Technical data sheet
01UT-5..
Outside Temperature Sensor
For measuring temperature in outdoor
areas. Typical applications at cold stores,
greenhouses, production plants and
warehouses. NEMA 4X / IP65 rated
enclosure.
Type Overview
Output signal
Type
passive
temperature
01UT-5A
01UT-5B
01UT-5E
01UT-5L
01UT-5M
01UT-5Q
Pt100
Pt1000
Ni1000 (JCI)
NTC10k2
NTC10k3
NTC20k
Technical Data
Electrical Data Electrical connection
Cable entry
Removable spring loaded terminal block max.
2.5 mm²
Cable gland with strain relief Ø6...8 mm (1/2"
NPT conduit adapter included)
Functional Data
Output signal passive temperature
Pt100
Pt1000
Ni1000 (JCI)
NTC10k2
NTC10k3
NTC20k
Application
air
Measuring Data
Measuring values
temperature
Measuring range temperature
-30...120°F [-35...50°C]
Accuracy temperature passive
passive sensors depending on used type
Pt.. = ±0.5°F @ 32°F [±0.3°C @ 0°C]
Ni.. = ±0.7°F @ 32°F [±0.4°C @ 0°C]
NTC.. = ±0.35°F @ 77°F [±0.2°C @ 25°C]
Materials
Cable gland
Mounting plate
Housing
PA6, black
Lexan, gray RAL7001
cover: lexan, gray
base: lexan, gray
seal: 0467 NBR70, black
UV resistant
www.belimo.com
01UT-5.. • en-us • 2019-08-20 • Subject to change
1 / 3
Technical data sheet
01UT-5..
Safety Data Ambient humidity
max. 95% r.H., non-condensing
-30...120°F [-35...50°C]
-30...120°F [-35...50°C]
max. 195°F [90°C]
Ambient temperature
Fluid temperature
Housing surface temperature
Protection class IEC/EN
Protection class UL
EU Conformity
III safety extra-low voltage (selv)
UL Class 2 Supply
CE Marking
Certification IEC/EN
Certification UL
IEC/EN 60730-1
cULus acc. to UL60730-1A/-2-9, CAN/CSA
E60730-1:02/-2-9
Degree of protection IEC/EN
Degree of protection NEMA/UL
Quality Standard
IP65
NEMA 4X
ISO 9001
Safety Notes
This device has been designed for use in stationary heating, ventilation and air-conditioning
systems and must not be used outside the specified field of application. Unauthorised
modifications are prohibited. The product must not be used in relation with any equipment
that in case of a failure may threaten humans, animals or assets.
Ensure all power is disconnected before installing. Do not connect to live/operating
equipment.
Only authorised specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied during installation.
The device contains electrical and electronic components and must not be disposed of as
household refuse. All locally valid regulations and requirements must be observed.
Remarks
General Remarks Concerning Sensors Due to self-heating with 2 wire passive sensors, the supply wire current affects the
measurement accuracy, so it should not exceed 1 mA.
When using lengthy connecting cables (depending on the cross section used), the cable
resistance must be taken into account. The lower the impedance of the sensor used, the
greater the effect of the line resistance on the measurement, because it generates an offset.
Scope of delivery
Scope of delivery Description
Mounting plate S housing
Type
A-22D-A09
Dowel
Screws
1/2" NPT conduit adapter
www.belimo.com
01UT-5.. • en-us • 2019-08-20 • Subject to change
2 / 3
Technical data sheet
01UT-5..
Wiring Diagram
Dimensions
Dimensions
.
Type
Weight
01UT-5A
01UT-5B
01UT-5E
01UT-5L
01UT-5M
01UT-5Q
0.26 lb [0.12 kg]
0.26 lb [0.12 kg]
0.26 lb [0.12 kg]
0.26 lb [0.12 kg]
0.26 lb [0.12 kg]
0.26 lb [0.12 kg]
www.belimo.com
01UT-5.. • en-us • 2019-08-20 • Subject to change
3 / 3