8715-01 [ASM-SENSOR]
POWER HiCORDER; 电源记录仪型号: | 8715-01 |
厂家: | ASM GMBH |
描述: | POWER HiCORDER |
文件: | 总4页 (文件大小:926K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Do you ever worry about power failure?
POWER HiCORDER 8714-01,8715-01
Recorders
Introducing easy-to-use power monitoring recorders!
See what you’ve been missing !
★ Capture Spikes, Sags, and Surges
★ Monitor and record power anomalies and fluctuations
easily, even unattended
★ Analyze Leakage Currents as well as AC/DC Current up
to 2000 amps
★ True-RMS with Trigger Function
★ 250µsec Transient Waveform Capture
2
Record power anomalies accurately with simple operation !
- Aplications -
What a Power Recorder Does
There are many power-quality concerns in today's
PC-based businesses, and detecting power anomalies
is important for maintaining factory facilities and
equipment. The POWER HiCORDERs 8714-01 and
8715-01 are monitoring recorders that can capture
instantaneous power drop-outs, brown-outs, spikes and
sags, and record voltage changes with simple operation,
and even monitor and record while totally unattended.
The compact B5 size and 1.5kg (52.9oz.) weight provide
excellent portability among worksites. (8714-01
)
Simple Setup
1. Simple setup. No worries about operability.
2. Accepts direct input of line voltages up to 400 V, and
up to 1000 V AC/ 2000 V DC with the use of the
DIFFERENTIAL PROBE 9322 accessory.
3. Voltage and current can be simultaneously measured on
four isolated channels.
6. High-speed A/D converter stores data in memory,
providing simple recording of events that cannot be
recorded by a pen recorder.
7. Two measurement functions are
available: Waveform Measurement
Mode (memory mode), and RMS
Trend Measurement Mode (RMS
recorder & memory).
4. Data immediately before an anomaly occurs can be stored
and recorded.
5. High quality data printouts on site.
8. HIOKI clamp-on probes (voltage-
output type) can be directly
connected.
Example
To monitor the current waveform on a 220 V
power line.
[ Setup ]
Measurement mode is set to Waveform, time axis to
2ms. Recording length is set to 20 division.
[ Channel setup ]
For current waveforms, after selecting a clamp-on
probe for the input type from Mode, select the range
of the clamp. Here, we select 9010 and 100A. Set
the range of the clamp-on probe in the same way.
[ Starting Measurement ]
Clamp the probe around the conductor to be
measured.
Press the START button.
The current waveform is
displayed on the screen.
To stop measuring, press
he STOP button.
Current Waveform Example
ꢀ
Two models: the two-channel (8714-01) and four-channel (8715-01)
- Specifications -
Basic Specifications
8714-01
8715-01
Waveform Measurement (Power Waveform Observation) Mode
Waveform Measurement mode (Power Waveform Observation),
RMS Trend Measurement mode (RMS Observation)
200 and 400µs, 1, 2, 5, 10, and 20ms/division, time axis zoom
×2 to ×10; 3 settings, compression 1/2 to 1/50; 5 settings
Measurement Mode
Time axis
1/80 of time axis ranges (minimum sampling period 2.5µs)
Sampling period
Recording length
Input types and
Input channels fixed, Analog 2 channels Input channels fixed, Analog 4 channels
Inter-channels and input-frame isolation
Inter-channels and input-frame isolation
number of channels
20, 50, 100, 200, or 400 division (800 division at sequential save OFF)
400k sample/s (2.5μs period)
Simultaneous sampling for 2 or 4 analog channels
Can record data from before the trigger point, 0/10/20/50, or 100%
of recording length
Maximum sampling rate
Memory capacity
Pre-trigger
continuous 2-channels measurement
(12-bit analog) × 64 kilo-words/ ch
continuous 4-channels measurement
(12-bit analog) × 64 kilo-words/ ch
Voltage axis normal (×1/2), magnified (×1), Left-right waveform scrolling,
Automatic, manual and partial (between A-B cursors) printing
Other functions
PC Card TYPE II slot × 1 : Flash ATA card (max.1 GB), MS-DOS
format. Memory contents : Settings data, Measurement data
(binary or text format), Screen data (BMP)
RMS Trend Measurement (RMS Fluctuation Measurement) Mode
External memory
Commercial mains power (50/60Hz)
Measurement objective
Clock, waveform data and settings, Battery life approx. 5 years (at
25°C/ 77°F).
1/2/5 seconds/DIV (cannot realtime print); 10/30 seconds; 1/2/5/10/30
minutes; or 1hour/DIV, time axis compression 1/2 to 1/50; 5 settings
Backup function
External control
Time axis
Terminal block : trigger input/output
250µs fixed (RMS value 800 data/second)
Continuous measurement only (up to 200 division of data are stored internally)
±3 % f.s.
Sampling period
Recording length
RMS accuracy
Operation: +5°C/41°F to +40°C/104°F, 35% to 80% relative humidity.
Storage: -10°C/14°F to +50°C/122°F, 35% to 80% relative humidity.
Environment conditions
(no condensation)
Safety: EN61010
EMC: EN61326, EN61000-3-2, EN61000-3-3
Applicable standards
Power supplies
100V Line: 75 to 125V rms (standard)
200V Line: 150 to 250V rms (standard)
400V Line: 275 to 525V rms (standard)
Clamp: 0A rms to f.s.value on clamp-on probe (rms)
9322 Differential probe: 400V Line; 275 to 525V rms (standard)
9322 Differential probe: 600V Line; 475 to 725V rms (standard)
(1) AC Adapter model 9418-15 or 9418-10 (DC 12V ±10%)
(2) BATTERY PACK 9447 (AC adapter has priority when used in
combination with battery pack, fast recharge possible with AC adapter)
Waveform display
area
15VA max.
Power consumption
Continuous operation time
Charge time
Voltage axis normal (×1/2), magnified (×5), Left-right waveform scroll,
Automatic, manual and partial (between A-B cursors) printing, Hybrid
recording: prints logging data for each division together with waveform
Approx. 3 hours (with BATTERY PACK 9447, trigger standby at 23°C/ 73°F)
Approx. 2 hours fast charge with power switch OFF (at 23°C/ 73°F)
approx. 280 (11.02) W × 170 (6.69) H × 52 (2.05) approx. 280 (11.02) W × 170 (6.69) H × 52 (2.05)
Other functions
Dimensions and
mass
RMS Trend Measurement (Instantaneous Waveform Measurement) Mode
Dmm (inch), 1.5kg/ 52.91oz (without batteries)
Dmm (inch) , 1.6kg/ 56.44oz (without batteries)
200 and 400µs, 1, 2, 5, 10, and 20ms/division, time axis zoom
×2 to ×10; 3 settings, compression 1/2 to 1/50; 5 settings
Instruction manual ×1, Measurement guide ×1, Recording paper ×
1, Paper attachment ×2, Blank box ×1, Strap ×1, AC ADAPTER
9418-15 ×1, CONNECTION CORD 9197 ×2 (8714-01), ×4 (8715-01),
Application disk ×1
Time axis
Supplied
accessories
1/80 of time axis ranges (minimum sampling period 2.5µs)
Sampling period
Recording length
20, 50, 100, or 200 division (400 division at sequential save OFF)
Can record data from before the trigger point, 0/10/20/50, or 100%
of recording length
Pre-trigger
Voltage axis normal (×1/2), magnified (×1), Left-right waveform scroll
Other functions
Other Functions
Printing of settings including input range, trigger time, etc., cursor
measurement, start condition retention, auto setup, list & gauge
printing, power-save function, DMM function (voltage shown as numerals
on the display), auto saving, partial saving (between A-B cursors or all data),
sequential save.
General
280 mm
(11.02 in)
Display update rate: 1 second
Display contents: RMS value (only measuring DC and 50/60Hz)
Display digit: 4 (last digit 0 to 4 is rounded zero, 5 to 9 is rounded five)
Voltage ranges: Auto-select only (five ranges from 10 mV to 100 V/ div.)
Accuracy: ±3% rdg. ±5dgt.
Mass (8714-01) : approx. 1.5kg/52.91oz
Mass (8715-01) : approx. 1.6kg/56.44oz
DMM Function
Recording and Display Section
5.7-inch STN color LCD, with English/Japanese language selector
240 × 320 dots
Display
112mm (4.41in) × 18m (59.06ft), thermal paper roll
100mm in full scale (10 divisions), 1 division = 10mm (0.39in)
Max. 1sec/division (with AC adapter use)
Recording paper
Recording area
Recording speed
Input section (accuracy at 23 ±5 ˚C/73 ±9 ˚F after 30 minutes warm-up time; accuracy guaranteed for 1 year)
Isolated BNC terminal, Input item: Voltage, 9010, 9018, 9132,
3283, 3284, 3285, 9322 (selectable)
Input
Trigger Function(only for anomalous waveform measurement and instantaneous power fluctuation recording)
Analog input CH1 - CH4 (8714-01: CH1 - CH2), external (either ON or
Trigger source
Voltage : 100, 200, 400V line, or 100V DC
9010 : 10, 20, 50, 100, 200, or 500A
9018 : 10, 20, 50, 100, 200, or 500A
OFF for each source), logical AND/OR of sources
Level trigger: At preset voltage level, on either rising or falling
edge
Window trigger: At entry or exit from preset upper and lower limits
Voltage drop trigger: Especially for 50/60Hz commercial power,
when peak voltage falls below preset value
Period trigger: When period of rising or falling edge of measured
signal exceeds preset period
9132 : 20, 50, 100, 200, 500, or 1000A
3283 : 10mA, 100mA, 1, 10, or 200A
Measurement range
3284 : 20 or 200A
3285 : 200 or 2000A
9322 : 400 or 600V line
Anomalous
waveform triggers
Waveform judgment trigger: Especially for 50/60Hz commercial
power, to monitor signals outside of judgment range in real time
(when time axis range 20ms/division is not applicable)
400kS/s (simultaneous sampling of all channels)
Max. sampling rate
Accuracy, frequency
characteristics
±0.5% f.s. (applied accuracy of clamp-on probe), DC to 50kHz ±3dB
Voltage drop trigger: Especially for 50/60Hz commercial power,
when peak voltage falls below preset value
RMS level trigger: At preset effective value, on either rising or
falling edge
OFF, 500Hz, 5kHz
Low-pass filter
Power fluctuation
Input resistance and
capacitance
measurement triggers
1MΩ, 7pF approx. (at 100kHz)
(valid only when instantaneous
waveform measurement is enabled) RMS window trigger: At entry or exit from preset upper and lower
limit levels
DC (fixed)
Input coupling
0, 10, 20, 50, 100% (for anomalous waveform measurement, instantaneous
power fluctuation recording)
450V AC rms, DC CAT II (upper voltage which when applied to between
input pins does not damage them)
Pre-Trigger
Max. allowable input
0.25% f.s. (f.s.=10 divisions, 0.1% f.s. for use with waveform judgment trigger)
Level setting resolution
Max. rated voltage
to earth
450V AC rms, DC (upper voltage which when applied to input channel
casing or between input channels does not damage them)
Off/On (0.5 divisions fixed filter width)
Trigger filter
4
Composition of options
ꢀ
Note:ꢀProductꢀnamesꢀappearingꢀhereinꢀareꢀtrademarksꢀorꢀregisteredꢀtrademarksꢀofꢀvariousꢀcompanies.ꢀ
Record Current Waveform
Record Current Waveform
CLAMP ON AC/DC HiTESTER
3285
200A or 2000AAC/DC, with
analog output of 1V f.s. DC, and
waveform monitor output of 1V
f.s. AC at 10Hz to 1kHz, or DC.
Requires the AC ADAPTER
9445-02/-03
CARRYING CASE 9391
Soft case type, for storing options
Holds more options than the 9648
hard case
CLAMP ON PROBE 9018-10
Input from 10 to 500A
40Hz to 3kHz for 0.2V AC output.
BNC terminal
CARRYING CASE 9648
Hard case type, for storing
options
Supplied with PC
Card adapter
CLAMP ON AC/DC HiTESTER
3284
PC CARD 128M 9726
(128MB capacity)
20A or 200AAC/DC, with
analog output of 1V f.s. DC, and
waveform monitor output of 1V
f.s. AC at 10Hz to 2kHz, or DC.
Requires the AC ADAPTER
9445-02/-03
PC CARD 256M 9727
Not CE certified
(256MB capacity)
PC Card Precaution
CLAMP ON PROBE 9132-10
Input from 20 to 1000A
40Hz to 1kHz for 0.2V AC output.
BNC terminal
PC CARD 512M 9728
Useꢀ onlyꢀ PCꢀ Cardsꢀ soldꢀ
byꢀ HIOKI.ꢀ Compatibilityꢀ
andꢀ performanceꢀ areꢀ notꢀ
guaranteedꢀforꢀPCꢀcardsꢀmadeꢀ
byꢀotherꢀmanufacturers.ꢀYouꢀ
mayꢀbeꢀunableꢀtoꢀreadꢀfromꢀorꢀ
saveꢀdataꢀtoꢀsuchꢀcards.
WAVE PROCESSOR 9335
Data conversion, print functions,
waveform display, compatible with
Windows 95/98/Me, Windows NT
4.0/2000/XP
(512MB capacity)
PC CARD 1G 9729
(1GB capacity)
CLAMP ON LEAK HiTESTER
3283
For leakage current measurement,
includes 10mA to 200A ranges,
with analog output of 1V f.s. DC,
and waveform monitor output
of 1V f.s. AC at 40Hz to 2kHz.
Requires the AC ADAPTER
9445-02/-03
Input from power-concent
1kV AC, 2kV DC input
AC ADAPTER 9445-02/-03
Use for the 3283, 3284,
3285, for USA/CSA
DIFFERENTIAL PROBE 9322
For inputs up to 2kV DC or
1kV AC, the 9322 requires
the AC ADAPTER 9418-15
CONCENT INPUT CORD
9448
9445-02, for EU 9445-03
Use for 100V commercial
line, 2m length
+
Not CE certified
CONVERSION ADAPTER
9199
OUTPUT CORD 9094
Required along with the
9199 adapter to connect
the 3283/3284/3285 to the
8714-01 or 8715-01
AC ADAPTER 9418-15
Use for the 9322, 100 to 240
V AC
POWER HiCORDER 8714-01 (2ch model)
POWER HiCORDER 8715-01 (4ch model)
Banana-to-BNC, use to
connect to insulation-BNC
terminal on Input section
Included accessories: AC ADAPTER 9418-15 ×1, Recording paper ×1, Blank box ×1, Strap ×1,
CONNECTION CORD 9197 (8714-01: ×2, 8715-01: ×4), Application disk ×1
Up to 450V AC input
+
CONVERSION ADAPTER
9199
Not CE certified
CONNECTION CORD 9197
For up to 500V,
1.5 m length
Banana-to-BNC, use to
connect to insulation-BNC
terminal on Input section
Not CE certified
LINE SPLITTER CT101A
For 100V/ 15A,
convenient for measuring
CONNECTION CORD
9217
RECORDING PAPER
9234
PAPER WINDER 220H
Insulation BNC-to-insulation
Input cords of included accessories are the 9197 only. For current
measurement, please purchase the optional clamp-on probe, or clamp-on
tester.
Paper width: 70 to 220 mm, 100V AC line current with
BNC, use to connect to
insulation-BNC terminal on
Input Module
18 m/ 59.06 feet length,
10 rolls/ 1 set
using special-purpose AC
adapter
clamp-on probe
CHARGE STAND 9643
AC ADAPTER 9418-15
BATTERY PACK 9447
Independent of main unit the
8714-01/8715-01, use with the AC
ADAPTER 9418-15 to charge one
Model BATTERY PACK 9447.
Universal 100 to 240 V AC,
12 V DC/ 2.5 A output
7.2V, 2400mAh
n Combination example: 2-channels, with current measurement
Main unit
Paper
Battery pack
9447×1
Current up to 500A
9018-10×2
Carrying case
9ꢀ91×1
Model number
quantity
×
8714-01×1
92ꢀ4×1 (10 rolls)
n Combination example: 4-channels, with current measurement
Main unit
Paper
Battery pack
9447×1
Current up to 500A
9018-10×4
Carrying case
9ꢀ91×1
Model number
quantity
×
8715-01×1
92ꢀ4×1 (10 rolls)
DISTRIBUTED BY
HEAD OFFICE :
Shanghai Representative Office :
81 Koizumi, Ueda, Nagano, ꢀ86-1192, Japan
1ꢀ10 Shanghai Times Square Office
TEL +81-268-28-0562 / FAX +81-268-28-0568 9ꢀ Huaihai Zhong Road
E-mail: os-com@hioki.co.jp
Shanghai, 200021, P.R.China
TEL +86-21-6ꢀ91-0090, 0092
FAX +86-21-6ꢀ91-0ꢀ60
E-mail: info@hioki.cn
HIOKI USA CORPORATION :
6 Corporate Drive, Cranbury, NJ 08512 USA
TEL +1-609-409-9109 / FAX +1-609-409-9108
E-mail: hioki@hiokiusa.com
All information correct as of Jan. 25, 2007. All specifications are subject to change without notice.
8714E4-71E-00P Printed in Japan