13-PDB-015-11-D [APITECH]
Power Line Filters Three Phase;型号: | 13-PDB-015-11-D |
厂家: | API Technologies Corp |
描述: | Power Line Filters Three Phase LTE |
文件: | 总11页 (文件大小:1561K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Three Phase Power Line Filters
Excellent attenuation for high voltage impulse.
Epoxy molded for internal component reliability and
metal case provides effective EMI shielding. Ideal for
digital, industrial and automation equipment.
Low Current/High Performance.............................PF80-PF81
Three-Phase Power Line Filters.............................PF82-PF83
High Performance ...................................................PF84-PF89
Power Line Filters
Three Phase
Low Current/High Performance
62-PMB/63-PMF Series
Features
I
Excellent attenuation for high voltage impulse
I
Effective for both balanced and unbalanced
three-phase loads
Circuit Diagram
I
Metal case provides effective EMI shielding
62-PMB-050-6-12 (5 Amp Delta)
I
Epoxy molded for internal component reliability
L
L
L
L
I
Compact and economical
CX
CX
CX
CY
CY
I
L
L
Excellent filtering characteristics for both normal
and common mode
I
Various current ratings available: 3, 5, 8 and 16 Amps
I
Safety agency approvals pending
CY
I
Operating temperature: -25°C to +85°C
(including temperature rise, see graph on page PF81)
63-PMF-030-8-14 and 63-PMF-080-8-14 (3 and 8 Amp Wye)
Applications
CX
L
CY
I
Digital equipment
L
CY
CX
I
Industrial equipment (UPS, inverters and converters)
L
L
CX
I
CY
Automation equipment
I
Computerized washing machines
CY
63-PMF-160-9-21 (16 Amp Wye)
L
L
L
L
CX
CX
CX CX
CX
CX
CY
CY
Specifications
Rated Voltage
Rated
Leakage Current
(Max.)
Capacitance
Inductance
(L1)
Temperature
Rise (Max.)
Model
(@ 50/60Hz)
Current
CY
CX
62-PMB-050-6-12
63-PMF-030-8-14
63-PMF-080-8-14
63-PMF-160-9-21
250VAC
480VAC
5A
3A
0.6mA
2200pF
0.22uF
115mH
45°C
30°C
40°C
45°C
1.0mH (4X)
0.74mH (4X)
1.2mH (4X)
1.0mA
4700pF (4X)
470uF (3X)
8A
16A
3.0mA
0.015uF (2X)
1.0uF (6X)
Note: Test Voltage 1500VAC one minute, line to ground.
Insulation Resistance: 300 MΩ min. at 500VDC.
Voltage Drop: 1V max. at rated current.
Weight: 8.82 ounces (250 grams) for 63-PMF-030-8-14 and 63-PMF-080-8-14
19.4 ounces (550 grams) for 62-PMB-050-6-12
51.5 ounces (1450 grams) for 63-PMF-160-9-21
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
PF80
Temperature Characteristics
Power Line Filters
Three Phase
Low Current/High Performance
62-PMB/63-PMF Series
62-PMB-050-6-12 (5 Amp)
5 — .157
(M4)
.865 (22)
2.753
(70)
3.539
(90)
3.460
(88)
.865 (22)
.039 (1)
* General .944 (24)
tolerance
.020 (0.5)
1.376
(35)
63-PMF-030-8-14 and 63-PMF-080-8-14 (3 and 8 Amp)
63-PMF-160-9-21 (16 Amp)
4 - .216
(ø5.5) Hole
4.444 (113)
4.050 (103)
.629 .708
Fast-on
(16) (18)
tab #250
Fast on
tab #250
BL
BK
4.286
(109)
.350 (8.9)
Fast on
tab #250
(Ground
tab)
.362
(9.2)
2.045
(52)
.983
(25)
2 - .197
(ø5) Hole
4.404
(112)
.350 (8.9)
BL
BK
.350 (8.9)
3.146
(80.0 0.5)
.547
(13.9)
.547
(13.9)
.208
(5.3)
3.585 (91.2)
1.809
(46)
.708
(18)
* General
tolerance
..059 (1.5)
5.112 (130.0)
5.702 (145 0.5)
6.292 (160)
Dimensions in inches (mm)
1.494 (38)
2.359 (60)
Common Mode
Normal Mode
62-PMB-050-6-12 (5 Amp)
62-PMB-050-6-12 (5 Amp)
63-PMF (3, 8 and 16 Amp)
63-PMF (3, 8 and 16 Amp)
63-PMF-160-9-21
63-PMF-030-8-14
63-PMF-160-9-21
63-PMF-030-8-14
63-PMB-050-8-12
63-PMF-080-8-14
63-PMF-080-8-14
63-PMB-050-8-12
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
PF81
Power Line Filters
Three Phase
13-PWF/PWL/PWB Series
Features
I
Excellent attenuation for high voltage impulse
I
Effective for both balanced and unbalanced
three-phase loads
Circuit Diagram
I
Metal case provides effective EMI shielding
Circuit 1
I
Epoxy molded for internal component reliability
A
A'
B'
I
Suitable for both Wye and Delta connection
I
Excellent filtering characteristics for both normal
and common mode
B
C
I
Operating temperature: -40°C to +85°C
I
Designed for 3-phase 4-line power supply systems
C'
N'
Applications
I
Digital equipment
I
Industrial equipment (UPS, inverters and converters)
N
G
I
Automation equipment
I
Computerized washing machines
Circuit 2
A
A'
B'
B
C
C'
N'
N
G
Specifications
Rated Voltage
Rated
Leakage
Circuit
Temperature Rise
(Max.)
Model
Figure
(@ 50/60Hz)
Current
Current (Max.)
Diagram
13-PWF-005-12-H
13-PWL-005-12-C
13-PWF-010-12-H
13-PWL-010-12-C
13-PWB-010-12-D
13-PWB-015-12-D
13-PWB-020-12-D
13-PWB-025-12-D
13-PWB-030-12-D
A
B
A
B
5A
1
10A
1.5mA
440/250VAC
30°C
15A
20A
25A
30A
2
C
Note: Test Voltage 1500VAC one minute, line to ground.
Insulation Resistance: 300 MΩ min. at 500VDC.
Voltage Drop: 1V max. at rated current.
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
PF82
Figure B
Power Line Filters
Three Phase
13-PWF/PWL/PWB Series
Figure A
Figure C
2.0 (51)
3.9 (98.5)
5.3 (135)
Dimensions in inches (mm)
Common Mode
Normal Mode
1
2
3
4
1
3
4
Filter
Filter
2
50Ω
Level
Meter
50Ω
Level
Meter
Oscillator
50Ω
Oscillator
50Ω
50Ω
50Ω
50Ω
13-PWF-005;-010;-PWL-005;-010;-PWB-010
13-PWF-005;-010;-PWL-005;-010;-PWB-010
80
70
80
70
13-PWB-010-12-D
13-PWF-005-12-H
13-PWL-005-12-C
60
50
40
30
20
60
50
40
30
20
13-PWF-010-12-H
13-PWL-010-12-C
13-PWF-005-12-H
13-PWL-005-12-C
13-PWB-010-12-D
13-PWF-010-12-H
13-PWL-010-12-C
10
0
10
0
0.1
0.2
0.5
1
2
5
10
20
50
0.1
0.2
1
2
10
20
0.5
5
50
Frequency (MHz)
Frequency (MHz)
13-PWB-015;-020;-025:-030
13-PWB-015;-020;-025:-030
80
70
80
70
13-PWB-015-12-D
13-PWB-020-12-D
13-PWB-025-12-D
13-PWB-015-12-D
60
50
40
30
20
60
50
40
30
20
13-PWB-020-12-D
13-PWB-025-12-D
13-PWB-030-12-D
13-PWB-030-12-D
10
0
10
0
0.1
0.2
1
2
10
20
0.1
0.2
1
2
10
20
0.5
5
50
0.5
5
50
Frequency (MHz)
Frequency (MHz)
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
PF83
Power Line Filters
Three Phase
High Performance
13-PDF/PDL/PDB Series
Features
I
Excellent attenuation for high voltage impulse
I
Effective for both balanced and unbalanced
three-phase loads
Circuit Diagram
I
Metal case provides effective EMI shielding
Circuit 1
I
Epoxy molded for internal component reliability
A
A'
B'
C'
I
Compact and economical
I
Excellent filtering characteristics for both normal
and common mode
B
I
Operating temperature: -40°C to +85°C
I
Designed for 3-phase, 3-Delta connection system
C
G
Applications
I
Digital equipment
I
Industrial equipment (UPS, inverters and converters)
I
Automation equipment
I
Switching power supplies
Circuit 2
A
A'
B'
C'
B
C
G
Specifications
Rated Voltage
Rated
Leakage
Circuit
Temperature Rise
(Max.)
Model
Figure
(@ 50/60Hz)
Current
Current (Max.)
Diagram
13-PDF-005-11-J
13-PDL-005-11-D
13-PDF-010-11-J
13-PDL-010-11-D
13-PDB-010-11-D
13-PDB-015-11-D
13-PDB-020-11-D
13-PDB-025-11-D
13-PDB-030-11-D
A
B
A
B
5A
1
10A
1.5mA
440/250VAC
30°C
15A
20A
25A
30A
2
C
Note: Test Voltage 1500VAC one minute, line to ground.
Insulation Resistance: 300 MΩ min. at 500VDC.
Voltage Drop: 1V max. at rated current.
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
PF84
Figure B
Ø .177 (4.5) (2X)
Power Line Filters
2.00
(51)
Three Phase
High Performance
2.52 (64)
2.95 (75)
13-PDF/PDL/PDB Series
1.06
(27)
3.35 (85)
Figure A
Figure C
6.5 0.2 (4X)
Ø .177 (4.5) (2X)
4.5 0.2 (4X)
M4 THREAD (8X)
95.3 0.5
105.0 2.0
2.52 2.91 3.35
(64) (74) (85)
50.0 1.0
84.0 2.0
12.5 1.0
1.42
(36)
2.00
(51)
11.5 1.0
26.5 1.0
50.8 0.5
98.5 2.0
134.5 3.0
38.5 2.0
3.15 (80)
Dimensions in inches (mm)
Common Mode
Normal Mode
1
3
4
1
3
4
Filter
Filter
2
2
50Ω
50Ω
Level
Level
Meter
Oscillator
50Ω
Oscillator
50Ω
50Ω
50Ω
50Ω
Meter
13-PDF-005;-010; PDL-005;-010 PDB-010
13-PDF-005;-010; PDL-005;-010 PDB-010
80
70
80
70
13-PDF-005-11-J
13-PDL-005-11-D
13-PDB-010-11-D
60
50
40
30
20
60
50
40
30
20
13-PDF-010-11-J
13-PDL-010-11-D
13-PDB-010-11-D
13-PDF-010-11-J
13-PDL-010-11-D
13-PDF-005-11-J
13-PDL-005-11-D
10
0
10
0
0.1
0.2
1
2
10
20
0.5
5
50
0.1
0.2
1
2
10
20
0.5
5
50
Frequency (MHz)
Frequency (MHz)
13-PDB-015;-020;-025:-030
13-PDB-015;-020;-025:-030
80
70
80
70
13-PDB-015-11-D
13-PDB-030-11-D
13-PDB-020-11-D
13-PDB-025-11-D
60
50
40
30
20
60
50
40
30
20
13-PDB-015-11-D
13-PDB-020-11-D
13-PDB-025-11-D
13-PDB-030-11-D
10
0
10
0
0.1
0.2
1
2
10
20
0.1
0.2
1
2
10
20
0.5
5
50
0.5
5
50
Frequency (MHz)
Frequency (MHz)
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
PF85
Power Line Filters
Three Phase
High Performance
13-PWB Series
Features
I
Excellent attenuation for high voltage impulse
I
Metal case provides effective EMI shielding
I
Circuit Diagram
Epoxy molded for internal component reliability
I
Excellent filtering characteristics for both normal
and common mode
Circuit 1
I
Various current ratings available: from 5 to 150 Amps
A
B
C
A'
B'
I
Operating temperature: -40°C to +85°C
I
Designed for 3-phase, 4-line power systems
Applications
C'
N'
I
Power supplies for data systems
N
G
I
Industrial equipment (UPS, inverters and converters)
I
Automation equipment
I
Telecommunications systems and equipment
Circuit 2
A
A'
B'
B
C
C'
N'
N
G
Specifications
Rated Voltage
Rated
Leakage
Circuit
Temperature Rise
(Max.)
Model
(@ 50/60Hz)
Current
Current (Max.)
Diagram
13-PWB-005-12-A
13-PWB-010-12-B
13-PWB-020-12-B
13-PWB-035-12-C
13-PWB-050-13-C
13-PWB-080-14-D
13-PWB-100-14-D
13-PWB-150-14-E
5A
10A
20A
35A
50A
80A
100A
150A
1
2
4.5mA
480/277VAC
30°C
9.0mA
20mA
Note: Test Voltage 1500VAC one minute, line to ground.
Insulation Resistance: 300 MΩ min. at 500VDC.
Voltage Drop: 1V max. at rated current.
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
PF86
I
L
H
P
Power Line Filters
Three Phase
E
High Performance
M
D
F
13-PWB Series
B
A
C
K
G
N
J
Dimensions in inches (mm)
Dimensions
Model
A
B
C
D
E
F
G
H
I
J
K
M
N
P
L
13-PWB-005-12-A 7.2 (184) 6.3 (160) 7.9 (202)
3.5 (86) .70 (18) 2.3 (58)
1.5 (38)
.25 x .37 (6.4 x 9.4)
.25 x .37 (6.4 x 9.5)
.25 x .38 (6.4 x 9.6)
.25 x .38 (6.4 x 9.7)
.25 x .38 (6.4 x 9.8)
.25 x .39 (6.4 x 9.9)
.25 x .36 (6.4 x 9.10)
.25 x .36 (6.4 x 9.11)
2.4
(60)
1.7
(44)
–
–
–
M4
13-PWB-010-12-B
3.9
M4
1.8
(45)
(100)
13-PWB-020-12-B
13-PWB-035-12-C
13-PWB-050-13-C
13-PWB-080-14-D
13-PWB-100-14-D
13-PWB-150-14-E
9.6
(243)
8.7
(220)
10.3
(261)
.98
(25)
3.5
4.9
2.9
(74)
1.9
(49)
3.1
(81)
3.8
(96)
2.3
(58)
M6
M8
M6
M8
(90)
(125)
2.2
(56)
6.1
(155)
7.3
1.2
M4
3.9
(99)
13.9
(354)
12.6
(320)
15.1
(384)
(185)
3.4
(86)
(30)
2.4
(62)
1.4 (35)
3.9 (100)
2.4 (61)
7.5 (190) 8.7 (220)
Common Mode
Normal Mode
1
3
4
1
3
Filter
Filter
2
2
4
50Ω
Level
Meter
50Ω
Level
Meter
Oscillator
50Ω
Oscillator
50Ω
50Ω
50Ω
50Ω
13-PWB-005;-010;-020;-035
13-PWB-005;-010;-020;-035
120
105
120
13-PWB-010-12-A
13-PWB-005-12-A
105
90
75
60
45
30
13-PWB-010-12-A
13-PWB-020-12-A
90
75
60
45
30
13-PWB-020-12-A
13-PWB-035-12-A
13-PWB-035-12-A
13-PWB-005-12-A
15
0
15
0
0.1
0.2
1
2
10
20
0.5
5
50
0.1
0.2
1
2
10
20
0.5
5
50
Frequency (MHz)
Frequency (MHz)
13-PWB-050;-080;-100;-150
13-PWB-050;-080;-100;-150
120
105
120
105
13-PWB-080-14-D
13-PWB-080-14-D
13-PWB-100-14-D
13-PWB-100-14-D
90
75
60
45
30
90
75
60
45
30
13-PWB-050-13-C
13-PWB-150-14-E
13-PWB-050-13-C
13-PWB-150-14-E
15
0
15
0
0.1
0.2
0.5
1
2
5
10
20
50
0.1
0.2
1
2
10
20
0.5
5
50
Frequency (MHz)
Frequency (MHz)
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
PF87
Power Line Filters
Three Phase
High Performance
13-PDB Series
Features
I
Excellent attenuation for high voltage impulse
I
Metal case provides effective EMI shielding
I
Circuit Diagram
Epoxy molded for internal component reliability
I
Excellent filtering characteristics for both normal
and common mode
Circuit 1
I
Various current ratings available: from 5 to 200 Amps
A
B
C
A'
B'
C'
I
Operating temperature: -40°C to +85°C
I
Designed for 3-phase, 3-line connection systems
Applications
I
Digital equipment
G
I
Industrial equipment (UPS, inverters and converters)
Circuit 2
A
A'
B'
C'
B
C
G
Specifications
Rated Voltage
Rated
Leakage
Circuit
Temperature Rise
(Max.)
Model
(@ 50/60Hz)
Current
Current (Max.)
Diagram
13-PDB-005-12-A
13-PDB-010-12-A
13-PDB-020-12-B
13-PDB-035-12-B
13-PDB-050-12-B
13-PDB-080-13-C
13-PDB-100-14-C
13-PDB-150-14-C
13-PDB-200-14-D
5A
10A
4.5mA
20A
35A
1
2
480/277VAC
50A
30°C
9.0mA
20mA
80A
100A
150A
200A
Note: Test Voltage 2250VDC one minute, line to ground.
Insulation Resistance: 500MΩ.
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
PF88
I
L
P
H
Power Line Filters
Three Phase
F
E
D
M
High Performance
13-PDB Series
B
A
C
G
N
K
J
Dimensions
Dimensions in inches (mm)
Model
A
B
C
D
E
F
G
H
I
J
K
M
N
P
L
13-PDB-005-12-A
13-PDB-010-12-A
13-PDB-020-12-B
13-PDB-035-12-B
13-PDB-050-12-B
13-PDB-080-13-C
13-PDB-100-14-C
13-PDB-150-14-C
13-PDB-200-14-D
7.2
(184)
6.3
(160)
7.9
(202)
1.6
(42)
2.4
(60)
3.3
(86)
.70
(18)
2.3
(58)
1.5
(38)
.25 x .37 (6.4 x 9.4)
.25 x .37 (6.4 x 9.5)
.25 x .38 (6.4 x 9.6)
.25 x .38 (6.4 x 9.7)
.25 x .38 (6.4 x 9.8)
.25 x .39 (6.4 x 9.9)
.25 x .36 (6.4 x 9.10)
.25 x .36 (6.4 x 9.11)
.25 x .36 (6.4 x 9.12)
M4
–
–
–
M4
1.9
(49)
2.7
(70)
3.9
(100)
.98
(25)
2.9
(74)
9.6
(243)
8.7
(220)
10.3
(261)
2.3
(58)
2.3
(58)
M6
M8
M6
M8
3.5
(90)
M4
2.2
(56)
6.1
(155)
7.3
(185)
1.2
(30)
3.3
(86)
13.9
(354)
12.6
(320)
15.1
(384)
2.5
(66)
2.4
(62)
2.4 (61)
3.9 (100)
7.5 (190) 8.6 (220) 1.4 (35)
Common Mode
Normal Mode
1
3
4
1
3
Filter
Filter
2
2
4
50Ω
Level
Meter
50Ω
Level
Meter
Oscillator
50Ω
Oscillator
50Ω
50Ω
50Ω
50Ω
13-PDB-005;-010;-020;-035
13-PDB-005;-010;-020;-035
120
120
105
13-PDB-010-12-A
105
90
75
60
45
30
15
13-PDB-020-12-B
13-PDB-005-12-A
90
75
60
45
30
13-PDB-035-12-B
13-PDB-035-12-B
13-PDB-020-12-B
13-PDB-005-12-A
13-PDB-010-12-A
15
0
0
0
0.01
.1
1
20
30
0
0.01
.1
1
20
30
0.02
10
60
0.02
10
60
Frequency (MHz)
Frequency (MHz)
13-PDB-050;-080;-100;-150;-200
13-PDB-050;-080;-100;-150;-200
120
105
120
105
13-PDB-100-14-C
13-PDB-100-14-C
13-PDB-080-13-C
13-PDB-050-12-B
13-PDB-200-14-D
13-PDB-050-12-B
90
75
60
45
30
90
75
60
45
30
13-PDB-080-13-C
13-PDB-150-14-C
13-PDB-150-14-C
13-PDB-200-14-D
15
0
15
0
0
0.01
.1
1
20
30
0
0.01
.1
1
20
30
0.02
10
60
0.02
10
60
Frequency (MHz)
Frequency (MHz)
API TECHNOLOGIES • 8061 Avonia Rd. • Fairview, PA 16415 • Ph: 814-474-1571 • Fax: 814-474-3110 • eis.apitech.com
API TECHNOLOGIES’ SPECTRUM CONTROL GmbH • Hansastrasse 6 • 91126 Schwabach, Germany • Phone: (49)-9122-795-0 • Fax: (49)-9122-795-58
PF89
相关型号:
©2020 ICPDF网 联系我们和版权申明