LDW480 [BEL]
Only 73 mm width aluminum enclosure;型号: | LDW480 |
厂家: | BEL FUSE INC. |
描述: | Only 73 mm width aluminum enclosure |
文件: | 总4页 (文件大小:569K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
LDW480 Series are single, two or three phase DIN Rail Switching
Power Supplies with active PFC.
Its compact size, high efficiency, excellent reliability together with easy
installation makes it ideal for various industrial, telecom and renewable
energy applications.
LDW480 Series are Class I isolation devices suitable for SELV and
PELV circuitry (up to 48 VDC models) and are designed to be mounted
on DIN rail and installed inside a protective enclosure.
High efficiency
•
•
•
•
•
•
•
•
Only 73 mm width aluminum enclosure
Single, two or three phase input AC 187 – 550 VAC
Wide DC input range 250 – 725 VDC
Active PFC for optimal efficiency
Compact size
150% overload capability
RoHS Compliant
Industrial Control
Communication
•
•
•
•
Instrumentation Equipment
Renewable
2
LDW480 Series
LDW480-24
LDW480-48
LDW480-72
200 - 500 VAC (250 - 725 VDC)
200 - 500 VAC (250 - 725 VDC)
200 - 500 VAC (250 - 725 VDC)
1 / 2 / 3
1 / 2 / 3
1 / 2 / 3
24 VDC
48 VDC
72 VDC
20 A
10 A
6 A
No ORing diode
No ORing diode
No ORing diode
Technical parameters are typical, measured in laboratory environment at 25°C and 400 VAC / 50 Hz, at nominal values, after minimum
5 minutes of operation.
Rated, single, two or three phase, UL certified
Operating
200 – 500 VAC
187 - 550 VAC
Input AC Voltage Range
Input DC Voltage Range
Input Frequency Range
Rated
250 – 725 VDC
With single, two or three phase
With single or two phase only
47 - 63 Hz
400 Hz
Single or two phase @ 200 VAC
Single or two phase @ 500 VAC
Three phase @ 200 VAC
2.9 A
1.3 A
1.8 A
0.8 A
Input AC Current
Three phase @ 500 VAC
Vin = 250 VAC
Vin = 725 VAC
2.1 A
0.8 A
Input DC Current
Power Factor Correction
Inrush Peak Current
Active
> 0.9
≤ 60 A
Touch (Leakage) Current
Continuous Overvoltage Protection
Internal Protection Fuse
≤ 0.6 mA
No damage up to 550 VAC / 725 VDC
None, external fuse must be provided
It is strongly recommended to provide external surge
arresters (SPD) according to local regulations.
Fuse AT 6.3A or MCB 6 A C curve
or 4 A D curve
Recommended External Protection
Output Power
480 W
LDW480-24
LDW480-48
LDW480-72
LDW480-24
LDW480-48
LDW480-72
LDW480-24
LDW480-48
LDW480-72
LDW480-24
LDW480-48
LDW480-72
24 VDC (23 – 28 VDC)
48 VDC (45 – 55 VDC)
72 VDC (72 – 85 VDC)
Rated Voltage
(Voltage Adjustment Range)
20 A
10 A
6 A
28 A
14 A
9 A
50 A
25 A
12 A
Continuous Current
Overload Limit
Short Circuit Peak Current
Load Regulation
Ripple & Noise1
Hold up Time
≤ 1%
LDW480-24 / LDW480-48
LDW480-72
≤ 50 mVpp
≤ 100 mVpp
≥ 50 ms
Overload, short circuit: Hiccup mode
Thermal protection
Protections
Output overvoltage
tech.support@psbel.com
3
LDW480 Series
LDW480-24
LDW480-48
LDW480-72
DC OK - green LED
OVERLOAD - red LED
DC OK - dry contact (NO, 24 VDC / 1A)
≥ 33 VDC
≥ 68 VDC
≥ 100 VDC
Output Over Voltage Protection
Status Signals
Parallel Connection
Efficiency
Possible for redundancy (with external ORing module)
LDW480-24 / LDW480-48
LDW480-72
> 92%
> 91%
LDW480-24 / LDW480-48
LDW480-72
< 42 W
< 42.5 W
Dissipated Power
1
Ripple and Noise are measured with 20 MHz bandwidth, probe terminated with a 0.1μF MKP parallel capacitor.
NOTE: Power rating, losses, efficiency, ripple, thermal behaviour and start-up may change outside of the nominal rated input range.
Contact factory for details.
UL certified up to 45°C
- 40 to + 70°C
Operating Temperature
(Start-up type tested: - 40°C)2
Storage Temperature
Derating
- 40º C to + 80º C
- 10 W /° C over 45°C
5 - 95% RH
Humidity
Non-condensing
Life Time Expectancy
At 25°C ambient, full load
65496 h (7.4 years)
Overvoltage Category
Pollution Degree
III (EN50178)
2 (IEC60664-1)
Protection Class
Class I
Input to Output
Input to Ground
Output to Ground
UL508 (certified)
EN60950 (reference)
EN50178 (reference)
EN55011 (CISPR11)
EN55022 (CISPR22)
EN61000-3-2
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
4.2 kVDC
2.2 kVDC
0.75 kVDC
Isolation Voltage
Safety Standards & Approvals
EMC Standards
Emission
Immunity
Class A
Class A
Class A
Level 3
Level 3
Level 3
Level 3
Level 2
EN61000-4-11
Protection Degree
Vibration Sinusoidal
EN60529
IP20
IEC 60068-2-6:2007 (5-17.8 Hz: ±1.6 mm;
17.8-500 Hz: 2g 2Hours / axis (X, Y, Z)
IEC 60068-2-6
IEC 60068-2-27:2008 (30 g 6 ms, 20 g 11 ms;
bumps / direction, 18 bumps total)
Shock
IEC 60068-2-27
2
Possible with load derating.
Weight
1000 g
Dimensions (W x H x D)
Mounting Rail
73 x 140 x 125 mm
IEC 60715/H15/TH35-7.5(-15)
2.5 mm²
Connection Terminals
Case Material
Screw type pluggable (24 - 12 AWG)
Aluminum
North America
+1 408 785 5200
Asia-Pacific
+86 755 298 85888
Europe, Middle East
+353 61 225 977
© 2017 Bel Power Solutions & Protection
BCD.00721_AC
4
LDW480 Series
Figure 1. Mechanical Drawing
PIN
1
DESCRIPTION
INPUT CONNECTION
OUTPUT CONNECTION
AC/DC input
Single phase:
L = Line
N = Neutral
= Earth ground
2 phase:
L1 = Phase 1
L2 = Phase 2
= Earth ground
3 phase:
L1 = Phase 1
L2 = Phase 2
L3 = Phase 3
= Earth ground
DC:
+ = Positive DC
- = Negative DC
DC output (load)
Diagnostic Output
(dry contact, NC output OK)
Green LED: Output OK
2
3
4
5
6
Red LED: Overload
Output voltage adjustment
Signaling:
DC OK: dry contact
NO
COM
L1(L) = + Positive DC
L2(N) = - Negative DC
L3 = do not connect
= Earth ground
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems,
equipment used in hazardous environments, or nuclear control systems.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.
tech.support@psbel.com