Modus W Series  
General Eastern Liquid  
Differential Pressure  
Transmitters  
The Modus W Series pressure transmitters are  
designed to measure low differential pressures  
of liquids or gases. A wide selection of standard  
pressure ranges and electrical ratings is available.  
The transmitters are housed in a compact,  
heavy duty, gasketted, cast aluminum  
enclosure designed to IP 65 of IEC 529  
standards and Type 4. The die cast aluminum  
enclosure incorporates a recessed neoprene  
gasket to prevent the ingress of moisture or  
dust. Wall mounting holes are enclosed in  
the cast aluminum box and concealed by the  
cover. The wall mounting holes and the cover  
attaching screws are outside the gasketted  
area.  
These transmitters feature no moving parts  
to wear out, a proven long term stability of  
piezoresistive devices, only 316 stainless steel  
in contact with the fluid, and an all-welded  
construction.  
Modus W Series transmitters are an excellent  
choice for many HVAC, process and automation  
monitoring requirements. Typical applications  
include measurement of differential pressure  
across flow elements, heat exchangers, pumps  
and filters, liquid level monitoring and other  
demanding differential pressure measurement  
and control applications.  
Access to the electrical terminals are made  
through knockouts on the front of the box. A  
choice of two knockouts and three hole sizes  
are available to accommodate usage of 0.5  
in (12.7 mm) conduit or metric sizes PG11 and  
PG13.  
Pluggable terminal block connectors are  
provided with wire protection and captive  
terminal screws.  
The Modus W Series includes one model:  
Model W30.  
Amphenol  
Advanced Sensors  
This model is available with the following power and  
signal configuration:  
Operation  
The pressure transmitter consists of two high accuracy  
piezoresistive sensors with stainless steel isolation  
diaphragms. Both sensors measure static pressure, and  
the difference between these two measurements is  
computed electronically. The use of high accuracy and  
stable sensors makes this measurement possible. Since  
each sensor measures the full static pressure, there is  
no possibility of over-pressurizing the transmitter if one  
sensor is disconnected from the line. No complex and/  
or expensive balancing valves are needed.  
Model W30  
• Two-wire  
• DC Voltage In  
• 4 to 20 mA out  
The span or zero adjustment is performed with a  
20-turn potentiometer for fine resolution. A 50%  
adjustment in output is possible.  
The Series W transmitters comply with the European  
requirements of Council Directive 2004/108/EC.  
Electrical Connectors  
W Series  
Polarized Euro plug/connectors.  
Specifications  
Connections  
Pluggable terminal block for wire 14 to 26 AWG.  
Mating connector is supplied  
Performance  
Accuracy  
Connection to enclosure ground is provided.  
1/2% of differential pressure range (includes non-  
linearity and hysteresis) or 1% for 6 psid (50 kPA)  
range  
Connector rating  
10 Amps/300 V  
Effect of Static Pressure on Differential Pressure  
Material  
Glass-filled polyester  
Measurement  
Less than 0.25% for static pressure change from 0 to  
100% or 0.5% for 6 psid (50 kPa) range  
Physical  
Calibration  
Traceable to National Institute of Standards and  
Technology (NIST)  
Dimensions  
3.56 in x 4.54 in x 2.18 in (90 mm x 115 mm x 55 mm)  
Enclosure material  
Aluminum Alloy #A380  
Environmental  
Process wetted surfaces are 316 stainless steel.  
Cover screws  
M4 stainless steel non-magnetic  
Operating Temperature Range  
32°F to 122°F (0°C to 50°C)  
Finish  
Black epoxy paint  
Storage Temperature  
-20°F to 160°F (-30°C to 70°C)  
Knockout  
Choice of 2 holes  
Effect of Temperature  
On zero: 0.05%/°C or 0.1%/°C for 6 psid (50 kPa)  
Hole sizes are offered in a choice of 1/2 in (12.7 mm)  
conduit or metric sizes of PG11 or PG13.  
Cable glands not included.  
range  
On span: 0.03%/°C or 0.06%/°C for 6 psid (50 kPa)  
range  
Pressure port connections  
1/8-28 female NPT  
Operating Humidity Range  
10% to 90% RH, non-condensing  
Weight  
1.2 lb (540 g)  
Shock Resistance  
10 G (11 ms)  
Vibration Resistance  
5 G 3 to 50 Hz  
W30 Series  
Specifications  
Electrical  
Supply Voltage  
11 to 32 VDC (See diagram for maximum loop  
resistance)  
Operating  
Region  
0
10  
20  
30  
Output  
Two-wire/4 to 20 mA output  
Power Supply Voltage  
*Loop resistance = wire resistance + receiver resistance  
Protected against reversal of polarity. Output limited  
to approximately 3.85 mA at low end of span and  
approximately 25 mA at upper end of span.  
Power Supply  
11
1
2
3
4
Enclosure  
Ground  
Standard Pressure Ranges for Modus  
W Series  
+
Receiver  
-
Wire  
-
US Units  
0 to 1050 W  
Wire  
+
Differential Pressure  
Range, psid  
Operating Static  
Pressure, psi  
Pressure Code  
31E  
32E  
33E  
34E  
35E  
36E  
37E  
38E  
0 to 6 psi  
Metric Units, Pascal  
0 to 10 psi  
0 to 15 psi  
0 to 30 psi  
0 to 60 psi  
0 to 100 psi  
0 to 150 psi  
0 to 200 psi  
0 to 100 psi  
0 to 300 psi  
Differential Pressure  
Range, kPa  
Operating Static  
Pressure, kPa  
Pressure Code  
31P  
32P  
33P  
34P  
35P  
36P  
37P  
38P  
0 to 50 Pa  
0 to 75 Pa  
0 to 700 kPa*  
0 to 100 Pa  
0 to 200 Pa  
0 to 500 Pa  
0 to 750 Pa  
0 to 1000 Pa  
0 to 1500Pa  
0 to 2000 kPa  
Metric Units, Millimeters of Water  
Differential Pressure  
Range, k mm H2O  
Operating Static  
Pressure, k mm H2O  
Pressure Code  
31M  
0 to 5.0 k mm H20  
0 to 7.5 k mm H20  
0 to 10 k mm H20  
0 to 20 k mm H20  
0 to 50 k mm H20  
0 to 75 k mm H20  
0 to 100 k mm H20  
0 to 150 k mm H20  
32M  
0 to 70 k mm H20  
Ordering Information  
Record selected option in blank indicated at bottom of form.  
W30  
33M  
34M  
35M  
Code  
X
Pressure Range (PPP)  
See Standard Pressure Ranges Tables  
36M  
0 to 200 k mm H20  
Code  
2
Knockout Quantity (KQ)  
Two holes  
37M  
38M  
Code  
Knockout Size (KS)  
R
S
1/2 in (12.7 mm) conduit  
PG 11  
W30 -  
___  
-
___  
-
___  
Typical model number.  
www.amphenol-sensors.com  
© 2014 Amphenol Corporation. All Rights Reserved. Specifications are subject to change without notice.  
Other company names and product names used in this document are the registered trademarks or  
trademarks of their respective owners.  
Amphenol  
Advanced Sensors  
AAS-920-301B-03/2014  

相关型号:

W30-38M-2-R

General Eastern Liquid Differential Pressure Transmitters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
AMPHENOL

W30-38M-2-S

General Eastern Liquid Differential Pressure Transmitters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
AMPHENOL

W30-38P-2-R

General Eastern Liquid Differential Pressure Transmitters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
AMPHENOL

W30-38P-2-S

General Eastern Liquid Differential Pressure Transmitters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
AMPHENOL

W30-48S1.5

DC/DC MODULES

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
INTRONICS

W30-48S1.8

DC/DC MODULES

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
INTRONICS

W30-48S12

DC/DC MODULES

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
INTRONICS

W30-48S15

DC/DC MODULES

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
INTRONICS

W30-48S2.5

DC/DC MODULES

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
INTRONICS

W30-48S3.3

DC/DC MODULES

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
INTRONICS

W30-48S5

DC/DC MODULES

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
INTRONICS

W3000

W3000 PLL Dual-Band Frequency Synthesizer

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
AGERE