LDN240 [BEL]
Single phase AC input 120 / 240 VAC (with switch);型号: | LDN240 |
厂家: | BEL FUSE INC. |
描述: | Single phase AC input 120 / 240 VAC (with switch) |
文件: | 总4页 (文件大小:539K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
LDN240 Series are single phase DIN Rail Switching Power Supplies,
suitable for worldwide applications such as process control, heavy
duty applications, but also building automation.
These units have received excellent market approval for their high
efficiency, excellent reliability and compactness. Simple but elegant
look and ease of installation due to pluggable connectors make them
ideal for various industrial applications.
LDN240 Series are Class I isolation devices suitable for SELV and
PELV circuitry (up to 48 VDC models) and are designed to be mounted
on DIN rail and installed inside a protective enclosure.
Single phase AC input 120 / 240 VAC (with switch)
High efficiencies and in compact size
Only 63 mm width aluminum enclosure
130% overload
Adjustable output voltage
Short circuit, overload and over temperature protection
RoHS Compliant
Automation
Process Control
Communication
Instrumentation Equipment
2
LDN240 Series
LDN240-12
LDN240-24
LDN240-24P
LDN240-48P
LDN240-72P
120 / 240 VAC (270 - 345 VDC)
120 / 240 VAC (270 - 345 VDC)
120 / 240 VAC (270 - 345 VDC)
120 / 240 VAC (270 - 345 VDC)
120 / 240 VAC (270 - 345 VDC)
1
1
1
1
1
12 VDC
24 VDC
24 VDC
48 VDC
72 VDC
16 A
No ORing diode
No ORing diode
10 A
10 A
5 A
Internal ORing diode
Internal ORing diode
Internal ORing diode
3.5 A
Technical parameters are typical, measured in laboratory environment at 25°C and 240 VAC / 50 Hz, at nominal values, after minimum
5 minutes of operation.
Rated, UL certified – settable with Input voltage selector 120 / 240 VAC
Input AC Voltage Range
Operating
92 – 132 / 187 - 264 VAC
Input DC Voltage Range
Input Frequency Range
Rated
270 - 345 VDC
47 - 63 Hz
Vin = 120 VAC
Vin = 240 VAC
4 A
2 A
Input AC Current
Input DC Current
Vin = 270 VDC
Vin = 345 VDC
1.3 A
1 A
Inrush Peak Current
≤ 40 A
Touch (Leakage) Current
Internal Protection Fuse
≤ 0.8 mA
Fuse 6.3 AT
Not user replaceable
It is strongly recommended to provide external surge
arresters (SPD) according to local regulations
Fuse 10 AT or MCB 10 A C curve
Recommended External Protection
Output Power
240 W
LDN240-12
LDN240-24 / LDN240-24P
LDN240-48P
12 VDC (12 – 15 VDC)
24 VDC (23 – 28 VDC)
48 VDC (45 – 55 VDC)
Rated Voltage
(Adjustable Voltage Range)
LDN240-72P
LDN240-12
72 VDC (72 – 85 VDC)
16 A
LDN240-24 / LDN240-24P
LDN240-48P
LDN240-72P
LDN240-12
LDN240-24 / LDN240-24P
LDN240-48P
10 A
5 A
3.5 A
19 - 16 A
13.5 A
6.8 A
Continuous Current
Overload Limit
LDN240-72P
LDN240-12
4.6 A
42 A
LDN240-24 / LDN240-24P
LDN240-48P
35 A
20 A
Short Circuit Peak Current
LDN240-72P
LDN240-12
LDN240-24
14 A
≤ 1.5%
≤ 1%
Load Regulation
Ripple & Noise1
LDN240-24P
LDN240-48P / LDN240-72P
LDN240-12
≤ 2.5%
≤ 1.5%
≤ 150 mVpp
LDN240-24 / LDN240-24P / LDN240-48P / LDN240-72P ≤ 100 mVpp
tech.support@psbel.com
3
LDN240 Series
Vin = 120 VAC
Vin = 240 VAC
≥ 60 ms
≥ 70 ms
Hold up Time
Protections
Overload, short circuit: Hiccup mode
Thermal protection
Output overvoltage
LDN240-12
LDN240-24 / LDN240-24P
LDN240-48P
LDN240-72P
≥ 18 VDC
≥ 33 VDC
≥ 68 VDC
≥ 100 VDC
Output Over Voltage Protection
DC OK - green LED
DC OK - dry contact (NO, 24 VDC / 1 A)
Status Signals
Possible for redundancy (with external ORing module)
P (models) - include internal ORing circuit
Parallel Connection
LDN240-12
LDN240-24
LDN240-24P
LDN240-48P
LDN240-72P
LDN240-12
LDN240-24
LDN240-24P
> 84%
> 88%
> 86%
> 88%
> 88%
< 36.5 W
< 33 W
< 39 W
< 33 W
< 34.5 W
Efficiency
Dissipated Power
LDN240-48P
LDN240-72P
1
Ripple and Noise are measured with 20MHz bandwidth, probe terminated with a 0.1μF MKP parallel capacitor.
NOTE: Power rating, losses, efficiency, ripple, thermal behaviour and start-up may change outside of the nominal rated input range.
Contact factory for details.
UL certified up to 50°C
- 40 to + 70°C
Operating Temperature
(Start-up type tested: - 40°C)2
Storage Temperature
Derating
- 40 to + 80°C
- 5 W / °C over 50°C
5 - 95% RH
Humidity
Non-condensing
Life Time Expectation
At 25°C ambient full load
77894 h (8.8 years)
Overvoltage Category
Pollution Degree
III (EN50178)
2 (IEC60664-1)
Protection Class
Class I
Input to Output
Input to Ground
Output to Ground
UL508 (certified)
EN60950 (reference)
EN50178 (reference)
EN55011 (CISPR11)
EN55022 (CISPR22)
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-11
4.2 kVDC
2.2 kVDC
0.75 kVDC
Isolation Voltage
Safety Standards & Approvals
EMC Emission
Class A
Class A
Level 3
Level 3
Level 3
Level 3
Level 2
EMC Immunity
Protection Degree
Vibration Sinusoidal
EN60529
IP20
5 - 17.8 Hz: ±1.6 mm; 17.8 - 500 Hz:
2 g 2 Hours / axis (X, Y, Z)
IEC 60068-2-6
30 g 6 ms, 20 g 11 ms; 3 bumps / direction,
18 bumps total
Shock
IEC 60068-2-27
2 Possible with load derating.
North America
Asia-Pacific
Europe, Middle East
+1 408 785 5200
+86 755 298 85888
+353 61 225 977
© 2016 Bel Power Solutions & Protection
BCD.00717_AB
4
LDN240 Series
Weight
750 g
Dimensions (W x D x H)
Mounting Rail
63 x 140 x 117 mm
IEC 60715/H15/TH35-7.5(-15)
2.5 mm²
Connection Terminals
Case Material
Screw type pluggable (24 - 12 AWG)
Aluminum
Figure 1. Mechanical Drawing
INPUT CONNECTION
OUTPUT CONNECTION
Single phase:
L = Line
N = Neutral
= Earth ground
DC:
L = + Positive DC
N = - Negative DC
= Earth ground
AC/DC input
1
2
+ = Positive DC
- = Negative DC
DC output (load)
Diagnostic Output
(dry contact, NC output OK)
Green LED: Output OK
3
Signaling:
DC OK: dry contact
NO
COM
4
5
6
Output voltage adjustment
Input voltage selector
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems,
equipment used in hazardous environments, or nuclear control systems.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.
tech.support@psbel.com