General Specifications  
• Power - 2.5 VA to 50 VA  
• Dielectric Strength - 4000 Vrms Hipot  
• Primaries - Dual primaries, 115/230 V, 50/60 Hz,  
• Secondaries - Single secondary  
• Class 2 Rating - inherently or non-inherently limited  
(secondary fuse requirements below)  
• Electrostatic Shield - Not necessary, split bobbin construction  
• Insulation System - Class F insulation, 155° C  
• Flammability Rating - Bobbin and shroud material rated UL 94V0  
Agency Certifications  
• UL recognized to UL 1585 / UL 5085-3 Class 2, File # E116583  
• CSA certified to C22.2 #66.1  
RoHS  
Compliant  
belfuse.com/signal  
CL2 Series Datasheet  
Part Number Selection  
Secondary RMS  
Secondary Fuse  
Required  
Secondary RMS  
Rating  
Secondary Fuse  
Required  
Part Number  
Rating  
Part Number  
CL2-20-12  
CL2-20-24  
CL2-30-12  
CL2-30-24  
CL2-50-12  
CL2-50-24  
12 V @ 1.66 A  
24 V @ 0.833 A  
12 V @ 2.50 A  
24 V @ 1.25 A  
12 V @ 4.20 A  
24 V @ 2.10 A  
N/A*  
N/A*  
CL2-2.5R-12  
CL2-2.5R-24  
CL2-5.0R-12  
CL2-5.0R-24  
CL2-10R-12  
CL2-10R-24  
12 V @ 0.20 A  
24 V @ 0.10 A  
12 V @ 0.42 A  
24 V @ 0.20 A  
12 V @ 0.83 A  
24 V @ 0.42 A  
N/A*  
N/A*  
N/A*  
N/A*  
N/A*  
N/A*  
3.0 A**  
1.75 A**  
5.0 A**  
2.5 A**  
*
Inherently limited ** Non-inherently limited  
Maximum secondary fuse value specified.  
Mechanical Specifications  
Dimensions  
VA  
Mounting Dimensions  
Sq. Pin  
Dimension  
Mounting Screw  
Weight  
lbs (kg)  
L
W
H*  
A
B
C
Inches (mm)  
N
Size  
Inches (mm)  
M
P
Size  
Qty  
1.62  
(41.3)  
1.43  
(36.5)  
1.12  
(28.6)  
.20  
(5.1)  
.25  
(6.4)  
1.00  
(25.4)  
0.025  
(0.64)  
1.06  
(26.9)  
0.25  
(0.11)  
2.5  
#4  
2
1.62  
(41.3)  
1.43  
(36.5)  
1.37  
(34.9)  
.20  
(5.1)  
.40  
(10.2)  
1.00  
(25.4)  
0.025  
(0.64)  
1.06  
(26.9)  
0.37  
(0.17)  
5.0  
#4  
#4  
#4  
#6  
#6  
2
2
2
4
4
1.87  
(47.6)  
1.56  
(39.7)  
1.37  
(34.9)  
.20  
(5.1)  
.40  
(10.2)  
1.14  
(29.0)  
0.036  
(0.91)  
1.25  
(31.8)  
0.53  
(0.24)  
10.0  
20.0  
30.0  
50.0  
2.25  
(57.2)  
1.87  
(47.6)  
1.62  
(41.3)  
.40  
(10.2)  
.40  
(10.2)  
1.46  
(37.1)  
0.036  
(0.91)  
1.50  
(38.1)  
0.90  
(0.41)  
2.62  
(66.7)  
2.18  
(55.5)  
1.56  
(39.7)  
.55  
(14.0)  
.27  
(7.0)  
1.68  
(42.7)  
0.045  
(1.02)  
1.75  
(44.5)  
2.18  
(55.5)  
1.15  
(0.52)  
3.00  
(76.2)  
2.50  
(63.5)  
1.83  
(46.5)  
.60  
(15.2)  
.30  
(7.6)  
1.90  
(48.3)  
0.045  
(1.02)  
2.00  
(50.8)  
2.50  
(63.5)  
1.70  
(0.77)  
* Dimension H represents the total distance from the seating plane to the uppermost surface, stand offs and/or risers inclusive.  
12  
6
115V  
50/60 Hz  
4
3
115V  
50/60 Hz  
1
7
Indicates like polarity  
Note:  
Primaries are designed to be used simultaneously. That is, they  
must be used either series or parallel connected (as one winding).  
ꢀee Accessories page for  
screꢁ anꢂ nut information.  
RoHS  
Compliant  
Custom versions available upon request.  
128 Atlantic Avenue, Lynbrook, NY 11563  
Toll Free 866-239-5777 | Tel 516-239-5777 | Fax 516-239-7208  
sales@signaltransformer.com | techhelp@signaltransformer.com  
belfuse.com/signal  
© 2019 Signal Transformer  
Specifications subject to change without notice  
CL2 PC Series 12.19  

相关型号:

CL2-2.5R-24

Inherently or Non-Inherently Limited
BEL

CL2-20-12

Inherently or Non-Inherently Limited
BEL

CL2-20-24

Inherently or Non-Inherently Limited
BEL

CL2-25-12

Split Bobbin Power Transformer, 25VA,
BEL

CL2-25-24

Split Bobbin Power Transformer, 25VA,
BEL

CL2-30-24

Split Bobbin Power Transformer, 30VA
BEL

CL2-5.0R-12

Inherently or Non-Inherently Limited
BEL

CL2-5.0R-24

Inherently or Non-Inherently Limited
BEL

CL2-50-12

Inherently or Non-Inherently Limited
BEL

CL2-50-24

Inherently or Non-Inherently Limited
BEL

CL2-C-C

CL2 SERIES
DIALIGHT

CL2-C-F

CL2 SERIES
DIALIGHT