01RT-5L-0 [BELIMO]
Room Sensor Temperature;型号: | 01RT-5L-0 |
厂家: | BELIMO |
描述: | Room Sensor Temperature |
文件: | 总3页 (文件大小:469K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Technical data sheet
01RT-5..
Room Sensor Temperature
Passive wall mount temperature sensors
with an incorporated manual override button
and sleek design. Available with four
different outputs to be seamlessly
connected to existing third-party controllers.
Type Overview
Type
Output signal
Pt1000
01RT-5B-0
01RT-5L-0
01RT-5M-0
01RT-5Q-0
NTC10k (10k2)
NTC10k3 (Precon)
NTC20k
Technical Data
Electrical Data Electrical connection
Cable entry
Spring loaded terminal block 0.5...1.5 mm²
Wire openings at the backside (for In-wall
wiring) and top-/bottom side (for On-wall
wiring)
Functional Data
Measuring Data
Output signal passive temperature
Pt1000
NTC10k (10k2)
NTC10k3 (Precon)
NTC20k
Application
air
Measuring values
Temperature
30...120°F [0...50°C]
Measuring range temperature
Accuracy temperature passive
Measuring current
Passive Sensors depending on used type
Pt.. = ±0.5°F @ 32°F [±0.3°C @ 0°C]
NTC.. = ±0.35°F @ 77°F [±0.2°C @ 25°C]
Pt1000: <0.3 mA @ 32°F [0°C]
NTC10k2: <2 mA @ 77°F [25°C]
NTC10k3: <2.7 mA @ 77°F [25°C]
NTC20k: <0.5 mA @ 77°F [25°C]
Time Constant τ (63%) in the room
Wall Coupling Factor
Housing
typical 360 s
35 %
Materials
white, RAL 9003
www.Belimo.US
01RT-5.. • en-us • 2020-07-02 • Subject to change
1 / 3
Technical data sheet
01RT-5..
Safety Data Ambient humidity
max. 95% r.H., non-condensing
30...120°F [0...50°C]
Ambient temperature
Fluid temperature
30...120°F [0...50°C]
Storage temperature
Protection class IEC/EN
EU Conformity
-4...140°F [-20...60°C]
III Protective extra-low voltage (PELV)
CE Marking
Certification IEC/EN
Degree of protection IEC/EN
Degree of protection NEMA/UL
Quality Standard
IEC/EN 60730-1 and IEC/EN 60730-2-9
IP30
NEMA 1
ISO 9001
Safety Notes
This device has been designed for use in stationary heating, ventilation and air-conditioning
systems and must not be used outside the specified field of application. Unauthorised
modifications are prohibited. The product must not be used in relation with any equipment
that in case of a failure may threaten humans, animals or assets.
Ensure all power is disconnected before installing. Do not connect to live/operating
equipment.
Only authorised specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied during installation.
The device contains electrical and electronic components and must not be disposed of as
household refuse. All locally valid regulations and requirements must be observed.
Remarks
General Remarks Concerning Sensors Due to self-heating with 2 wire passive sensors, the supply wire current affects the
measurement accuracy, so it should not exceed 1 mA.
When using lengthy connecting cables (depending on the cross section used), the cable
resistance must be taken into account. The lower the impedance of the sensor used, the
greater the effect of the line resistance on the measurement, because it generates an offset.
Manual override Once the Manual Override button is pressed, the thermistor within the room sensor is
temporarily shorted out and a signal is sent to the controller. The DDC programmer can
utilize the signal to provide an array of HVAC sequence options.
Scope of delivery
Screws
Wiring Diagram
www.Belimo.US
01RT-5.. • en-us • 2020-07-02 • Subject to change
2 / 3
Technical data sheet
01RT-5..
Dimensions
Type
Weight
01RT-5B-0
01RT-5L-0
01RT-5M-0
01RT-5Q-0
0.19 lb [0.09 kg]
0.19 lb [0.09 kg]
0.19 lb [0.09 kg]
0.19 lb [0.09 kg]
www.Belimo.US
01RT-5.. • en-us • 2020-07-02 • Subject to change
3 / 3
相关型号:
01T1002SFA3
RESISTOR, TEMPERATURE DEPENDENT, NTC, 10000 ohm, CHASSIS MOUNT, RADIAL LEADED, LEAD FREE
VISHAY
©2020 ICPDF网 联系我们和版权申明