01DTS-505X [BELIMO]
Low Temperature Detection Sensor;型号: | 01DTS-505X |
厂家: | BELIMO |
描述: | Low Temperature Detection Sensor |
文件: | 总3页 (文件大小:413K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Technical data sheet
01DTS-5..
Low Temperature Detection Sensor
For monitoring the temperatures of water/air
heaters in ventilation and air conditioning
systems to prevent frost damage to the
cooling registers. Manual or automatic reset
versions and adjustable setpoints. The frost
alarm is provided with a 1-pole changeover
switch.
Type Overview
Output signal
Additional
features
Type
temperature
switch
Probe length
01DTS-504
01DTS-504X
01DTS-505
01DTS-505X
changeover
changeover
changeover
changeover
Auto reset
Manual reset
Auto reset
10 ft [3 m]
10 ft [3 m]
20 ft [6 m]
20 ft [6 m]
Manual reset
Technical Data
Electrical Data Cable entry
Cable gland cap nut with strain relief Ø6...8
mm
Functional Data
Measuring Data
Output signal switch note
1x SPDT (4A @ AC/DC 24V)
air
Application
Measuring values
temperature
Measuring range temperature
15...60°F [-10...15°C]
Accuracy temperature active
Cable gland
±0.9°F [±0.5°C]
PA6, gray
Materials
Housing
Base: ABS, gray
seal: 0467 NBR70, black
cover ABS, transparent
Probe material
Copper/vapor filled R507
max. 95% r.H., non-condensing
-30...160°F [-35...70°C]
-30...120°F [-35...50°C]
III protective extra-low voltage (pelv)
CE Marking
Safety Data
Ambient humidity
Ambient temperature
Fluid temperature
Protection class IEC/EN
EU Conformity
Certification IEC/EN
Degree of protection IEC/EN
Degree of protection NEMA/UL
Quality Standard
IEC/EN 60730-1
IP65
NEMA 4
ISO 9001
www.belimo.com
01DTS-5.. • en-us • 2019-08-20 • Subject to change
1 / 3
Technical data sheet
01DTS-5..
Safety Notes
This device has been designed for use in stationary heating, ventilation and air-conditioning
systems and must not be used outside the specified field of application. Unauthorised
modifications are prohibited. The product must not be used in relation with any equipment
that in case of a failure may threaten humans, animals or assets.
Ensure all power is disconnected before installing. Do not connect to live/operating
equipment.
Only authorised specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied during installation.
The device contains electrical and electronic components and must not be disposed of as
household refuse. All locally valid regulations and requirements must be observed.
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualified licensed electrician or
other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
Scope of delivery
Wiring Diagram
Scope of delivery Description
Type
Mounting kit, with mounting brackets
A-22D-A08
set point range (factory setting 41°F [5°C])
If the capillary leaks, the switch changes to the frost position.
www.belimo.com
01DTS-5.. • en-us • 2019-08-20 • Subject to change
2 / 3
Technical data sheet
01DTS-5..
Dimensions
Dimensions
.
Type
Probe length
10 ft [3 m]
10 ft [3 m]
20 ft [6 m]
20 ft [6 m]
Weight
01DTS-504
01DTS-504X
01DTS-505
01DTS-505X
0.89 lb [0.41 kg]
0.89 lb [0.41 kg]
1.01 lb [0.46 kg]
1.01 lb [0.46 kg]
www.belimo.com
01DTS-5.. • en-us • 2019-08-20 • Subject to change
3 / 3