LDB120 [BEL]

Output: 12 or 24 VDC model dependent;
LDB120
型号: LDB120
厂家: BEL FUSE INC.    BEL FUSE INC.
描述:

Output: 12 or 24 VDC model dependent

文件: 总4页 (文件大小:409K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
LDB120 Series is a single phase 120 W integrated DIN Rail Battery  
Charger / DC UPS Power Supplies, suitable for wide variety of  
industrial applications.  
In case of mains or unit failure the DC UPS function enables the power  
supply to feed the load from the battery without any interruption, until  
the mains is recovered or the battery reaches the “Deep Discharge  
Voltage” threshold.  
These units have received excellent market approval for their high  
efficiency, excellent reliability and compactness. Simple but elegant  
look and easy installation make them market leaders for various  
industrial applications.  
LDB120 Series are isolation devices suitable for SELV and PELV  
circuitry and are designed to be mounted on DIN rail and installed  
inside a protective enclosure.  
Input: 120 - 240 VAC  
Output: 12 or 24 VDC model dependent  
To be used with Lead Acid batteries or lithium batteries  
(compatible with Lead Acid batteries)  
Efficiency up to 86%  
Economic solution for general purpose applications  
Instantaneous LOAD switch BACKUP mode  
2
LDB120 Series  
LDB120-12  
LDB120-24  
120 - 240 VAC (140 - 345 VDC)  
120 - 240 VAC (140 - 345 VDC)  
1
1
12 VDC  
24 VDC  
7 A  
5 A  
Technical parameters are typical, measured in laboratory environment at 25°C and 240 VAC / 50 Hz, at nominal values, after  
minimum 5 minutes of operation.  
Nominal  
Range  
120 - 240 VAC  
100 - 264 VAC  
Input AC Voltage Range  
Input DC Voltage Range  
Input Frequency  
Rated  
110 - 345 VDC  
47 - 63 Hz  
Vin = 120 VAC  
Vin = 240 VAC  
2.0 A  
1.1 A  
Input AC Current  
Input DC Current  
Vin = 140 VDC  
Vin = 345 VDC  
1.4 A  
0.5 A  
Inrush peak current ² / I²t  
Touch (Leakage) Current  
Internal Protection Fuse  
24 A / 0.50 A²s  
0.6 mA  
Not user replaceable  
Fuse 3.15 AT  
Fuse 4 AT or MCB 4 A C curve /  
Cartridge fuse Class CC 4AT 250 VAC  
It is strongly recommended to provide external surge  
arresters (SPD) according to local regulations  
Recommended External Protection 1  
1 In order to be UL compliant use Listed Cartridge nonrenewable (JDDZ) fuse Class CC 4AT 250 VAC.  
2 Peak current measured after 0.2 ms from main connection; 240 VAC/ 50 Hz; Ambient temperature at 25°C; Cold Start.  
Output Power  
120 W  
LDB120-12 (to be set at 14 VDC for battery charging) 12 VDC (12 15 VDC)  
LDB120-24 (to be set at 27 VDC for battery charging) 24 VDC (23 28 VDC)  
Rated Voltage (Adjustable Voltage Range)  
Continuous Current  
LDB120-12  
LDB120-24  
LDB120-12  
LDB120-24  
LDB120-12  
LDB120-24  
7 A  
5 A  
11.5 A  
6.5 A  
> 20 A / 40 ms  
> 16 A / 80 ms  
Overload Limit  
Short Circuit Peak Current  
Load Regulation  
Ripple & Noise 3  
1%  
100 mVpp  
Vin = 120 VAC  
Vin = 240 VAC  
Vin = 120 VAC  
Vin = 240 VAC  
10 ms  
80 ms  
10 ms  
55 ms  
LDB120-12  
LDB120-24  
Hold up Time  
Overload/short circuit: Hiccup mode  
Thermal protection  
Output overvoltage  
LDB120-12  
Protections  
18 VDC  
33 VDC  
Output Overvoltage Protection (Active)  
Battery Protections  
LDB120-24  
Against short-circuit with resettable fuse (9 A)  
Against reverse polarity connection  
Against deep discharge  
tech.support@psbel.com  
3
LDB120 Series  
LDB120-12  
LDB120-24  
10.5 VDC ± 0.5 V  
20.5 VDC ± 0.5 V  
Deep Discharge Cut-Off Voltage  
LOAD ON PSU - green LED  
Status Signals  
LOAD ON BATTERY - amber LED  
Dry contact (SPDT, 24 VDC / 1 A)  
Not Recommended  
Parallel Connection  
Efficiency  
LDB120-12  
LDB120-24  
LDB120-12  
LDB120-24  
> 83.5%  
> 86%  
< 21 W  
< 20 W  
Dissipated Power  
Battery Information  
Rated Voltage  
LDB120-12  
LDB120-24  
12 - 14.4 VDC  
24 - 28.8 VDC  
Max Charging Current  
0.8 A  
3 Ripple and Noise are measured with 20MHz bandwidth, probe terminated with a 0.1μF MKP parallel capacitor.  
NOTE: Power rating, losses, efficiency, ripple, thermal behaviour and start-up may change outside of the nominal rated input range.  
Contact factory for details.  
Operating Temperature 4  
Storage Temperature  
UL certified up to 50°C  
- 40 to + 70°C  
- 40 to + 80°C  
LDB120-12  
LDB120-24  
- 0.75 W/°C over 50°C  
- 1.2 W/°C over 50°C  
Derating  
Humidity  
Non-condensing  
5 - 95% RH  
Lifetime Expectancy  
at 25°C ambient full load  
167’953 h (19.1 years)  
MTBF  
at 25°C ambient full load, according to MIL-HDBK-217F > 600 000 h  
Overvoltage Category  
Pollution Degree  
EN 50178  
IEC 60664-1  
III  
2
Protection Class  
Class I  
Input to Output  
Input to Ground  
Output to Ground  
UL508 (certified)  
EN 60950 (reference)  
EN 50178 (reference)  
EN 55022 (CISPR22)  
EN 55011 (CISPR11)  
EN 61000-4-2  
EN 61000-4-3  
EN 61000-4-4  
EN 61000-4-5  
EN 61000-4-11  
4.2 kVDC  
2.2 kVDC  
0.75 kVDC  
Isolation Voltage  
Safety Standards & Approvals  
EMC Standards  
Emission  
Immunity  
Class A  
Class A  
Level 3  
Level 2  
Level 2  
Level 3  
Level 2  
Protection Degree  
Vibration Sinusoidal  
EN 60529  
IP20  
5-17.8 Hz: ±1.6 mm; 17.8-500 Hz: 2 g  
2 hours / axis (X, Y, Z)  
IEC 60068-2-6  
30 g 6 ms, 20 g 11 ms;  
3 bumps / direction, 18 bumps total  
Shock  
IEC 60068-2-27  
4 Start-up type tested: - 40°C, possible at nominal voltage with load deration.  
North America  
+1 408 785 5200  
Asia-Pacific  
+86 755 298 85888  
Europe, Middle East  
+353 61 225 977  
© 2021 Bel Power Solutions & Protection  
BCD.00856_AC  
4
LDB120 Series  
Weight  
500 g  
Dimensions  
54 x 115 x 110 mm  
IEC 60715/H15/TH35-7.5(-15)  
2.5 mm²  
Mounting Rail  
Connection Terminals  
Case Material  
Screw type pluggable (24 - 12 AWG)  
Aluminum  
Figure 1. Mechanical Drawing  
INPUT CONNECTION  
OUTPUT CONNECTION  
LOAD + = Positive DC  
LOAD - = Negative DC  
BATTERY + = Positive DC Battery  
BATTERY - = Negative DC Battery  
Single phase:  
L = Line  
N = Neutral  
= Earth ground  
Signaling:  
SPDT dry contact  
DC:  
L = + Positive DC  
N = - Negative DC  
NO  
NC  
COM  
= Earth ground  
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems,  
equipment used in hazardous environments, or nuclear control systems.  
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the  
date manufactured. Specifications are subject to change without notice.  
tech.support@psbel.com  

相关型号:

LDB120-12

Output: 12 or 24 VDC model dependent
BEL

LDB120-24

Output: 12 or 24 VDC model dependent
BEL

LDB181G8115G-120

Chip Multilayer Hybrid Baluns
MURATA

LDB181G8120G-120

Chip Multilayer Hybrid Baluns
MURATA

LDB181G8405C-110

Chip Multilayer Hybrid Baluns
MURATA

LDB181G8420C-110

Chip Multilayer Hybrid Baluns
MURATA

LDB181G8820C-110

Chip Multilayer Hybrid Baluns
MURATA

LDB181G9505C-110

Chip Multilayer Hybrid Baluns
MURATA

LDB181G9510C-110

Chip Multilayer Hybrid Baluns
MURATA

LDB182G4505C-110

Chip Multilayer Hybrid Baluns
MURATA

LDB182G4510C-110

Chip Multilayer Hybrid Baluns
MURATA

LDB182G4510G-120

Chip Multilayer Hybrid Baluns
MURATA