1250-1S-120 [BOURNS]
General Duty AC Surge Protective Device; 总值班室交流浪涌保护器型号: | 1250-1S-120 |
厂家: | BOURNS ELECTRONIC SOLUTIONS |
描述: | General Duty AC Surge Protective Device |
文件: | 总3页 (文件大小:379K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Features
■ Compact design ideal for limited spaces
■ Standards compliance:
■ RoHS compliant*
■ 50 kA max. discharge current rating
■ Multi-pole uni-block design
■ DIN Rail mountable
■ UL 60691 compliant integrated thermal
disconnect
■ Visual fault indicator
■ Remote signalling capability
1250 Series General Duty AC Surge Protective Device
General Information
Electrical Diagram
®
L/N
. . .
The Bourns Model 1250 Series is a general duty Surge Protective Device (SPD)
designed to protect high risk electrical service entrance and branch panels. This SPD is
intended to be installed at the front end of the installation, in the main switchboard, close
to sensitive terminals or in installations without LPS (lightning rods).
C
V : High energy varistor
Ft : Thermal fuse
Ft
C : Remote signaling contact
t° : Thermal disconnection system
The Model 1250 Series is a single-pole module that can be configured for both common
mode and differential mode protection in single and three phase applications up to 480 V.
V
Electrical Characteristics
Model No.
Characteristic
1250-xS-120
1250-xS-230
1250-xS-400
220/380 V,
277/480 V,
347/600 V
1250-xS-480
120/240 V,
120/208 V
220/380 V,
347/600 V,
480 V
AC Network
240/415 V
Connection Mode
1-Pole, L-N or L-G
AC System
IT, TT, TN, Single, Split Phase, Delta, Wye
Max. Operating Voltage (MCOV)
TOV Withstand
150 V
150 V
275 V
275 V
400 V
400 V
550 V
550 V
Leakage Current at Uc
Follow Current
< 1 mA
None
20 kA
50 kA
--
UL Nominal Discharge Current (In)
15 Impulses 8/20 µs
Max. Discharge Current (I
1 Impulse 8/20 µs
)
max
Max. Lightning Current (I
1 Impulse 10/350 µs
)
imp
UL Voltage Protection Rating (VPR)
Protection Level (Up)
700 V
0.9 kV
1000 V
1.25 kV
1200 V
1.8 kV
1800 V
2.5 kV
UL Short-Circuit Current Rating (SCCR)
100kAIC
General Characteristics
Model No.
Characteristic
1250-xS-120
1250-xS-230
1250-xS-400
1250-xS-480
Thermal Disconnector
Overcurrent Protection
Connection
UL 60691
Time Delay - 125 A Max.
By Screw Terminals, #6 AWG Max.
Dimensions
90 x 18 x 67 mm / (3.543 x 0.709 x 2.638 In.)
DIN Rail, 35 mm Symmetrical
250 Vac Max., 2 A
Mounting
Remote Signal Indicator
Enclosure Material
Thermoplastic UL 94V0
Environmental Characteristics
Model No.
Characteristic
1250-xS-120
1250-xS-230
1250-xS-400
1250-xS-480
Operating Temperature
Operating Altitude
-50 °C to +85 °C
13,000 ft. (4,000 m)
5 to 95 % Non-condensing, up to 100 % External
IP 20
Relative Humidity
Environmental Rating
*RoHS Directive 2002/95/EC Jan. 27, 2003 including annex and RoHS Recast 2011/65/EU June 8, 2011.
Specifications are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.
Applications
■ Electrical service entrance
■ Branch panels
1250 Series General Duty AC Surge Protective Device
Product Dimensions and Schematics
1250-1S-xxx
10.6
67.0
18.0
(.709)
(.417)
(2.638)
L/N
L/N
Mi
Ft
t°
AC Surge
Protector
SPD1250-xxx
90.0
(3.543)
Uc
V
In
Imax
Up
C
1250-2S-xxx
67.0
(2.638)
36.0
(1.417)
L/N
L/N
90.0
(3.543)
L
N
Mi
Mi
Ft
Ft
MM
(INCHES)
DIMENSIONS:
t°
t°
AC Surge
Protector
SPD1250-xxx SPD1250-xxx
AC Surge
Protector
Uc
Uc
V
V
In
In
Imax
Up
Imax
Up
44.0
(1.732)
10.6
(.417)
C
60.8
(2.394)
1250-3S-xxx
54.0
(2.126)
L1
L2
L3
L
L
L
Mi
Mi
Mi
Ft
Ft
Ft
t°
t°
t°
AC Surge
Protector
AC Surge
Protector
AC Surge
Protector
SPD1250-xxx SPD1250-xxx SPD1250-xxx
Uc
Uc
Uc
V
V
V
In
In
In
Imax
Up
Imax
Up
Imax
Up
C
Specifications are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.
1250 Series General Duty AC Surge Protective Device
Product Dimensions and Schematics (Continued)
1250-4S-xxx
72.0
(2.835)
L/N
L/N
L/N
L/N
L
L
L
N
Mi
Mi
Mi
Mi
Ft
Ft
Ft
Ft
t°
t°
t°
t°
AC Surge
Protector
AC Surge
Protector
AC Surge
Protector
AC Surge
Protector
MM
(INCHES)
SPD1250-xxx SPD1250-xxx SPD1250-xxx SPD1250-xxx
DIMENSIONS:
Uc
In
Uc
Uc
Uc
V
V
V
V
In
In
In
Imax
Up
Imax
Up
Imax
Up
Imax
Up
C
Standards Compliance
How To Order
1250 - x S - xxx
IEC61643-1 - International ................................ Class I, Class II
EN 61643-11 - Europe....................................... Class I, Class II
NF EN 61643-11 - France ................................. Class I, Class II
UL1449 3rd Edition - USA.................... Type 4, Type 2 Location
UL1449 3rd Edition - Canada............... Type 4, Type 2 Location
CSA C22.2 No. 8-M1986............ Class 9091 32, Class 9091 92
RoHS..............................................RoHS Directive 2002/95/EC
Jan. 27, 2003 including annex and
Series
Configuration
1 = One Protected Pole
2 = Two Protected Poles
3 = Three Protected Poles
4 = Four Protected Poles
Remote Signaling Code
S = Remote Signaling
RoHS Recast 2011/65/EU June 8, 2011
Operating Voltage
120 = 120/240 V, 120/208 V
230 = 220/380 V, 240/415 V
400 = 220/380 V, 277/480 V, 347/600 V
480 = 347/600 V, 480 V
Asia-Pacific: Tel: +886-2 2562-4117 • Fax: +886-2 2562-4116
Europe: Tel: +41-41 768 5555 • Fax: +41-41 768 5510
The Americas: Tel: +1-951 781-5500 • Fax: +1-951 781-5700
www.bourns.com
REV. 05/13
Specifications are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.
相关型号:
©2020 ICPDF网 联系我们和版权申明