S-TS800NU-FTU-LL-600 [ALTECH]
Thermal Magnetic Circuit Breaker,;型号: | S-TS800NU-FTU-LL-600 |
厂家: | ALTECH CORPORATION |
描述: | Thermal Magnetic Circuit Breaker, |
文件: | 总12页 (文件大小:2883K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
TD / TS Series
Molded Case
Circuit Breakers
UL489 Listed
Molded Case
Circuit Breaker
• 4 Frame Sizes
• Compact Design
• Thermal Magnetic
• 240, 480, 600VAC
• 3 Poles
LISTED
E231289
• Up to 100kA Short Circuit Interrupting Capacity
• Circuit Breakers are supplied with line and load terminals
• HACR rated
• CE version (without UL approval) available upon request
SPECIFICATIONS
Current Rating
15-125A / 600V AC
150-250A / 600V AC
300-400A / 600V AC
500-800A / 600V AC
Wire Ratings
60°/ 75°C Cu only
60°/ 75°C Cu only
75°C Cu only
Calibration Temperature
TD125
TS250
TS400
TS800
40°C (104°F)
75°C Cu only
INTERRUPTING CAPACITY
TD125
TS250
TS400
TS800
NU HU NU HU NU HU NU HU
240V 50 100 50 100 50 100 50 100
480V 35
600V 10
65
14
35
10
65
18
35 65
14 20
35 65
18 25
TERMINAL SIZE ACCEPTABILITY AND TERMINAL TORQUE
Frame Types
Wire Range
Tightening Torque
[lb.in.]
Conductor
Cross-section
Number of
Conductors
TD125 (15 - 125A)
TS250 (150 - 250A)
14 - 8 AWG
6 - 1/0 AWG
1 AWG
1/0 - 2/0 AWG
3/0 - 4/0 AWG
300 - 400 kcmil
250 - 400 kcmil
500 kcmil
1
1
1
1
1
1
1
1
2
60
90
150
180
250
325
325
375
250
375
500
500
TS400 (300 - 400A)
3/0 AWG
TS800 (500 - 600A)
TS800 (700 - 800A)
250 - 500 kcmil
300 - 500 kcmil
300 - 400 kcmil
up to 2
up to 2
up to 3
TRIP CHARACTERISTICS
FTU
Fixed-Thermal
Fixed-Magnetic
Adjustable-Thermal
Fixed-Magnetic
Adjustable-Thermal
Adjustable-Magnetic
Rated current
See trip curve pages 76-77
0.8 - 1 x current adjustable
See trip curve pages 76-77
0.8 - 1 x current adjustable
5 - 10 x current adjustable
FMU
ATU
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
66
PART NUMBERING SYSTEM
S –
TD125
NU – FTU – LL – 15
Frame Type
TD125: 15-125A
TS250: 150-250A
TS400: 300-400A
TS800: 500-800A
Interrupting Type
NU, HU
See page 66
Trip Type
FTU, FMU, ATU
Rated Current (A)
15, 20, ..., 800
DIMENSIONS
Dimensions
Frame types
Basic Dimensions W x H x D [inch/mm]
TD125
TS250
TS400
TS800
3.54 x 6.46 x 3.39/90 x 164 x 86
4.13 x 7.01 x 3.39/105 x 178 x 86
5.51 x 11.5 x 4.33/140 x 292 x 110
8.27 x 16.85 x 5.31/210 x 428 x 135
W
D
Accessories device
Mechanical
(S-AL, S-AX, S-UVT, S-SHT)
interlock device
Circuit
breaker
Locking devices
(Removable, Fixed)
Trip units
Extended
rotary handle
Flange handle
(Cable operating handle)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
67
TD / TS Series
Circuit Breakers
Normal Interrupting
Capacity (NU)
Circuit Breakers are supplied with line and load terminals
Interrupting Capacity
Application Examples:
Power distribution, power generation,
motors, etc. Relatively short thermal trip
delay and medium magnetic trip point.
TD125
50
TS250
50
TS400
50
TS800
50
240V
480V
600V
35
35
35
35
10
10
14
18
LISTED
E231289
FTU
FMU
ATU
TS250FTU
TS250FMU
1848
1584
1320
2112
2376
2640
24500°CA
24500°CA
Im=2500A
Im=2500A
3P
3P
Ir Im
Ir Im
Rated
Type/
Cat. No.
Rated
Current
15A
Type/
Cat. No.
FMU*
Adjustable-
thermal, Fixed-
magnetic
FTU
Fixed-thermal,
Fixed-magnetic
Current
40A
50A
S-TD125NU-FMU-LL-40
S-TD125NU-FMU-LL-50
S-TD125NU-FMU-LL-60
S-TD125NU-FMU-LL-80
S-TD125NU-FMU-LL-100
S-TD125NU-FMU-LL-125
S-TS250NU-FMU-LL-160
S-TS250NU-FMU-LL-200
S-TS250NU-FMU-LL-250
S-TS400NU-FMU-LL-300
S-TS400NU-FMU-LL-400
S-TS800NU-FMU-LL-500
S-TS800NU-FMU-LL-600
S-TS800NU-FMU-LL-800
S-TD125NU-FTU-LL-15
S-TD125NU-FTU-LL-20
S-TD125NU-FTU-LL-30
S-TD125NU-FTU-LL-40
S-TD125NU-FTU-LL-50
S-TD125NU-FTU-LL-60
S-TD125NU-FTU-LL-80
S-TD125NU-FTU-LL-100
S-TD125NU-FTU-LL-125
S-TS250NU-FTU-LL-150
S-TS250NU-FTU-LL-160
S-TS250NU-FTU-LL-175
S-TS250NU-FTU-LL-200
S-TS250NU-FTU-LL-225
S-TS250NU-FTU-LL-250
S-TS400NU-FTU-LL-300
S-TS400NU-FTU-LL-350
S-TS400NU-FTU-LL-400
S-TS800NU-FTU-LL-500
S-TS800NU-FTU-LL-600
S-TS800NU-FTU-LL-700
S-TS800NU-FTU-LL-800
20A
30A
60A
80A
40A
50A
100A
125A
160A
200A
250A
300A
400A
500A
600A
800A
60A
80A
100A
125A
150A
160A
175A
200A
225A
250A
300A
350A
400A
500A
600A
700A
800A
Standard Pack: 1
Weight:
TD125: 2.65 lb.
TS250: 4.19 lb.
TS400: 12.57 lb.
TS800: 29.98 lb.
TS250ATU
1848
1584
1320
2112
2376
2640
1848
1584
1320
2112
2376
2640
24500°CA
3P
Standard Pack: 1
Weight:
Ir Im
Rated
Type/
Cat. No.
ATU*
Adjustable-
thermal,
Adjustable-
magnetic
TD125: 2.65 lb.
TS250: 4.19 lb.
TS400: 12.57 lb.
TS800: 29.98 lb.
Current
160A
200A
250A
300A
400A
500A
600A
800A
S-TS250NU-ATU-LL-160
S-TS250NU-ATU-LL-200
S-TS250NU-ATU-LL-250
S-TS400NU-ATU-LL-300
S-TS400NU-ATU-LL-400
S-TS800NU-ATU-LL-500
S-TS800NU-ATU-LL-600
S-TS800NU-ATU-LL-800
Accessories (see pages 70-72)
Dimensions (see pages 73-75)
Trip Curves (see pages 76-77)
Standard Pack: 1
Weight:
TD125: 2.65 lb.
TS250: 4.19 lb.
TS400: 12.57 lb.
TS800: 29.98 lb.
* Not a stock item, please consult Altech for availability.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
68
TD / TS Series
Circuit Breakers
High Interrupting
Capacity (HU)
Circuit Breakers are supplied with line and load terminals
Interrupting Capacity
Application Examples:
Power distribution, power generation,
motors, etc. Relatively short thermal trip
delay and medium magnetic trip point.
TD125
100
65
TS250
100
65
TS400
100
65
TS800
100
65
240V
480V
600V
14
18
20
25
LISTED
E231289
FTU
FMU
ATU
TS250FTU
TS250FMU
1848
1584
1320
2112
2376
2640
24500°CA
24500°CA
Im=2500A
Im=2500A
3P
3P
Ir Im
Ir Im
FMU*
Adjustable-thermal,
Fixed-magnetic
Rated
Current
15A
Type/
Cat. No.
Rated
Type/
Cat. No.
FTU
Fixed-thermal,
Fixed-magnetic
Current
40A
50A
S-TD125HU-FTU-LL-15
S-TD125HU-FTU-LL-20
S-TD125HU-FTU-LL-30
S-TD125HU-FTU-LL-40
S-TD125HU-FTU-LL-50
S-TD125HU-FTU-LL-60
S-TD125HU-FTU-LL-80
S-TD125HU-FTU-LL-100
S-TD125HU-FTU-LL-125
S-TS250HU-FTU-LL-150
S-TS250HU-FTU-LL-160
S-TS250HU-FTU-LL-175
S-TS250HU-FTU-LL-200
S-TS250HU-FTU-LL-225
S-TS250HU-FTU-LL-250
S-TS400HU-FTU-LL-300
S-TS400HU-FTU-LL-350
S-TS400HU-FTU-LL-400
S-TS800HU-FTU-LL-500
S-TS800HU-FTU-LL-600
S-TS800HU-FTU-LL-700
S-TS800HU-FTU-LL-800
S-TD125HU-FMU-LL-40
S-TD125HU-FMU-LL-50
S-TD125HU-FMU-LL-60
S-TD125HU-FMU-LL-80
S-TD125HU-FMU-LL-100
S-TD125HU-FMU-LL-125
S-TS250HU-FMU-LL-160
S-TS250HU-FMU-LL-200
S-TS250HU-FMU-LL-250
S-TS400HU-FMU-LL-300
S-TS400HU-FMU-LL-400
S-TS800HU-FMU-LL-500
S-TS800HU-FMU-LL-600
S-TS800HU-FMU-LL-800
20A
30A
60A
80A
40A
50A
100A
125A
160A
200A
250A
300A
400A
500A
600A
800A
60A
80A
100A
125A
150A
160A
175A
200A
225A
250A
300A
350A
400A
500A
600A
700A
800A
Standard Pack: 1
Weight:
TD125: 2.65 lb.
TS250: 4.19 lb.
TS400: 12.57 lb.
TS800: 29.98 lb.
TS250ATU
1848
1584
1320
2112
2376
2640
1848
1584
1320
2112
2376
2640
24500°CA
3P
Ir Im
Standard Pack: 1
Weight:
Rated
Type/
Cat. No.
ATU*
Adjustable-
thermal,
Adjustable-
magnetic
TD125: 2.65 lb.
TS250: 4.19 lb.
TS400: 12.57 lb.
TS800: 29.98 lb.
Current
160A
200A
250A
300A
400A
500A
600A
800A
S-TS250HU-ATU-LL-160
S-TS250HU-ATU-LL-200
S-TS250HU-ATU-LL-250
S-TS400HU-ATU-LL-300
S-TS400HU-ATU-LL-400
S-TS800HU-ATU-LL-500
S-TS800HU-ATU-LL-600
S-TS800HU-ATU-LL-800
Accessories (see pages 70-72)
Dimensions (see pages 73-75)
Trip Curves (see pages 76-77)
Standard Pack: 1
Weight:
TD125: 2.65 lb.
TS250: 4.19 lb.
TS400: 12.57 lb.
TS800: 29.98 lb.
* Not a stock item, please consult Altech for availability.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
69
Accessories
Electrical Auxiliaries
Auxiliary Switch (S-AX), Alarm Switch (S-AL)
• Can be installed in all frame types
Contact Operation
MCCB
ON
OFF
TRIP
Cat. No.
S-AX
AXa1
AXb1
AXa1
Position
of S-AX
AXc1
AXc1
AXb1
AXa1
AXb1
AXa1
AXb1
Position
of S-AL
AXc1
AXc1
S-AL
Installation - see page 71
Technical Data
Conventional thermal current I
5A
th
Rated operational current I
with rated operational voltage U
I (A)
e
e
Voltage
Resistive Load Inductive Load
e
- Altemating current 50/60Hz AC
125V
250V
30V
5
3
3
2
- Direct current DC
4
3
125V
250V
0.4
0.2
0.4
0.2
Installation - see page 71
Shunt Release, S-SHT
• Can be installed in all frame types
• Range of operational voltage: 0.7 - 1.1 x Vn
• Frequency (only AC): 45Hz - 65Hz
Technical Data
Consumption
AC (VA) DC (W)
Control voltage (V)
mA
30
24
Cat. No.
S-SHT-12
S-SHT-24
S-SHT-48
S-SHT-120
S-SHT-230
S-SHT-440
DC 12V
AC/DC 24V
AC/DC 48V
AC/DC 110~130V
AC 220~240V/DC250V
AC 380~500V
-
0.36
0.58
1.23
1.37
1.88
-
Power
consumption
0.58
1.22
1.36
1.80
1.15
25
10.5
7.5
2.3
Max. opening time (msec)
50
Tightening torque of terminal screw
Installation - see page 71
7.1 lb.in.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
70
Accessories
Electrical Auxiliaries
Undervoltage Release, S-UVT
• Can be installed in all frame types
• Reset-Hold Voltage = 0.85 x Vn
• Drop-Out Voltage = 0.35 - 0.7 x Vn
• Frequency (only AC): 45Hz - 65Hz
Technical Data
Control voltage (V)
AC/DC 24V
Consumption
AC (VA) DC (W)
mA
27
23
5.8
5.4
3.8
3.5
Cat. No.
0.64
1.09
0.73
1.21
1.67
1.68
0.65
1.10
0.75
1.35
-
S-UVT-24
S-UVT-48
S-UVT-120
S-UVT-230
S-UVT-410
S-UVT-460
Power
AC/DC 48V
consumption
AC/DC 110~130V
AC 200~240V/DC 250V
AC 380~440V
AC 440~480V
-
Max.opening time (msec)
50
Tightening torque of terminal screw
Transformer operating voltage (V)
- Drop (Circuit breaker trips)
7.1 lb.in.
0.7~1.35Vn
~0.85Vn
- Rise (Circuit breaker can be switched on)
Installation - Maximum possibilities
Position
Accessory
S-AX
TD125
TS250
TS400
TS800
–
1
1
2
–
1
1
1
1
–
3
–
1
–
1
3
–
1
–
2
Left
S-AL
S-SHT or S-UVT
S-AX
Right
S-AL
TD125
TS250
TS400
TS800
AL
AX AX
AX
AX
AL
SHT/
UVT
AX AX AX
SHT/
UVT
AL
AL AL
AX AX AX
SHT/
UVT
SHT/
UVT
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
71
Accessories
Handle Kits
Extended Rotary Handle Kits*
Shaft length: 12”, (16”, 24”, upon request)
Frame Type
Cat. No.
NEMA 1, 3R, 12
S-EHU1-12
S-EHU2-12
S-EHU3-12
S-EHU4-12
Cat. No.
NEMA 4X
S-EHU1-12/NEMA 4X
S-EHU2-12/NEMA 4X
S-EHU3-12/NEMA 4X
S-EHU4-12/NEMA 4X
TD125
TS250
TS400
TS800
Dimensions (see page 75)
Flange Handle Kits*
Frame Type
Cable**
Cat. No.
NEMA 1, 3R, 12
S-FH1-36
Length
36”
48”
TD125
TS250
TS400
TS800
S-FH2-48
S-FH3-60
S-FH4-72
Flange handle
(Cable operating handle)
60”
72”
For use with only right handed
flange type enclosures.
* Kits include all necessary hardware to mount to MCCB
** Longer cable available upon request.
Locking Devices
Mechanical Interlocking Device
Fixed Locking Device
Cat. No.
Cat. No.
Padlockable Device
S-PHL1
MCCB
TD125
TS250
TS400
TS800
Padlocks are not supplied.
Interlocking Device
S-MIT13
S-MIT23
MCCB
TD125
TS250
TS400
TS800
Function
OFF or ON position
OFF or ON position
OFF or ON position
OFF or ON position
S-PHL2
S-PHL3
S-PHL4
S-MIT33
S-MIT43
Padlocks are not supplied.
0.2~0.3inch
(5~8mm)
Interlock handle
Interlock bar
Padlock dimensions
1.2inch
(30mm)
Removable Locking Device
Cat. No.
MCCB
TD125
TS250
TS400
TS800
Function
Padlockable device
S-PL1
S-PL2
OFF position
OFF position
OFF position
OFF position
S-PL3
S-PL4
Padlocks are not supplied.
Cover Aux.
0.2~0.3inch
(5~8mm)
1.2inch
(30mm)
Padlock dimensions
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
72
TD / TS Series
Circuit Breakers
Dimensions
TD125
3.035 (77.1)
2.958 (75.15)
2.716 (69)
3.543 (90)
3.389 (86.1)
3.496 (88.81)
3.625 (92.1)
4.212 (107)
0.578 (14.7)
TS250
3.385 (86)
2.952 (75)
2.716 (69)
4.133 (105)
0.629 (16)
3.546 (90.1)
3.661 (93)
4.318 (109.7)
Dimensions shown in inches (mm)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
73
TD / TS Series
Circuit Breakers
Dimensions
TS400
4.33 (110)
3.838 (97.5)
3.11 (79)
5.511 (140)
4.645 (118)
4.842 (123)
1.082 (27.5)
6.181 (157)
TS800
5.846 (148.5)
5.511 (140)
4.566 (116)
3.543 (90)
8.267 (210)
3.149 (80)
4.685 (119)
5.039 (128)
5.314 (135)
7.775 (197.5)
Dimensions shown in inches (mm)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
74
Overall Dimensions - Extended Rotary Handles
Panel drilling
1.18 (30)
1.10 (28)
14.5 (368.3)
TD125
12 in. Shaft: 14.5(368.3)
24 in. Shaft: 26.5(673.1)
Dimensions : inch
(mm)
0.433 (11)
1.39 (35.3)
1.38 (35)
14.54 (369.3)
12 in. Shaft: 14.54 (369.3)
TS250
24 in. Shaft: 26.54 (674.1)
Dimensions : inch
(mm)
0.433 (11)
15.93 (404.6)
1.39 (35.3)
1.83 (46.5)
12 in. Shaft: 15.93 (404.6)
TS400
24 in. Shaft: 27.93 (709.4)
Dimensions : inch
(mm)
0.433 (11)
17.42 (442.5)
12 in. Shaft: 15.93 (404.6)
TS800
24 in. Shaft: 27.93 (709.4)
2.22 (56.3)
2.76 (70)
Dimensions : inch
(mm)
0.433 (11)
Panel drilling for MCCB
Panel drilling rotary handle
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
75
TD / TS Series
Circuit Breakers
Trip Curves
TD125 - FTU/FMU; 15~125A
FTU:Ir=1× In
FMU:Ir=0.8~1× In
TD125 / TS250
TS400 / TS800
140
130
120
110
100
90
Calibration Temp.104°F
80
In:15A -> Im=400A
In:20A -> Im=400A
In:30A -> Im=400A
In:40A -> Im=400A
70
20 30 40 50 60 70 80 90 100 110 120
FTU/FMU:Im=10× In
Ambient Temperature (°F)
Min. 400A
0.5
0.8
1
2
3
4
5
6
7
8
10
20
30 40 50 70 100
200 300
X Normal Current In (I/Ir)
TS250 - FTU/FMU; 150~250A
TS250 - ATU; 160~250A
FTU:Ir=1 × In
ATU:Ir=0.8~1× In
FMU:Ir=0.8~1× In
ATU:Im=5~10× In
FTU/FMU:Im=10× In
pressure tripping
10ms
pressure tripping
t
t
10ms
0.5
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
76
TD / TS Series
Circuit Breakers
Trip Curves
TS400 - FTU/FMU; 300~400A
TS400 - ATU; 300~400A
FTU:Ir=1 × In
ATU:Ir=0.8~1× In
FMU:Ir=0.8~1× In
ATU:Im=5~10 × In
FTU/FMU:Im=10 × In
pressure tripping
10ms
pressure tripping
10ms
t
t
TS800 - FTU/FMU; 500~800A
TS800 - ATU; 500~800A
FTU:Ir=1 × In
ATU:Ir=0.8~1× In
FMU:Ir=0.8~1× In
FTU/FMU:Im=10× In
ATU:Im=5~10 × In
pressure tripping
10ms
pressure tripping
10ms
t
t
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com
77
相关型号:
S002611
Power Bipolar Transistor, 10A I(C), 60V V(BR)CEO, 1-Element, PNP, Silicon, TO-220AB, Plastic/Epoxy, 3 Pin, TO-220, 3 PIN
CENTRAL
©2020 ICPDF网 联系我们和版权申明