA - Ratings)  
0.3-63A (RC): 10kA  
0.3-63A (RC): 10kA  
Interrupting Capacity (VDE - Ratings)  
Mechanical Endurance  
10000 ON/OFF operations  
10000 ON/OFF operations  
40°C (104°F)  
40°C (104°F)  
Calibration Temperature  
10/0.3A - 32A = 1.4kg (3.1 lb.)  
40A - 63A = 1.6kg (3.5 lb.)  
5/0.3A - 32A = 1.3kg (2.9 lb.)  
40A - 63A = 1.45kg (3.2 lb.)  
Standard Pack and Weight  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Terminal Size Acceptability  
Terminal Torque  
Basic Dimensions (Elevation View)  
Not European standard rating.  
Please refer to page 21 for specific  
applications.  
DC rating (Manufacturer’s self certification):  
One pole 48VDC, two pole series 125VDC  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
17.5 mm (0.69 in.)  
35 mm (1.38 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
12  
TWO POLE  
THREE POLE  
Basic Dimensions (side view)  
35 mm  
(1.38 in.)  
70mm (2.76 in.)  
2D  
3D  
Rated  
Type/  
Type/  
V-EA-D Trip  
0.3A Through 10A Rated Current  
Current  
Cat. No.  
Approvals  
Cat. No.  
Approvals  
1.13-1.45xIN  
60  
40  
3DU03  
3DU05  
3DU075  
NA  
3DU1  
3DU1.6  
3DU2  
3DU2.5  
3DU3  
3DU3.5  
3DU4  
3DU5  
3DU6  
0.3A  
0.5A  
0.75A  
2DU03  
2DU05  
2DU075  
NA  
2DU1  
2DU1.6  
2DU2  
2DU2.5  
2DU3  
2DU3.5  
2DU4  
2DU5  
2DU6  
U
U
L
L
U
U
L
L
10  
Thermal Overload  
Must Trip< 1 hr = 145% RC  
Must Not Trip> 1 hr = 113% RC  
U
U
L
L
4
0.8A  
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
1
U
U
L
L
U
U
L
L
10  
4
U
U
L
L
U
U
L
L
U
U
L
L
1
U
U
L
L
0.4  
U
U
L
L
10-1  
U
U
L
L
4x10-2  
U
U
L
L
U
U
3DU8  
3DU10  
NA  
L
10-2  
2DU8  
2DU10  
NA  
L
U
4x10-3  
U
L
L
12A  
10-3  
NA  
12.5A  
13A  
NA  
1
2
3
4
5 6 8 10  
20  
40  
100  
16  
U
U
L
L
3DU13  
3DU15  
3DU16  
3DU20  
3DU25  
3DU30  
3DU32  
3DU40  
3DU50  
3DU60  
3D63  
Multiple of Rated Current  
2DU13  
2DU15  
2DU16  
2DU20  
2DU25  
2DU30  
2DU32  
2DU40  
2DU50  
2DU60  
2D63  
U
U
L
L
15A  
16A  
20A  
25A  
30A  
32A  
40A  
50A  
60A  
63A  
U
U
V-EA-D Trip  
13A Through 63A Rated Current  
L
L
U
U
L
L
1.13-1.45xIN  
60  
40  
U
U
L
L
U
U
L
L
U
U
L
L
10  
Thermal Overload  
Must Trip< 1 hr = 145% RC  
Must Not Trip> 1 hr = 113% RC  
U
U
L
L
4
U
U
L
L
1
U
U
L
L
10  
4
480Y/277VAC  
480Y/277VAC  
1
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.4  
10-1  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
0.3-10A (RC): 10kA; 13-60A (RC): 5kA  
no branch circuit protection required  
4x10-2  
0.3-63A (RC): 10kA  
0.3-63A (RC): 10kA  
10-2  
4x10-3  
10000 ON/OFF operations  
10000 ON/OFF operations  
40°C (104°F)  
40°C (104°F)  
10-3  
1
2
3
4
5 6 8 10 1620  
40  
100  
5/1.4kg (3.1 lb.)  
4/1.68kg (3.7 lb.)  
Multiple of Rated Current  
DMagnetic Trip Parameters  
Rated current 0.3A to 63A.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
1. Hold for a minimum of 100ms at  
surge of 10 times rated current.  
2. Trip in under 100ms at 16 times  
rated current.  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
NB: Trip curves shown comply with North  
American standards. For trip curves  
according to European standards please  
consult Altech.  
35 mm (1.38 in.)  
52.5 mm (2.07 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
13  
E-TRIP  
ONE POLE  
ONE POLE PLUS NEUTRAL  
CHARACTERISTICS  
Application Examples:  
High efficiency motors, which have  
exceedingly high inrush currents.  
Relatively short thermal trip delays  
and very high magnetic trip points.  
Prototype testing is recommended.  
The V-EA-E is the result of continuous  
research and improvement of our G-  
and D-Trip circuit breakers. It  
combines the short thermal trip delay  
of the G-Trip and an even higher  
magnetic trip point than the D-Trip.  
1E  
2EN  
Rated  
Type/  
Type/  
Therefore, the V-EA-E provides  
adequate motor overload and short  
circuit protection.  
Current  
Cat. No.  
Approvals  
Cat. No.  
Approvals  
0.3A  
0.5A  
0.75A  
1EU03  
1EU05  
1EU075  
NA  
1EU1  
1EU1.6  
1EU2  
1EU2.5  
1EU3  
1EU3.5  
1EU4  
1EU5  
1EU6  
U
2ENU03  
2ENU05  
2ENU075  
NA  
2ENU1  
2ENU1.6  
2ENU2  
2ENU2.5  
2ENU3  
2ENU3.5  
2ENU4  
2ENU5  
2ENU6  
U
L
L
U
U
L
L
U
U
L
L
0.8A  
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
Type Designation  
U
U
L
L
2
E
N
U
60  
U
U
L
L
U
U
L
L
(a) (b) (c) (d) (e)  
U
U
L
L
U
U
L
L
(a) = Number of Poles  
U
U
L
L
(b) = Trip Characteristic  
(c) = Blank: without neutral pole  
U
U
L
L
U
U
L
L
U
U
L
= N:  
(d) = U:  
= R:  
with neutral pole  
UL/CSA version  
ring tongue terminals,  
UL/CSA version  
L
U
U
L
L
2ENU8  
1EU8  
U
U
L
L
2ENU10  
2ENU12  
2ENU125  
2ENU13  
2ENU15  
2ENU16  
2ENU20  
2ENU25  
2ENU30  
2ENU32  
2ENU40  
2ENU50  
2ENU60  
2EN63  
1EU10  
1EU12  
1EU125  
1EU13  
1EU15  
1EU16  
1EU20  
1EU25  
1EU30  
1EU32  
1EU40  
1EU50  
1EU60  
1E63  
U
U
L
L
12A  
U
U
L
L
12.5A  
13A  
U
U
L
= Blank: European version  
L
U
U
L
L
15A  
16A  
20A  
25A  
30A  
32A  
40A  
50A  
60A  
63A  
(e) = Rated Current  
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
Approvals:  
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
UL508 Listed  
L
277VAC  
277VAC  
Voltage Rating  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
Interrupting Capacity  
(UL/CSA - Ratings)  
0.3-10A (RC): 10kA; 12-60A (RC): 5kA  
no branch circuit protection required  
0.3-10A (RC): 10kA; 12-60A (RC): 5kA  
no branch circuit protection required  
Group Short Circuit  
(UL/CSA - Ratings)  
0.3-63A (RC): 10kA  
0.3-63A (RC): 10kA  
Interrupting Capacity (VDE - Ratings)  
Mechanical Endurance  
10000 ON/OFF operations  
10000 ON/OFF operations  
40°C (104°F)  
40°C (104°F)  
Calibration Temperature  
10/0.3A - 32A = 1.4kg (3.1 lb.)  
40A - 63A = 1.6kg (3.5 lb.)  
5/0.3A - 32A = 1.3kg (2.9 lb.)  
40A - 63A = 1.45kg (3.2 lb.)  
Standard Pack and Weight  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Terminal Size Acceptability  
Terminal Torque  
Basic Dimensions (Elevation View)  
Not European standard rating.  
Please refer to page 21 for specific  
applications.  
DC rating (Manufacturer’s self certification):  
One pole 48VDC, two pole series 125VDC  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
17.5 mm (0.69 in.)  
35 mm (1.38 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
14  
TWO POLE  
THREE POLE  
Basic Dimensions (side view)  
35 mm  
(1.38 in.)  
70mm (2.76 in.)  
2E  
3E  
V-EA-E Trip  
0.3A Through 10A Rated Current  
Rated  
Current  
Type/  
Cat. No.  
Type/  
Cat. No.  
Approvals  
Approvals  
1.05-1.35xIN  
60  
40  
0.3A  
0.5A  
0.75A  
2EU03  
2EU05  
2EU075  
NA  
2EU1  
2EU1.6  
2EU2  
2EU2.5  
2EU3  
2EU3.5  
2EU4  
2EU5  
2EU6  
U
3EU03  
3EU05  
3EU075  
NA  
3EU1  
3EU1.6  
3EU2  
3EU2.5  
3EU3  
3EU3.5  
3EU4  
3EU5  
3EU6  
U
L
L
10  
U
U
L
L
Thermal Overload  
Must Trip< 1 hr = 135% RC  
Must Not Trip> 1 hr = 105% RC  
4
U
U
L
L
1
0.8A  
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
U
U
L
L
10  
4
U
U
L
L
U
U
L
L
U
U
L
L
1
U
U
L
L
0.4  
U
U
L
L
10-1  
U
U
L
L
4x10-2  
U
U
L
L
10-2  
U
U
L
L
4x10-3  
U
U
L
L
2EU8  
3EU8  
U
U
L
2EU10  
2EU12  
2EU125  
2EU13  
2EU15  
2EU16  
2EU20  
2EU25  
2EU30  
2EU32  
2EU40  
2EU50  
2EU60  
2E63  
L
3EU10  
3EU12  
3EU125  
3EU13  
3EU15  
3EU16  
3EU20  
3EU25  
3EU30  
3EU32  
3EU40  
3EU50  
3EU60  
3E63  
10-3  
1
2
3
4
5
6
8 10 141820  
40  
100  
U
U
L
L
12A  
Multiple of Rated Current  
E0.3A-E10A  
U
U
L
L
12.5A  
13A  
U
U
L
L
V-EA-E Trip  
12A Through 60A Rated Current  
U
U
L
L
15A  
16A  
20A  
25A  
30A  
32A  
40A  
50A  
60A  
63A  
U
U
L
L
1.05-1.35xIN  
60  
40  
U
U
L
L
U
U
L
L
10  
U
U
L
L
Thermal Overload  
Must Trip< 1 hr = 135% RC  
Must Not Trip> 1 hr = 105% RC  
4
U
U
L
L
1
U
U
L
L
U
U
L
L
10  
4
U
U
L
L
1
480Y/277VAC  
480Y/277VAC  
0.4  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
10-1  
4x10-2  
0.3-10A (RC): 10kA; 12-60A (RC): 5kA  
no branch circuit protection required  
0.3-10A (RC): 10kA; 12-60A (RC): 5kA  
no branch circuit protection required  
10-2  
4x10-3  
0.3-63A (RC): 10kA  
0.3-63A (RC): 10kA  
10-3  
1
2
3
4
5
6
8 10 1418 20  
40  
100  
10000 ON/OFF operations  
10000 ON/OFF operations  
Multiple of Rated Current  
40°C (104°F)  
40°C (104°F)  
EMagnetic Trip Parameters  
Rated Current, 0.3A to 50A (  
60/63A (- - - - -).  
),  
5/1.4kg (3.1 lb.)  
4/1.68kg (3.7 lb.)  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Magnetic Trip:  
1. Hold for a minimum of 100ms at  
surge of 14 times (60A, 10 times)  
rated current.  
2. Trip in under 100ms at 18 times  
(60A, 14 times) rated current.  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
NB: Trip curves shown comply with North  
American standards. For trip curves  
according to European standards please  
consult Altech.  
35 mm (1.38 in.)  
52.5 mm (2.07 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
15  
G-TRIP  
ONE POLE  
ONE POLE PLUS NEUTRAL  
CHARACTERISTICS  
Application Examples:  
General industrial, including motors,  
some transformers, solenoids, control  
circuits, lighting and wiring. Meets the  
US trip norms with relatively short  
thermal trip delay and high magnetic  
trip point.  
Type Designation  
1G  
2GN  
Rated  
Current  
Type/  
Cat. No.  
Type/  
Cat. No.  
2
G
N
U
60  
Approvals  
Approvals  
(a) (b) (c) (d) (e)  
U
U
L
L
0.3A  
0.5A  
0.75A  
1GU03  
1GU05  
NA  
2GNU03  
2GNU05  
NA  
(a) = Number of Poles  
U
U
L
L
(b) = Trip Characteristic  
(c) = Blank: without neutral pole  
U
U
L
0.8A  
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
1GU08  
1GU1  
1GU1.6  
1GU2  
1GU2.5  
1GU3  
1GU3.5  
1GU4  
2GNU08  
2GNU1  
2GNU1.6  
2GNU2  
2GNU2.5  
2GNU3  
2GNU3.5  
2GNU4  
L
U
U
L
L
= N:  
(d) = U:  
= R:  
with neutral pole  
UL/CSA version  
ring tongue terminals,  
UL/CSA version  
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
= Blank: European version  
U
U
L
L
(e) = Rated Current  
U
U
L
L
1GU5  
1GU6  
1GU8  
2GNU5  
2GNU6  
2GNU8  
U
U
L
L
U
U
L
L
U
U
L
1GU10  
1GU12  
1GU125  
1GU13  
1GU15  
1GU16  
1GU20  
1GU25  
1GU30  
1GU32  
1GU40  
1GU50  
1GU60  
1G63  
2GNU10  
2GNU12  
2GNU125  
2GNU13  
2GNU15  
2GNU16  
2GNU20  
2GNU25  
2GNU30  
2GNU32  
2GNU40  
2GNU50  
2GNU60  
2GN63  
L
U
U
L
12.5A  
13A  
12A  
L
Approvals:  
U
U
L
L
U
U
L
L
U
U
L
15A  
16A  
20A  
25A  
30A  
32A  
40A  
50A  
60A  
63A  
L
U
U
L
L
UL508 Listed  
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
277VAC  
Voltage Rating  
277VAC  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
Interrupting Capacity  
(UL/CSA - Ratings)  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.3-10A (RC): 10kA; 12-60A (RC): 5kA  
no branch circuit protection required  
Group Short Circuit  
(UL/CSA - Ratings)  
0.3-10A (RC): 10kA; 12-60A (RC): 5kA  
no branch circuit protection required  
0.3-63A (RC): 10kA  
Interrupting Capacity (VDE - Ratings)  
Mechanical Endurance  
0.3-63A (RC): 10kA  
10000 ON/OFF operations  
10000 ON/OFF operations  
40°C (104°F)  
Calibration Temperature  
40°C (104°F)  
5/0.3A - 32A = 1.3kg (2.9 lb.)  
40A - 63A = 1.45kg (3.2 lb.)  
Standard Pack and Weight  
10/0.3A - 32A = 1.4kg (3.1 lb.)  
40A - 63A = 1.6kg (3.5 lb.)  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Terminal Size Acceptability  
Terminal Torque  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Basic Dimensions (Elevation View)  
Not European standard rating.  
Please refer to page 21 for specific  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
applications.  
DC rating (Manufacturer’s self certification):  
One pole 48VDC, two pole series 125VDC  
AC Motor Starting, Across-the-line approval  
pending  
*
17.5 mm (0.69 in.)  
35 mm (1.38 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
16  
TWO POLE  
THREE POLE  
Basic Dimensions (side view)  
35 mm  
(1.38 in.)  
70mm (2.76 in.)  
2G  
3G  
Rated  
Type/  
Type/  
V-EA-G Trip  
Current  
Cat. No.  
Approvals  
Cat. No.  
Approvals  
0.3A Through 10A Rated Current  
1.05-1.35xIN  
60  
40  
U
U
L
L
0.3A  
0.5A  
0.75A  
2GU03  
2GU05  
NA  
3GU03  
3GU05  
NA  
U
U
L
L
10  
Thermal Overload  
Must Trip= 125% Rated Current  
4
Must Not Trip< 1 hr = 135% RC  
Must Not Trip> 1 hr = 105% RC  
Must Not Trip= Rated Current  
U
U
L
0.8A  
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
2GU08  
2GU1  
2GU1.6  
2GU2  
2GU2.5  
2GU3  
2GU3.5  
2GU4  
3GU08  
3GU1  
3GU1.6  
3GU2  
3GU2.5  
3GU3  
3GU3.5  
3GU4  
L
1
U
U
L
L
U
U
L
L
10  
4
U
U
L
L
U
U
L
L
1
U
U
L
L
0.4  
U
U
L
L
U
U
L
L
10-1  
U
U
L
L
4x10-2  
2GU5  
2GU6  
2GU8  
3GU5  
3GU6  
3GU8  
U
U
L
L
10-2  
U
U
L
L
4x10-3  
U
U
L
2GU10  
2GU12  
2GU125  
2GU13  
2GU15  
2GU16  
2GU20  
2GU25  
2GU30  
2GU32  
2GU40  
2GU50  
2GU60  
2G63  
3GU10  
3GU12  
3GU125  
3GU13  
3GU15  
3GU16  
3GU20  
3GU25  
3GU30  
3GU32  
3GU40  
3GU50  
3GU60  
3G63  
L
10-3  
U
U
L
12.5A  
13A  
12A  
L
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
1
2
3
4
5 6 8 10  
20  
40  
100  
U
U
L
L
Multiple of Rated Current  
U
U
L
L
V-EA-G Trip  
U
U
L
15A  
16A  
20A  
25A  
30A  
32A  
40A  
50A  
60A  
63A  
L
12A Through 63A Rated Current  
U
U
L
L
1.05-1.35xIN  
60  
40  
U
U
L
L
U
U
L
L
10  
U
U
L
L
Thermal Overload  
Must Trip= 125% Rated Current  
Must Not Trip< 1 hr = 135% RC  
Must Not Trip> 1 hr = 105% RC  
Must Not Trip= Rated Current  
4
U
U
L
L
U
U
L
L
1
U
U
L
L
U
U
L
L
10  
4
1
480Y/277VAC  
480Y/277VAC  
0.4  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.3-60A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
10-1  
4x10-2  
0.3-10A (RC): 10kA; 12-60A (RC): 5kA  
no branch circuit protection required  
0.3-10A (RC): 10kA; 12-60A (RC): 5kA  
no branch circuit protection required  
10-2  
4x10-3  
0.3-63A (RC): 10kA  
0.3-63A (RC): 10kA  
10-3  
10000 ON/OFF operations  
10000 ON/OFF operations  
1
2
3
4
5 6 8 10  
20  
40  
100  
Multiple of Rated Current  
40°C (104°F)  
40°C (104°F)  
GMagnetic Trip Parameters  
Rated Current, 0.3A to 63A.  
5/1.4kg (3.1 lb.)  
4/1.68kg (3.7 lb.)  
Magnetic Trip:  
1. Hold for a minimum of 100ms at  
surge of 8 times rated current.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
2. Trip in under 100ms at 10 times  
rated current.  
NB: Trip curves shown comply with North  
American standards. For trip curves  
according to European standards please  
consult Altech.  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
35 mm (1.38 in.)  
52.5 mm (2.07 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
17  
Z-TRIP  
ONE POLE  
ONE POLE PLUS NEUTRAL  
CHARACTERISTICS  
Application Examples:  
Semiconductors, components which  
fail-short  
(vs. fail-open),  
and  
components/devices with low surge-  
current and short circuit withstand  
capabilities. Relatively short thermal  
delay and very low magnetic trip point.  
Type Designation  
1Z  
2ZN  
2
Z
N
U
30  
Rated  
Type/  
Type/  
Cat. No.  
(a) (b) (c) (d) (e)  
Current Cat. No.  
Approvals  
Approvals  
(a) = Number of Poles  
U
U
L
L
2ZNU03  
2ZNU05  
2ZNU075  
NA  
0.3A  
0.5A  
0.75A  
1ZU03  
1ZU05  
1ZU075  
NA  
(b) = Trip Characteristic  
(c) = Blank: without neutral pole  
U
U
L
L
U
U
L
L
= N:  
(d) = U:  
= R:  
with neutral pole  
UL/CSA version  
ring tongue terminals,  
UL/CSA version  
0.8A  
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
U
L
U
2ZNU1  
2ZNU1.6  
2ZNU2  
2ZNU2.5  
2ZNU3  
2ZNU3.5  
2ZNU4  
2ZNU5  
2ZNU6  
2ZNU8  
2ZNU10  
2ZNU12  
2ZNU125  
2ZNU13  
2ZNU15  
2ZNU16  
2ZNU20  
2ZNU25  
2ZNU30  
2ZNU32  
NA  
L
1ZU1  
1ZU1.6  
1ZU2  
1ZU2.5  
1ZU3  
1ZU3.5  
1ZU4  
1ZU5  
1ZU6  
1ZU8  
1ZU10  
1ZU12  
1ZU125  
1ZU13  
1ZU15  
1ZU16  
1ZU20  
1ZU25  
1ZU30  
1ZU32  
NA  
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
= Blank: European version  
L
U
U
L
L
(e) = Rated Current  
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
Approvals:  
U
U
L
12A  
L
U
U
L
12.5A  
13A  
L
U
U
L
L
U
U
L
L
15A  
16A  
20A  
25A  
30A  
32A  
40A  
50A  
60A  
63A  
UL508 Listed  
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
U
U
L
L
NA  
NA  
NA  
NA  
NA  
NA  
Voltage Rating  
277VAC  
277VAC  
Interrupting Capacity  
(UL/CSA - Ratings)  
0.3-32A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.3-32A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
Group Short Circuit  
(UL/CSA - Ratings)  
0.3-10A (RC): 10kA; 12-32A (RC): 5kA  
no branch circuit protection required  
0.3-10A (RC): 10kA; 12-32A (RC): 5kA  
no branch circuit protection required  
Interrupting Capacity (VDE - Ratings)  
Mechanical Endurance  
0.3-32A (RC): 10kA  
0.3-32A (RC): 10kA  
10000 ON/OFF operations  
10000 ON/OFF operations  
Calibration Temperature  
40°C (104°F)  
40°C (104°F)  
Standard Pack and Weight  
10/0.3A - 32A = 1.4kg (3.1 lb.)  
40A - 63A = 1.6kg (3.5 lb.)  
5/0.3A - 32A = 1.3kg (2.9 lb.)  
40A - 63A = 1.45kg (3.2 lb.)  
Terminal Size Acceptability  
Terminal Torque  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Basic Dimensions (Elevation View)  
Not European standard rating.  
Please refer to page 21 for specific  
applications.  
DC rating (Manufacturer’s self certification):  
One pole 48VDC, two pole series 125VDC  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
17.5 mm (0.69 in.)  
35 mm (1.38 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
18  
TWO POLE  
THREE POLE  
Basic Dimensions (side view)  
35 mm  
(1.38 in.)  
70mm (2.76 in.)  
2Z  
3Z  
V-EA-Z Trip  
Rated  
Current Cat. No.  
Type/  
Type/  
Cat. No.  
0.3A Through 10A Rated Current  
Approvals  
Approvals  
1.05-1.35xIN  
60  
40  
U
U
L
L
0.3A  
0.5A  
0.75A  
2ZU03  
2ZU05  
2ZU075  
NA  
3ZU03  
3ZU05  
3ZU075  
NA  
U
U
L
10  
L
Thermal Overload  
Must Trip< 1 hr = 135% RC  
Must Not Trip> 1 hr = 105% RC  
4
U
U
L
L
0.8A  
1.0A  
1.6A  
2.0A  
2.5A  
3.0A  
3.5A  
4.0A  
5.0A  
6.0A  
8.0A  
10A  
1
40  
U
U
L
2ZU1  
2ZU1.6  
2ZU2  
2ZU2.5  
2ZU3  
2ZU3.5  
2ZU4  
2ZU5  
2ZU6  
2ZU8  
2ZU10  
2ZU12  
2ZU125  
2ZU13  
2ZU15  
2ZU16  
2ZU20  
2ZU25  
2ZU30  
2ZU32  
NA  
L
3ZU1  
3ZU1.6  
3ZU2  
3ZU2.5  
3ZU3  
3ZU3.5  
3ZU4  
3ZU5  
3ZU6  
3ZU8  
3ZU10  
3ZU12  
3ZU125  
3ZU13  
3ZU15  
3ZU16  
3ZU20  
3ZU25  
3ZU30  
3ZU32  
NA  
20  
10  
U
U
L
L
U
U
L
L
4
U
U
L
L
U
U
1
L
L
0.4  
U
U
L
L
U
U
L
L
10-1  
U
U
L
L
4x10-2  
U
U
L
L
10-2  
U
U
L
L
4x10-3  
U
U
L
L
U
U
L
L
12A  
10-3  
1
2
3
4
5 6 8 10  
20  
40  
100  
U
U
L
L
12.5A  
13A  
Multiple of Rated Current  
U
U
L
L
V-EA-Z Trip  
U
U
L
L
15A  
16A  
20A  
25A  
30A  
32A  
40A  
50A  
60A  
63A  
12.5A Through 32A Rated Current  
U
U
L
L
1.05-1.35xIN  
U
U
L
L
60  
40  
U
U
L
L
U
U
L
L
10  
Thermal Overload  
Must Trip< 1 hr = 135% RC  
Must Not Trip> 1 hr = 105% RC  
U
U
L
L
4
1
NA  
NA  
NA  
NA  
NA  
NA  
10  
4
480Y/277VAC  
480Y/277VAC  
1
0.4  
0.3-32A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
0.3-32A (RC): 10kA with UL-listed  
RK5 back-up fuse or MCCB  
10-1  
4x10-2  
0.3-10A (RC): 10kA; 12-32A (RC): 5kA  
no branch circuit protection required  
0.3-10A (RC): 10kA; 12-32A (RC): 5kA  
no branch circuit protection required  
10-2  
0.3-32A (RC): 10kA  
0.3-32A (RC): 10kA  
4x10-3  
10000 ON/OFF operations  
10000 ON/OFF operations  
10-3  
1
2
3
4
5 6 8 10  
20  
40  
100  
40°C (104°F)  
40°C (104°F)  
Multiple of Rated Current  
5/1.4kg (3.1 lb.)  
4/1.68kg (3.7 lb.)  
ZTrip Parameters  
Rated Current, 0.3A to 32A.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Top: 18-3 AWG; Bottom: 18-2 AWG  
20 lb.in.  
Magnetic Trip:  
1. Hold for a minimum of 100ms at  
2 times rated current.  
2. Trip in under 100ms at 3 times  
rated current.  
91.5 mm  
(3.60 in.)  
91.5 mm  
(3.60 in.)  
NB: Trip curves shown comply with North  
American standards. For trip curves  
according to European standards please  
consult Altech.  
35 mm (1.38 in.)  
52.5 mm (2.07 in.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
19  
Table HP 1: AMPERE RATINGS & HORSEPOWER RATING 1 PHASE  
FLA & LRC CONVERTED TO  
TABLE HORSEPOWER (SEE NOTE #2)  
USE FLA & LRC RATINGS WHERE  
NO HP RATING IS GIVEN  
NOMINAL CIRCUIT VOLTAGE  
V-EA  
RATED  
MOTOR  
NAMEPLATE  
MOTOR  
NAMEPLATE  
110-120  
VAC  
200  
VAC  
208  
VAC  
220-240  
VAC  
265  
VAC  
277  
VAC  
CURRENT  
(SEE NOTE #1)  
FLA  
RATING  
STARTING/  
LRC RATING  
0.30A  
0.50A  
0.75A  
0.30A  
0.50A  
0.75A  
1.80A  
3.00A  
4.35A  
0.80A  
1.0A  
1.6A  
0.80A  
1.0A  
1.6A  
4.8A  
6.0A  
9.6A  
2.0A  
2.5A  
3.0A  
2.0A  
2.5A  
3.0A  
12.0A  
15.0A  
18.0A  
1/6hp  
1/6hp  
1/4hp  
1/6hp  
1/6hp  
1/4hp  
1/6hp  
1/4hp  
1/3hp  
1/6hp  
1/6hp  
1/6hp  
1/6hp  
3.5A  
4.0A  
3.5A  
4.0A  
21.0A  
24.0A  
1/4hp  
1/4hp  
1/4hp  
1/3hp  
1/4hp  
1/3hp  
1/3hp  
1/3hp  
1/3hp  
1/3hp  
5.0A  
6.0A  
8.0A  
5.0A  
6.0A  
8.0A  
30.0A  
36.0A  
48.0A  
1/6hp  
1/4hp  
1/3hp  
1/3hp  
1/2hp  
3/4hp  
1/2hp  
1/2hp  
3/4hp  
1/2hp  
1/2hp  
1hp  
1/2hp  
3/4hp  
1hp  
1/2hp  
3/4hp  
1hp  
10.0A  
10.0A  
60.0A  
1/2hp  
1hp  
1hp  
11/2hp  
11/2hp  
2hp  
12.0A  
12.5A  
12.0A  
12.5A  
72.0A  
75.0A  
1/2hp  
1/2hp  
11/2hp  
11/2hp  
11/2hp  
11/2hp  
2hp  
2hp  
2hp  
2hp  
2hp  
2hp  
13.0A  
15.0A  
16.0A  
13.0A  
15.0A  
16.0A  
78.0A  
90.0A  
96.0A  
1/2hp  
3/4hp  
1hp  
11/2hp  
2hp  
2hp  
11/2hp  
2hp  
2hp  
2hp  
2hp  
2hp  
2hp  
3hp  
3hp  
2hp  
3hp  
3hp  
20.0A  
25.0A  
20.0A  
25.0A  
120.0A  
150.0A  
11/2hp  
2hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
5hp  
3hp  
5hp  
30.0A  
32.0A  
40.0A  
30.0A  
32.0A  
40.0A  
180.0A  
192.0A  
240.0A  
2hp  
2hp  
3hp  
3hp  
3hp  
5hp  
3hp  
5hp  
71/2hp  
5hp  
5hp  
71/2hp  
5hp  
5hp  
71/2hp  
5hp  
5hp  
71/2hp  
50.0A  
60.0A  
50.0A  
60.0A  
300.0A  
360.0A  
3hp  
5hp  
71/2hp  
10hp  
10hp  
10hp  
10hp  
10hp  
10hp  
10hp  
10hp  
15hp  
NOTE #1: For AC motor circuit nameplate full load current, AC general-use loads, AC resistance loads, AC incandescent lamp (tungsten) loads,  
AC electric discharge lamp (ballast) loads.  
NOTE #2: Conversions per UL508® Table 45.2 and NFPA-70: National Electrical Code® 1999 Tables 430-148 and 430-151A.  
Table HP 2: AMPERE RATING & HORSEPOWER RATING 3 PHASE & 2 PHASE - 4 WIRE  
FLA & LRC RATINGS CONVERTED TO TABLE HORSEPOWER (SEE NOTE #2)  
USE FLA & LRC RATINGS WHERE NO HP IS LISTED  
V-EA  
RATED  
CURRENT  
MOTOR  
NAMEPLATE NAMEPLATE  
FLA  
MOTOR  
110-120  
VAC  
Motor Design  
200  
VAC  
Motor Design  
208  
VAC  
Motor Design  
220-240 VAC  
(SEE NOTE #3)  
Motor Design  
440-480  
VAC  
Motor Design  
STARTING/  
(SEE NOTE #1) RATING  
LRC RATING  
B, C, D  
E
B, C, D  
E
B, C, D  
E
B, C, D  
E
B, C, D  
E
0.30A  
0.50A  
0.75A  
0.30A  
0.50A  
0.75A  
3.0A  
5.0A  
7.5A  
0.80A  
1.0A  
1.6A  
0.80A  
1.0A  
1.6A  
8.0A  
10.0A  
16.0A  
1/2hp  
1/2hp  
2.0A  
2.5A  
3.0A  
2.0A  
2.5A  
3.0A  
20.0A  
25.0A  
30.0A  
1/2hp  
1/2hp  
1/2hp  
1/2hp  
1/2hp  
1/2hp  
3/4hp  
1hp  
11/2hp  
3/4hp  
1hp  
11/2hp  
1/2hp  
1/2hp  
1/2hp  
1/2hp  
1/2hp  
1/2hp  
1/2hp  
1/2hp  
3.5A  
4.0A  
3.5A  
4.0A  
35.0A  
40.0A  
1/2hp  
3/4hp  
1/2hp  
3/4hp  
3/4hp  
3/4hp  
3/4hp  
3/4hp  
3/4hp  
3/4hp  
3/4hp  
3/4hp  
2hp  
2hp  
2hp  
2hp  
5.0A  
6.0A  
8.0A  
5.0A  
6.0A  
8.0A  
42.0A  
50.4A  
67.2A  
1/2hp  
1/2hp  
3/4hp  
1/2hp  
1/2hp  
3/4hp  
1hp  
1hp  
2hp  
1hp  
1hp  
2hp  
1hp  
1hp  
2hp  
1hp  
1hp  
2hp  
1hp  
11/2hp  
2hp  
1hp  
11/2hp  
2hp  
3hp  
3hp  
5hp  
3hp  
3hp  
5hp  
10.0A  
10.0A  
84.0A  
1hp  
1hp  
2hp  
2hp  
2hp  
2hp  
3hp  
3hp  
5hp  
5hp  
12.0A  
12.5A  
12.0A  
12.5A  
100.8A  
105.0A  
11/2hp  
11/2hp  
11/2hp  
11/2hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
71/2hp  
71/2hp  
71/2hp  
71/2hp  
13.0A  
15.0A  
16.0A  
13.0A  
15.0A  
16.0A  
109.2A  
126.0A  
134.4A  
11/2hp  
2hp  
2hp  
11/2hp  
2hp  
2hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
3hp  
5hp  
3hp  
3hp  
5hp  
71/2hp  
10hp  
10hp  
71/2hp  
10hp  
10hp  
20.0A  
25.0A  
20.0A  
25.0A  
168.0A  
210.0A  
3hp  
3hp  
3hp  
3hp  
5hp  
5hp  
5hp  
5hp  
5hp  
71/2hp  
5hp  
71/2hp  
5hp  
71/2hp  
5hp  
71/2hp  
10hp  
15hp  
10hp  
15hp  
30.0A  
32.0A  
40.0A  
30.0A  
32.0A  
40.0A  
252.0A  
268.8A  
226.0A  
5hp  
5hp  
5hp  
5hp  
5hp  
5hp  
5hp  
5hp  
71/2hp  
10hp  
10hp  
71/2hp  
10hp  
71/2hp  
10hp  
10hp  
10hp  
10hp  
10hp  
10hp  
20hp  
20hp  
30hp  
20hp  
20hp  
20hp  
5hp  
10hp  
5hp  
71/2hp  
50.0A  
60.0A  
50.0A  
60.0A  
282.5A  
339.0A  
71/2hp  
10hp  
71/2hp  
10hp  
15hp  
15hp  
10hp  
10hp  
15hp  
20hp  
10hp  
10hp  
15hp  
20hp  
10hp  
15hp  
30hp  
40hp  
25hp  
30hp  
NOTE #1: For AC motor circuit nameplate full load current, AC general-use loads, AC resistance loads, AC incandescent lamp (tungsten) loads,  
AC electric discharge lamp (ballast) loads.  
NOTE #2: Conversions per UL508® proposed Tables 45.2 and 45.4 and NFPA-70: National Electrical Code® 1999 Tables 430-149, 430-150 and 430-151B.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
20  
V-EA INTERNAL RESISTANCE  
Resistances listed are “hot” values, as  
opposed to cold start values. Operating  
voltage drop across the V-EA and power  
loss per pole can be approximated with  
basic formulas:  
Trip Characteristic  
Rated  
Current  
(Amp)  
B
C
D
E
G
Z
(Ohms)  
(Ohms)  
(Ohms)  
(Ohms)  
(Ohms)  
(Ohms)  
0.3  
0.5  
0.75/0.8  
1.0  
1.6  
2.0  
2.5  
3.0  
3.5  
4.0  
5.0  
6.0  
8.0  
10  
12/12.5  
13  
15/16  
20  
25  
0.0528  
0.0216  
0.0113  
0.0085  
0.0067  
0.0050  
0.0032  
0.0025  
0.0019  
0.0018  
16.8620  
6.8540  
3.0540  
1.7000  
0.5870  
0.4190  
0.2950  
0.2020  
0.1390  
0.1090  
0.0654  
0.0528  
0.0278  
0.0216  
0.0084  
0.0085  
0.0067  
0.0050  
0.0032  
0.0025  
0.0019  
0.0018  
16.8620  
6.0009  
3.0540  
1.7560  
0.5870  
0.4190  
0.2950  
0.2020  
0.1390  
0.1090  
0.0654  
0.0491  
0.0240  
0.0187  
0.0085  
0.0076  
0.0064  
0.0041  
0.0027  
0.0022  
0.0018  
0.0017  
14.52000  
5.92000  
2.70000  
1.48000  
0.57400  
0.40500  
0.26900  
0.18600  
0.13900  
0.10600  
0.05900  
0.04600  
0.03040  
0.02020  
0.00724  
0.00724  
0.00731  
0.00582  
0.00411  
0.00272  
0.00212  
0.00184  
0.00172  
16.8620  
6.8540  
3.0540  
1.7560  
0.5870  
0.4190  
0.2950  
0.2020  
0.1390  
0.1090  
0.0654  
0.0491  
0.0333  
0.0211  
0.0084  
0.0084  
0.0076  
0.0064  
0.0046  
0.0030  
0.0022  
0.0019  
0.00179  
31.5060  
10.2460  
5.3920  
2.6910  
0.9440  
0.8900  
0.4290  
0.3460  
0.1790  
0.1620  
0.1050  
0.0823  
0.0371  
0.0278  
0.0151  
0.0151  
0.0114  
0.0075  
0.0050  
0.0032  
V
P
= I  
= I  
x R  
x R  
DROP  
OPERATING  
TABLE  
TABLE  
2
LOSS P/P  
OPERATING  
Voltage drops should be reviewed when  
V-EAs with high internal resistance are  
used (e.g., load voltage minimums).  
Power loss should be reviewed when  
V-EAs with high rated currents are used  
(e.g., enclosure heating).  
The listed V-EA internal resistance values  
should not be used in calculations of  
available short-circuit current downstream  
of the V-EA. The dynamic impedance of  
the V-EA under short-circuit conditions  
can vary significantly from internal  
resistance values in normal operation.  
30/32  
40  
50  
60/63  
LINE CURRENT FREQUENCY EFFECTS ON TRIP CURVES  
The thermal trip is not affected by the frequency of the line  
current. The magnetic trip is within the trip zone of the  
characteristic curve for frequencies from 16 2/3 to 60Hz. At  
lower and higher frequencies, the magnetic trip will be delayed  
longer than indicated by the characteristic curve, roughly as  
follows:  
Frequency Effects on Magnetic Trip Curves  
Trip  
Curve  
Trip Zone  
At  
Trip Zone  
At  
Trip Zone  
At  
Trip Zone  
At  
Trip Zone  
At  
16 2/3 - 60Hz  
(x RC)  
100 Hz  
(x RC)  
200 Hz  
(x RC)  
400 Hz  
(x RC)  
DC  
(x RC)  
Z
B
C
G
D
E
2 - 3  
3 - 5  
2.2 - 3.3  
3.3 - 5.5  
2.4 - 3.6  
3.6 - 6.0  
2.8 - 4.2  
4.2 - 7.0  
3.0 - 4.5  
4.5 - 7.5  
At 100Hz: Mag. Trip Current = 1.1 x curve current  
At 200Hz: Mag. Trip Current = 1.2 x curve current  
At 400Hz: Mag. Trip Current = 1.4 x curve current  
5 - 10  
8 - 10  
10 - 16  
14 - 18  
5.5 - 11.0  
8.8 - 11.0  
11.0 - 17.6  
15.4 - 19.8  
6.0 - 12  
7.0 - 14.0  
11.2 - 14.0  
14.0 - 22.4  
19.6 - 25.2  
7.5 - 15.0  
12.0 - 15.0  
15.0 - 24.0  
21.0 - 27.0  
9.6 - 12.0  
12.0 - 19.2  
16.8 - 21.6  
At DC:  
Mag. Trip Current = 1.5 x curve current  
For example, at 16 2/3 - 60 Hz the magnetic trip zone for the “G”  
characteristic is 8 to 10 times the rated current of the specific  
V-EA (i.e., hold for at least 100ms at 8 x RC, trip in less than  
100ms at 10 x RC). With a 400Hz current, a magnetic trip at 10  
x RC would be greatly delayed (thermal would likely trip first), as  
the magnetic trip zone is now 11.2 to 14 x RC. If a quicker  
magnetic trip is required with 400Hz, the “B” or “C” characteristic  
should be considered.  
MECHANICAL ENDURANCE RATINGS (ON/OFF OPERATIONS)  
Application  
2 x (1.15 x RC)  
2 x RC  
RC  
No Load  
Total  
AC General Use  
1000  
6000  
5000  
6000  
4000  
4000  
4000  
4000  
4000  
10000  
10000  
10000  
10000  
10000  
AC Motor Starting Across the Line  
AC Incandescent Lamps (Tungsten)  
AC Electrical Discharge Lamps (Ballast)  
AC Resistance  
6000  
6000  
Manufacturers self certification  
20000 ON/OFF operations with no load  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
21  
SHORT CIRCUIT RATINGS FOR V-EA MANUAL MOTOR CONTROLLER  
Backup  
Protection  
UL-Listed  
RK5-Fuse  
up to 10kA  
UL-Listed  
MCCB  
up to 10kA  
No BCP  
Required  
up to:  
Trip  
Curve  
Amp Range  
0.3 - 10A  
all  
all  
all  
all  
4xRC*  
4xRC*  
10kA  
5kA  
5kA  
5kA  
min 15A, max 70A min 15A, max 70A  
12 - 30/32A  
40 - 50A  
4xRC*  
max 125A  
4xRC*  
max 125A  
4xRC*  
max 200A  
4xRC*  
max 200A  
60 / 63A  
4xRC*  
4xRC*  
max 250A  
max 250A  
*up to nearest rated current  
TEMPERATURE CORRECTION CURVE  
Ambient Temperature and Adjacent Mounting/Loading Adjustment  
160  
150  
Ambient Temperature Adjustment  
5% of RC for every 10°C (18°F).  
140  
130  
120  
110  
100  
90  
Adjacent Mounting Temperature  
Adjustment 3% of RC for every  
additional pole above 3.  
Maximum 20% off RC for a total  
of 10 poles or more.*  
80  
70  
60  
* Cooling spacer (Part #15.960)  
between each group of 3 poles  
will eliminate these adjustments.  
50  
40  
-40  
-40  
-30  
-22  
-20  
-4  
-10  
14  
0
32  
10  
50  
20  
68  
30  
86  
40  
104  
50  
122  
60  
140  
70  
158  
80  
176  
90 (°C)  
194 (°F)  
Ambient Temperature  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
22  
CUT-AWAY VIEWS OF V-EA MINIATURE CIRCUIT BREAKER  
Shown in “on” position  
Manual Disconnect/Reset  
Magnetic (Instantaneous) Trip  
Thermal (Inverse-Time) Trip  
Arc Guides  
De-ionization Chamber (Arc Chute)  
Arc Chamber  
Shown in “off” position  
Magnetic Trip  
Electromagnetic Coil  
Thermal Trip  
Top Terminal  
Bimetallic Element  
M5 Cross-Slot Screw  
Bottom Terminal  
M5 Cross-Slot Screw  
Bottom Terminal Cage  
Top Terminal Cage  
Fixed Contact  
Moveable Contact,  
Pivoted Lever  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
23  
INSTALLATION RECOMMENDATIONS  
INTRODUCTION  
EASY REMOVAL  
The V-EA* easily snaps onto a readily available, international  
standard 35mm DIN Rail. Mounting can be in any position from  
full horizontal to full vertical without affecting performance.  
Removal, One Pole  
1. Insert tip of 4mm or less straight blade screwdriver into the  
slot of the metal retaining clip.  
All housings are the same size regardless of rated current,  
simplifying layout and modifications.  
2. Brace the shank of the screwdriver against the terminal  
side of the V-EA* and gently lever the clip away from the  
DIN rail.  
Line power feed can be to either top or bottom terminals. This  
provides flexibility to power distribution enclosure entry (top,  
bottom, sides) and internal raceway runs (e.g., power in one  
horizontal raceway can feed both the row above and the row  
below).  
3. When the clip moves out, continue rotating screwdriver  
and V-EA* up and off of the bottom of the DIN rail lip.  
4. Grasp V-EA* and lift upwards to disengage from the top  
lip of the rail, then remove.  
Minimal free space is required to remove or replace the V-EAs,  
and with standard housing and terminal sizes, ratings can be  
changed or multi-poles can replace multi-single pole or vice-  
versa. To obtain the highest density mounting arrangement  
without serious problems from heat build-up, see “Temperature  
Correction Curve” (page 22).  
Altech and our distributors are pleased to quote custom rail  
assemblies. Multi-function assemblies can include cut-to-order  
DIN Rail, mounted V-EA and MA circuit breakers, FI Earth  
Leakage breakers, lightning/surge protectors, interface modules  
(cable fan-out, relays, I/O, power supply, etc.), terminal blocks  
with marking tags, and other control components to meet your  
specifications. Order assemblies with only one part number or  
even your drawing number.  
DIN Rail Information  
Mounting rails are internationally standardized and are available  
in several sizes with or without perforations. Zinc-plated yellow  
chromated steel is standard. Copper and aluminum DIN Rails  
are also available. Please contact Altech for your DIN Rail  
needs.  
WIRING  
Field wiring terminal size acceptability:  
Top: 18-3 AWG  
Bottom: 18-2 AWG  
Use 75°C insulation copper conductors only, loaded to  
60°C ampacity.  
35mm  
(1.38 in.)  
35mm  
(1.38 in.)  
Stock  
1.0mm (.039 in.)  
Thick  
Stock  
1.5mm (.059 in.)  
Thick  
Wire conductor stripping length:  
Top Terminals: 11.5mm (approximately 7/16”)  
Bottom Terminals: 12.5mm (approximately 1/2”)  
TS35x7.5  
TS35x15  
For terminal screws, we recommend a #2 Phillips or  
Posidriv screwdriver. Terminals are also readily  
accessible to battery operated screwdrivers. Please  
contact Altech for tool and ordering information.  
25mm  
5.3mm  
17.5mm  
7
18mm  
mm  
C
L
6.2mm  
Terminal tightening torque is rule-of-thumb 20 lb.in.  
C
C
L
17.5mm  
L
5.3mm  
TS35 DIN Rail Perforations Dimensions + 0.1mm (.003 in.)  
SNAP-ON MOUNTING  
1. Place the upper lip of the V-EA* under the upper lip of the rail.  
2. Press down on bottom terminal area until the V-EA* spring-  
loaded clip snaps under lower lip of the rail.  
* V-EA miniature circuit breaker handling is representative for MA  
circuit breakers and FI Earth Leakage circuit breakers.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
24  
V-EA DIMENSIONS  
General  
Mounting in  
Enclosure  
44mm (1.73 in.)  
115mm (4.53 in.)  
37.5mm (1.48 in.)  
25.5mm (1.0 in.)  
6mm (.24 in.)  
18mm  
(.71 in.)  
7mm  
(.28 in.)  
TS35 x 7.5  
DIN Rail  
46mm  
(1.81 in.)  
Actual  
Cut-Out  
Transparent  
Outer Cover  
of Enclosure  
20mm  
(.79 in.)  
8mm (.31 in.)  
15mm (.59 in.)  
14mm (0.55 in.)  
63mm (2.48 in.)  
Interior  
(Cut-Out)  
Cover  
30.5mm  
(1.20 in.)  
3mm (.12 in.)  
NOTE 2  
44mm (1.73 in.)  
68mm (2.68 in.)  
70mm (2.76 in.) NOTE 1  
For note information see section below.  
Not Shown: Width of Face (Thickness)  
One Pole 17.5mm (.69 in.)  
Two Pole 35mm (1.38 in.)  
Three Pole 52.5mm (2.07 in.)  
ALTECH/SPELSBERG EK/AK NONMETALLIC ENCLOSURES FOR MCBS  
NOTE 1: For totally enclosing the V-EA, the  
minimum interior depth of the enclosure is  
70mm plus DIN Rail depth (7.5 or 15mm) plus  
any rail mounting stand-off depth.  
NOTE 2: Fork lugs with a thickness up to  
3mm can be inserted in the lower terminals  
under the head of the captive M5 (i.e. 5mm  
diameter to outside of threads) terminal screw.  
NOTE 3A: The V-EA’s raised face is sized to  
fit through standard European enclosure cut-  
outs, which allow sight and operation of the  
trip/reset handle but keep all wiring covered.  
As shown in Fig. 1, Altech/Spelsberg AK/EK  
nonmetallic enclosures are ready-made for  
this attractive and efficient packaging ap-  
proach.  
NOTE 3B: The V-EA was successfully short-  
circuit tested in TYPE 1 metal enclosures with  
the V-EA face extending through a 46mm cut-  
out in the cover. Typical applications include:  
V-EA on 35mm wide by 15mm deep DIN  
Rail, mounted to back wall of a 3 inch deep  
enclosure with no back panel.  
V-EA on 35mm wide by 7.5mm deep DIN  
Rail, mounted to the back panel of a 3 inch  
deep enclosure with panel.  
Fig 1. Altech/Spelsberg EK/AK nonmetallic enclosure with Altech/ABL Sursum V-EA  
and MA Circuit Breakers installed.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
25  
MA THREE PHASE  
ADJUSTABLE TRIP  
MINIATURE CIRCUIT  
BREAKERS/MANUAL  
MOTOR CONTROLLERS  
UL508 listed  
CAN/CSA-C22.2 No.14 certified  
The MA was designed to handle the high  
inrush loads of 3 phase transformers, power  
supplies, motors, etc. The MA protects wiring  
and equipment from damage caused by the  
three major classes of over-current, yet  
greatly reduces the number of nuisance trips Type Designation  
in high starting and inrush current circuits.  
MA  
__  
RT  
__  
__  
__  
An IEC device with excellent ratings under a  
UL listing at 480Y/277V (including group  
ratings) and at 500V under international  
standards, the Altech/ Sursum MA provides  
short and long term cost effective circuit  
protection for USA and/or export  
applications. The short term advantages  
include: (1) adjustable thermal trip allows  
finalization of initial designs before  
procurement of the load equipment is  
complete; (2) snap-on mounting for readily  
available, internationally standardized DIN  
Rail saves panel layout design time as well  
as installation and change labor; (3) large  
cage-clamp terminals with screws suitable to  
power screwdrivers, simplifies and speeds  
wiring; (4) convenient switched disconnect  
during factory testing and/or initial start-up  
saves time and aggravation. The key long  
term advantage is customer satisfaction and  
proven over-current protection of wiring and  
equipment (and the lack of rework/repair  
costs).  
(a) (b) (c) (d)  
(a) = MA - Manual Motor Controller  
(b) = Rated Current  
(c) = U - US Housing  
(d) = Blank - Standard Terminal  
RT - Ring-tongue Terminal  
Voltage Rating  
480Y/277VAC  
0.16A-2.5A: 42kA; 4.0A-16A: 14kA; 20A-40A: 10kA  
AIC (Interrupt Capacity)  
Standard Short Circuit Withstand Rating 0.16A-2.5A: 42kA; 4.0A-16A: 14kA  
(UL/CSA Ratings)  
Group Short Circuit Ratings  
(UL/CSA Ratings)  
see above  
Typical Life  
6000 on/off operations with 2xRC  
25°C, +0°, -5° (77°F, +0° -9°)  
1/450g (1.0 lb.)  
Calibration Temperature  
Standard Pack and Weight  
Terminal Size Acceptability  
Top/Bottom: 18-3 AWG  
GROUP SHORT  
CIRCUIT RATING  
AT 480VAC  
3Ø HORSEPOWER RATINGS AT NOMINAL LINE VOLTAGE  
Type and  
Rated  
Current  
FLA Dial  
Adjustment  
Markings  
(See Note for HEA Definition)  
a
460-480V  
HP (HEA)  
110-120V  
HP (HEA)  
200V  
208V  
220-240V  
HP (HEA)  
(and BCP size)  
Cat. No.  
HP (HEA) HP (HEA)  
MA0.16U  
MA0.25U  
MA0.40U  
MA0.63U  
MA1.0U  
MA1.6U  
MA2.5U  
MA4.0U  
MA6.3U  
MA10U  
MA16U  
MA20U  
MA25U  
MA32U  
MA40U  
15.901U  
15.902U  
15.903U  
15.904U  
15.905U  
15.906U  
15.907U  
15.908U  
15.909U  
15.910U  
15.911U  
15.912U  
15.913U  
15.914U  
15.915U  
0.1/ 0.12/0.14/0.16  
0.16/0.19/0.22/0.25  
0.25/0.30/0.35/0.40  
0.40/0.48/0.56/0.63  
0.63/0.75/0.87/1.0  
1.0/1.2/1.4/1.6  
1.6//1.9/2.2/2.5  
2.5/3.0/3.5/4.0  
4.0/4.8/5.6/6.3  
6.3/7.5/8.7/10  
42kARMS  
Through MA2.5U, ampere rated for motor circuits having a full-  
load-amperage (FLA) not exceeding the MA’s general purpose  
rated current (RC, equals maximum dial setting) and a locked  
rotor current not exceeding 6 times the MA’s RC.  
symmetrical  
(max. 1200A  
MCCB  
or RK5)  
14kARMS  
1/2 (4.0) 3/4 (3.2)  
3/4 (5.6) 11/2 (6.0)  
3/4  
11/2  
2
(3.1)  
(5.7)  
1
(3.6)  
2
3
5
(3.42)  
(4.8)  
(7.6)  
symmetrical  
(max. 350A  
MCCB  
11/2 (5.2)  
1
2
3
3
5
5
(7.2)  
(13.6)  
(19.2)  
(19.2)  
2
3
5
5
(7.8)  
(11.0)  
(17.5)  
(7.5)  
3
5
5
(9.6)  
10/12/14/16  
or RK5)  
3
(10.6)  
(16.7)  
(15.2) 10 (14.0)  
(15.2) 10 (14.0)  
10kARMS  
16/17/18.5/20  
5
symmetrical  
(max. 350A  
MCCB  
20/21.5/23/25  
(17.5) 71/2 (24.2) 71/2 (22.0) 15 (21.0)  
25/27/30/32  
(30.4) 71/2 (25.0) 71/2 (24.2)  
(30.4) 10 (32.0) 10 (31.0)  
10 (28.0) 20 (27.0)  
10 (28.0) 25 (34.0)  
32/34/37/40  
or RK5)  
Note: HEA - Horsepower Equivalent Amperes, the nominal amperage assigned to standard motor horsepower ratings in design guide tables such as  
NFPA-70 Tables 430-148, 430-149, 430-150; UL1077 Table 16.2; CSA - C22.2 No. 235-M89 Tables 44 and 45; CSA-C22.2 No. 14-M91 Table 19, etc.  
Multiply HEA values (in parenthesis) by 1.1 if power factor is 90%, and by 1.2 if power factor is 80%.  
a
The standard-circuit short-circuit rating is 14kA for all types. Group ratings can be used in a standard circuit (e.g., MA1.0U at 42kA), but a higher  
standard rating cannot be used in a group circuit (e.g., MA40U at 14kA only in standard circuit.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
26  
DIMENSIONS  
TRIP CHARACTERISTICS MA/U  
120  
60  
44mm (1.73 in.)  
MA0.16U-MA16U  
MA 3 Phase Controller  
40  
37.5mm (1.48 in.)  
25.5mm (1.0 in.)  
6mm (.24 in.)  
Thermal Overload (B, C, D)  
Must TripCurrent = 115% of Dial Setting  
Must Not Trip> 1 hr = 105% of Dial Setting  
20  
10  
7mm  
(.28 in.)  
6
4
2
1
40  
20  
10  
6
4
2
1
0.6  
0.4  
Magnetic Trip  
Nominal 1100% of Rated Current  
0.2  
0.1  
1 1.15 1.5 2 2.3  
3
4 5 6 6.9 8 10 12 16 19  
Multiple of Dial Setting (Thermal)  
7mm (.28 in.)  
Multiple of Rated Current (Magnetic Trip)  
Rated Current = Max. Dial Setting  
17.5mm (1.28 in.)  
120  
30.5mm  
3mm  
(.12 in.)  
(1.20 in.)  
60  
40  
MA20U-MA40U  
MA 3 Phase Controller  
44mm (1.73 in.)  
Thermal Overload (B, C, D)  
Must TripCurrent = 115% of Dial Setting  
Must Not Trip> 1 hr = 105% of Dial Setting  
20  
68mm (2.68 in.)  
10  
6
4
2
1
3
5
1
L1  
L2  
L3  
40  
20  
10  
6
4
12A  
10A  
14A  
16A  
40°C  
20°C  
MA.16  
2
1
VDE 0660 AC-3  
500V  
50-60Mz  
ABL SURSUM  
0.6  
0.4  
Magnetic Trip  
T1  
T2  
T3  
Nominal 1100% of Rated Current  
0.2  
0.1  
2
4
6
11.15 1.5 2 2.3  
3
4
5
6 6.9 8 10 12 15  
12.5  
Multiple of Dial Setting (Thermal)  
52.5mm (2.07 in.)  
Multiple of Rated Current (Magnetic Trip)  
Rated Current = Max. Dial Setting  
MA/USA Manual Motor Controller  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
27  
FI EARTH LEAKAGE  
CIRCUIT BREAKERS  
FI compact Earth Leakage Circuit  
Breakers detect and interrupt earth  
(ground) faults. They are VDE  
approved for the European system  
of protecting people, animals,  
equipment and property from  
dangerous line-to-ground and shock  
hazard currents.  
US applications include ground-fault  
protection of equipment (GFPE)  
using the 10mA and 30mA fault  
current ratings, especially when high  
distributed capacitance or other  
leakages cause excessive nuisance  
trips at lower fault currents.  
Applications for the 300mA rating are  
equipment protection and fire  
prevention, limiting the energy of a  
fault to less than the minimum  
ignition energy for many materials.  
a
FI 2  
FI 4  
Maximum  
Rated  
Line  
Fault  
Trip  
Fault  
Trip  
Current  
Current  
Current  
Type  
Cat. No.  
Type  
Cat. No.  
16A  
10mA  
FI 21.01 15.921  
25A  
25A  
30mA  
FI 22.03 15.922  
FI 22.30 15.924  
30mA  
300mA  
FI 42.03  
FI 42.30  
15.926  
15.929  
300mA  
40A  
40A  
30mA  
FI 23.03 15.923  
FI 23.30 15.925  
30mA  
300mA  
FI 43.03  
FI 43.30  
15.927  
15.930  
300mA  
Type Designation  
63A  
63A  
30mA  
300mA  
FI 44.03  
FI 44.30  
15.928  
15.931  
__  
__  
__  
(c)  
FI  
(a) (b)  
(a) = 2-2 pole; 4-4 pole  
(b) = 1-16A; 2-25A; 3-40A; 4-63A  
(c) = 01 - 10mA  
Earth Leakage Circuit Breaker  
Earth Leakage Circuit Breaker  
with Auxiliary Contactsb  
with Auxiliary Contactsb  
25A  
40A  
63A  
30mA  
30mA  
FI 22.03Y 15.932  
FI 23.03Y 15.934  
30mA  
30mA  
30mA  
FI 42.03Y  
FI 43.03Y  
FI 44.03Y  
15.933  
15.935  
15.936  
= 03 - 30mA  
= 30 - 300mA  
Voltage Rating (maximum)  
Short Circuit Capacity  
240VAC, 50/60Hz  
(VDE: 125/220VAC, 50Hz)  
415VAC, 50/60Hz (400Hz available on request)  
(VDE: 220/380VAC, 50Hz)  
Up to rated current (RC) 40A = 1.5kA, RC 63A = 2kA. 10kA in combination with series fuse of  
European Operation Class gL/gG: RC 16A = 63A fuse, RC 20/40A = 80A fuse, RC 63A = 100A fuse.  
Fault Trip Current Calibration  
FI trips are calibrated at less than fault trip current for ensured safety (Typical trip range between  
66.6-83.3% fault trip current, e.g., typical trip at 20-25mA for fault RC of 30mA)  
Typical Life  
Fully functional after 4,000 operations to DIN/VDE 0664 (CEE27) and 16000 additional fault current trips.  
Standard Pack and Weight  
1/290g (0.64 lb.);  
1/450g (1.0 lb.)  
1/390g (0.86 lb.) with auxiliary contact  
1/550g (1.21 lb.) with auxiliary contact  
Terminal Size Acceptability  
Equivalent Circuit  
16-6 AWG  
14-3 AWG  
1
N
1 3 5 N  
2
N
Test  
2 4 6 N Test  
a
For 2-Phase applications, terminal 5 and 6 (next  
to Neutral terminals) must be connected to one  
phase for the test circuit to be operable.  
Note: If the power system has a marked conductor, it must connect through the FI and not be grounded at any  
point downstream.  
b
Provided with mounted Auxiliary Switch, one N.O.,  
one N.C. isolated feedthrough contact (Form X  
double make and Y double break), which adds  
9mm (.35 in.) to the width dimension.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
28  
64mm (2.52 in.)  
58mm (2.28 in.)  
8mm  
13.5mm  
13.5mm  
13.5mm  
5.8mm  
(0.23 in.)  
10.9mm  
(0.43 in.)  
22.9mm  
(0.90 in.)  
(0.31 in.) (0.53 in.) (0.53 in.) (0.53 in.)  
1
N
1
3
5
N
46°  
2
N
2
4
6
N
6.5mm  
(0.26 in.)  
3.2mm  
15.7mm  
(0.13 in.) (0.62 in.)  
31mm (1.22 in.)  
9mm  
18mm  
9mm  
18mm  
18mm  
(0.71 in.)  
18mm  
(0.71 in.)  
(0.35 in.) (0.71 in.)  
(0.35 in.) (0.71 in.)  
44mm (1.73 in.)  
72mm (2.83 in.)  
36mm (1.42 in.)  
68mm (2.68 in.)  
FI 2  
FI 4  
FI 2 and FI 4  
Temperature Range  
Environmental Information marked with “Snowflake” approval for -25°C to 40°C (-13°F to 104°F) ambient  
temperature. (Temperature effect on RC: for every 10°C temperature rise above 40°C decrease RC by 7%.)  
Fluctuating Climate Conditions  
Electrical Shock Protection  
To maximum 45°C, 95% relative humidity.  
Uninsulated electrically live parts within 30mm of the operating handle are “finger safe” (terminal screw  
heads) and uninsulated live parts within 100mm of the operating handle are “back-of-hand safe” (terminals).  
15g with impact force half-cycle sinusoidal and 11ms duration, 18 impacts total with 6 on each principal axis  
(3 impacts each face). FI is DIN Rail mounted during the test, and electrically loaded with 25% of Fault RC.  
Successful testing required no trip during the test, no damage and no loosened parts.  
Impact/Shock Protection  
5g, at frequency of 55Hz to 2,000Hz, applied for 35 ± 5 minutes along each of the three principal axes, plus  
5 minutes of application at every established critical resonant frequency. FI is DIN Rail mounted during the  
test, and loaded with 25% Fault RC. To pass, the FI did not trip at 25% Fault RC, but did trip between each  
of the principal axis tests when the fault current was raised to 125% Fault RC, and there was no damage  
and no loosened parts. Suitable for machinery and mobile vehicle applications.  
Vibration/Seismic Resistance  
Ingress Protection (IP) Class 40; internal working components and live parts (excluding terminals) are  
protected against ingress of solid objects greater than 1mm diameter (class 4-), but have no protection from  
ingress of water (class-0).  
Housing Class  
The FI is tested and approval stamped for tripping sensitivity to non-sinusoidal fault currents, which become  
zero or almost zero within one cycle of the line frequency. Waveforms and allowed trip-current ranges are as  
follows:  
Non-Sinusoidal Fault  
1.  
AC Sinusoidal Fault - 0.5-1.0 times Fault RC  
2a.  
2b.  
Pulsating DC Fault;  
Positive and Negative Half-Waves - 0.35-1.4 times Fault RC  
Phased Half-Wave, 90° - 0.25-1.4 times Fault RC  
Phased Half-Wave, 135° - 0.11-1.4 times Fault RC  
3.  
Pulsating DC on 6mA  
DC (continuous) Base - Max. 1.4 times Fault RC + 6mA  
At VDE rated voltage, suitable for Class C environments with relatively high dust and moisture levels and  
little HVAC control, e.g., industrial, commercial, agricultural; on machine tools, hoists, warehouse equipment,  
etc.; in boiler rooms, unheated storage, covered shipping/receiving, open workshops, etc.  
Insulation Category  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
29  
V-EA AND MA  
CIRCUIT BREAKER  
ACCESSORIES  
Accessories can be factory or field  
mounted on V-EA miniature circuit  
breakers and MA motor protection  
switches for enhanced control and  
monitoring  
capabilities.  
Field  
mounting kits include all necessary  
parts and instructions. Accessories  
can be gang mounted on a single  
breaker (the Auxiliary Switch in the  
outside position). The mounting  
arrangement links the internal latch-  
pins for the tripping mechanisms,  
FA  
UA  
ensuring  
simultaneous  
trips.  
Shunt Trip  
Undervoltage Trip  
Handles are linked to simplify  
manual resetting.  
Trip/Coil  
Line Voltage  
50/60Hz  
Type/  
Voltage  
AC/DC  
Max. Coil  
Type  
Cat. No.  
Cat. No.  
Current  
Approvals  
U
L
FA12U  
12V  
24V  
1.3A  
0.6A  
0.2A  
0.25A  
0.5A  
0.8A  
UA120  
UA208  
UA240  
UA277  
UA254  
UA480  
120VAC  
208VAC  
240VAC  
277VAC  
254VAC  
480VAC  
15.956  
15.957  
15.951  
15.958  
15.959  
15.955  
U
L
FA24U  
U
L
FA48U  
48-72V  
110V  
FA110Ua  
FA110Ua  
FA110Ua  
U
L
U
L
220V  
U
L
380VAC  
Std.Pk.: 1  
Std.Pk.: 1  
Unit Weight: 70 grams (0.16 lb.)  
Width: 17.5mm (.689in.)  
Unit Weight: 120 grams (0.27 lb.)  
Width: 17.5mm (.689in.)  
Coil actuated, the FA Shunt Trip allows  
electrical remote tripping of a breaker. It  
is trip-free and the housing and terminal  
specifications are the same as for V-EA  
miniature circuit breakers.The Shunt Trip  
contains its own contacts which break  
the tripping power circuit when tripped. It  
is available with trip-coils in most  
standard control voltages. The device is  
UL and CSA listed for general use.  
Re-power your system under controlled  
conditions following a power loss or  
serious undervoltage. Altech/Sursum UA  
Undervoltage Trips are coupled to the  
tripping latch pins of the V-EA or MA to  
which they are attached, reliably produc-  
ing trips at the drop-out voltage and  
preventing resetting when less than 85%  
line voltage is present. The Undervoltage  
Trip is provided with at least 6-inch  
pigtails of stranded fixture wire for hook-  
up to the V-EA or MA line terminals.  
• Reset-Hold Voltage = 0.85 x Ve  
• Drop-Out Voltage = 0.35 to 0.7 x Ve  
a
One device with wide voltage range.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
30  
Touch protection  
Cat. No. 15.962 (top) and 15.961 (bottom)  
The V-EA protects against electrical shock  
during manual actuation in accordance with  
VDE 0106/Part 100 and VDE 0470/Part 1,  
with “finger safe” terminal-screw heads and  
“back of hand” safe terminals. If additional  
“touch” protection is desired, separate touch  
protector covers can easily be snapped on to  
the V-EA top and/or bottom terminals.  
H
Auxiliary Switch  
Lock-out  
Cat. No. 15.969  
Type/  
Cat. No.  
Prevent inadvertent  
resetting of the V-EA or MA  
during maintenance.  
Approvals For Use With:  
U
L
H1U  
V-EA, MA  
FI  
HFI11  
Std. Pk.: 1  
Unit Weight: 45 grams (0.12 lb.)  
Width: 9mm (.354in.)  
Ring Tongue  
Terminals  
Contact Ratings  
H1U  
Available for VE-A and  
HFI11  
MA series. Please  
specify when ordering  
and refer to type  
designation.  
10A / 220V AC  
6A / 230V AC  
3A / 110V DC or pulsed  
1A / 220V DC or pulsed 1A / 220V DC or pulsed  
Wire Size (max.)  
4mm2 (12 AWG)  
4mm2 (12 AWG)  
Two isolated, feedthrough Form X and  
Y contacts are provided: one with the  
same form as the breaker (HS designa-  
tion, closed auxiliary contacts when  
breaker is on and breaker contacts are  
closed); and one with the opposite form  
as the breaker (HO designation, closed  
auxiliary contacts when breaker is  
tripped and breaker contacts are open).  
Upper level terminals are metal-  
stamped "HS" and lower level terminals  
are stamped "HO", providing clear iden-  
tification for drawings and physical  
wiring (line/load on either terminal).  
Busbar Systems  
(please see pgs. 32-35  
for your busbar needs)  
Cooling Spacer  
Cat. No. 15.960  
(see also Correction  
Curve, pg. 22)  
Altech/Sursum H Auxiliary Switch is  
suitable for logic interrogation and for  
use as a two-circuit Form C contact. It  
can also function as an auxiliary switch  
for control circuits. The H1U is UL and  
CSA listed for general use.  
V-EA and MA can also be locked in the on and off position by  
simply using a common lead or meter seal, which gets fed  
through the hole in the handle and a corresponding hole in  
the case housing.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
31  
ALTECH BUSBAR SYSTEMS  
The Altech Busbar system is an innovative  
Without Busbar  
way to jumper up to 57 poles of Altech  
Miniature Circuit Breakers (MCB)/ Manual  
Motor Controllers (MMC).  
The advantages of this jumper system are:  
• Installation time savings  
• Panel space savings  
• Less or no maintenance  
• High electrical ratings  
With Busbar  
• Customers can cut the busbar  
without losing the UL approval  
Two Power Feed Methods  
START/ END Feed Method  
CENTER/ MIDDLE Feed Method  
Rated current per phase  
Rated current per power feed block  
L1  
L2  
80A  
L3  
80A  
L1  
L2  
L3  
18mm2 : 80A  
18mm2 : 160A* 160A* 160A*  
25mm2 : 200A* 200A* 200A*  
25mm2 : 100A 100A 100A  
L1  
L2  
L3  
80/100A  
80/100A  
80/100A  
80/100A  
80/100A  
80/100A  
80/100A  
80/100A  
80/100A  
Please note: The 160-200A rating is pending upon  
successful completion of UL testing.  
*
L1  
L2  
L3  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
32  
POWER FEED DEVICES  
Power Feed Lug  
Power Feed Block*  
Application examples:  
UL508 listed  
UL File 205412  
Easy connection of the power supply wires to  
the busbar/MCB. Power Feed Devices  
ensures permanent connection.  
Type Designation:  
P
50  
U
T
(c) (b) (c) (d)  
DIN Rail Clip  
(a) = Power Feed lug/block  
(b) = 50mm2 or 95mm2 cross-section area  
16 mm  
(0.63 in.)  
(c) = USA and Canadian design basics  
(d) = T-Terminal connection  
B-Busbar connection  
31.6 mm  
(1.24 in.)  
31.6 mm  
(1.24 in.)  
11 mm  
(0.43 in.)  
35.6 mm  
(1.40 in.)  
35.6 mm  
(1.40 in.)  
63 mm  
(2.48 in.)  
B
A
B
A
6.8 mm (0.27 in.)  
3 mm (0.12 in.)  
88.5 mm  
(3.48 in.)  
Type/Cat. No:  
P50UT  
115A/480VAC  
10-1 AWG  
P95UB  
*
Electrical Ratings  
Terminal Site Acceptability  
Recommended/Required Torque  
Material of Lug  
200A/480VAC  
3-4/0 AWG  
4.5Nm (40lb. in.)  
MS58 Brass  
7Nm (62lb. in.)  
MS58 Brass  
Insulation Material  
For use with  
Zytel FR 72G25-V Plastic  
18 and 25mm2 1-3 phase Busbar  
Zytel FR 72G25-V Plastic  
18 and 25mm2 3 phase Busbar  
ASSEMBLY INSTRUCTIONS  
P50UT  
P95UB  
The power feed lugs (Cat. # P50UT) fit together with the lugs of  
the busbar in the terminals of the MCB/MA.  
*Subject to UL approval.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
33  
1 PHASE  
BUSBAR ORDERING  
INFORMATION  
UL508 listed  
UL File 205412  
For choosing the proper busbar, please  
consider the following specifications:  
56 x 17.8 = 996.8 mm (39.24 in.)  
17.8 mm (0.70 in.)  
1. Number of phases  
3.5 mm (0.14 in.)  
2 mm (0.79 in.)  
2. Number of devices / MMCs  
3. Number of poles/number of pins  
4. Sum of out going device currents  
15 mm (0.59 in.)  
1007 mm (39.65 in.)  
18mm2  
Type/Cat. No.  
No. of  
Pins ❶  
No. of MMC  
to Jumper  
Length/  
mm  
Type/Cat. No. Designation:  
3
P
25  
U
3
H
/ —  
1P18U1/2  
1P18U1/4  
1P18U1/8  
1P18U1/12  
1P18U1/24  
1P18U1/36  
1P18U1/48  
1P18U1/57  
2
2x1 pole  
4x1 pole  
32  
68  
(a) (b) (c) (d) (e) (f)  
(g)  
4
(a) = Number of transverse copper strips  
inserted. (Can be 1, 2 or 3 for  
1, 2 or 3 phases)  
8
8x1 pole  
144  
208  
420  
638  
852  
1009  
12  
24  
36  
48  
57  
12x1 pole  
24x1 pole  
36x1 pole  
48x1 pole  
57x1 pole  
(b) = Pin version  
(c) = 18mm2 or 25mm2 cross-section area  
(d) = USA and Canadian design basics  
(e) = 1 or 3 track insulation  
(f) = Blank - No Spacing  
H-Auxiliary Switch (1/2 pole)  
spacing  
1 PHASE  
UL508 listed  
UL File 205412  
(g) = Total number of pins  
Technical Specifications:  
36 x 27 = 972 mm (38.27 in.)  
27 mm (1.06 in.)  
• Material of Busbar: E-Cu58 F25 Copper  
2 mm (0.79 in.)  
4mm (0.16 in.)  
• Insulation Track Material:  
Noryl ENV 130 Plastic  
• Electrical Ratings:  
18mm2: 80A/480VAC  
25mm2: 100A/480VAC  
15 mm (0.59 in.)  
• Manufactured according to VDE 0660  
Part 100 and 502, VDE 0606, VDE 0659  
982 mm (38.66 in.)  
With Auxiliary Switch (1/ 2 pole) Spacing  
18mm2  
Type/Cat. No.  
No. of  
Pins ❶  
No. of MMC  
to Jumper  
Length/  
mm  
NOTES:  
1P18U1H/2  
1P18U1H/4  
1P18U1H/8  
1P18U1H/12  
1P18U1H/18  
1P18U1H/24  
1P18U1H/30  
1P18U1H/37  
2
2x1 pole  
4x1 pole  
48  
Do not exceed the busbars rated current.  
4
102  
206  
314  
472  
640  
804  
982  
For additional pin configurations,  
please consult Altech.  
8
8x1 pole  
12  
18  
24  
30  
37  
12x1 pole  
18x1 pole  
24x1 pole  
30x1 pole  
37x1 pole  
For one pole spacing busbars, please consult Altech.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
34  
2 PHASE  
3 PHASE  
UL508 listed  
UL File 205412  
UL508 listed  
UL File 205412  
55 x 17.75 = 976 mm (38.43 in.)  
17.75 mm  
(0.70 in.)  
56 x 17.75 = 994 mm (39.13 in.)  
17.75 mm  
(0.70 in.)  
2 mm (.079 in.)  
2 mm (.079 in.)  
7 mm  
(0.28 in.)  
7 mm  
(0.28 in.)  
L2 L1  
L3 L2 L1  
21 mm  
(0.83 in.)  
21 mm  
(0.83 in.)  
Copper strips  
Insulation Track  
Copper strips  
Insulation Track  
End Cap  
End Cap  
End Cap  
End Cap  
L3 L2 L1  
L2 L1  
1009 mm (39.72 in.)  
991 mm (39.02 in.)  
18mm2  
Type/Cat. No.  
25mm2  
Type/Cat. No.  
No. of  
Pins ❶  
No. of MMC  
to Jumper  
Length/  
mm  
18mm2  
Type/Cat. No.  
25mm2  
Type/Cat. No.  
No. of  
Pins ❶  
No. of MMC Length/  
to Jumper  
mm  
2P18U3/4  
2P18U3/8  
2P25U3/4  
2P25U3/8  
4
2x2 pole  
4x2 pole  
6x2 pole  
9x2 pole  
12x2 pole  
18x2 pole  
24x2 pole  
28x2 pole  
65  
3P18U3/6  
3P18U3/9  
3P25U3/6  
3P25U3/9  
6
2x3 pole  
3x3 pole  
4x3 pole  
6x3 pole  
8x3 pole  
12x3 pole  
16x3 pole  
19x3 pole  
101  
154  
208  
315  
421  
635  
849  
1009  
8
137  
208  
315  
421  
635  
849  
991  
9
2P18U3/12  
2P18U3/18  
2P18U3/24  
2P18U3/36  
2P18U3/48  
2P18U3/56  
2P25U3/12  
2P25U3/18  
2P25U3/24  
2P25U3/36  
2P25U3/48  
2P25U3/56  
12  
18  
24  
36  
48  
56  
3P18U3/12  
3P18U3/18  
3P18U3/24  
3P18U3/36  
3P18U3/48  
3P18U3/57  
3P25U3/12  
3P25U3/18  
3P25U3/24  
3P25U3/36  
3P25U3/48  
3P25U3/57  
12  
18  
24  
36  
48  
57  
2 PHASE  
3 PHASE  
UL508 listed  
UL File 205412  
UL508 listed  
UL File 205412  
15 x 62.3 = 934.5 mm  
22 x 44.5 = 979 mm (38.54 in.)  
44.5 mm (1.75 in.)  
17.8 mm (0.70 in.)  
62.3 mm (2.45 in.)  
2 mm (.079 in.)  
17.8 mm  
(0.70 in.)  
7 mm (0.28 in.)  
2 mm (.079 in.)  
7 mm (0.28)  
21 mm  
(0.83 in.)  
21 mm  
(0.83 in.)  
1009 mm (39.72 in.)  
982 mm (38.66 in.)  
With Auxiliary Switch (1/ 2 pole) Spacing  
With Auxiliary Switch (1/ 2 pole) Spacing  
18mm2  
Type/Cat. No.  
25mm2  
Type/Cat. No.  
No. of  
Pins ❶  
No. of MMC  
to Jumper  
Length/  
mm  
18mm2  
Type/Cat. No.  
25mm2  
Type/Cat. No.  
No. of  
Pins ❶  
No. of MMC Length/  
to Jumper  
mm  
2P18U3H/4  
2P18U3H/8  
2P18U3H/12  
2P18U3H/18  
2P18U3H/24  
2P18U3H/36  
2P18U3H/46  
2P25U3H/4  
2P25U3H/8  
2P25U3H/12  
2P25U3H/18  
2P25U3H/24  
2P25U3H/36  
2P25U3H/46  
4
2x2 pole  
4x2 pole  
6x2 pole  
9x2 pole  
12x2 pole  
18x2 pole  
23x2 pole  
74  
164  
253  
386  
520  
787  
1009  
3P18U3H/6  
3P18U3H/9  
3P18U3H/12  
3P18U3H/18  
3P18U3H/24  
3P18U3H/36  
3P18U3H/48  
3P25U3H/6  
3P25U3H/9  
3P25U3H/12  
3P25U3H/18  
3P25U3H/24  
3P25U3H/36  
3P25U3H/48  
6
2x3 pole  
3x3 pole  
4x3 pole  
6x3 pole  
8x3 pole  
12x3 pole  
16x3 pole  
110  
172  
235  
359  
484  
733  
982  
8
9
12  
18  
24  
36  
46  
12  
18  
24  
36  
48  
For one pole spacing busbars, please consult Altech.  
For one pole spacing busbars, please consult Altech.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
35  

相关型号:

3ZU16

Thermal Magnetic Circuit Breaker,
ALTECH

3ZU2.5

Thermal Magnetic Circuit Breaker,
ALTECH

3ZU25

Thermal Magnetic Circuit Breaker,
ALTECH

3ZU3.5

Thermal Magnetic Circuit Breaker,
ALTECH

3_3VSPC

3.3V 233MHz AMD K6? Processor Specifications
ETC

4--21028--4

Pneumatic CERTI-CRIMP Tool Holder
MACOM

4--21028--9

Pneumatic CERTI-CRIMP Tool Holder
MACOM

4--435166--9

Dual In- Line Package
TE

4--435626--0

Dual In- Line Package
TE

4--435626--1

Dual In- Line Package
TE

4--435626--2

Dual In- Line Package
TE

4--435626--3

Dual In- Line Package
TE