VKA60MS05 [CANDD]
50 WATT SINGLE OUTPUT HALF BRICK DC/DC CONVERTER; 50瓦单输出半砖DC / DC转换器型号: | VKA60MS05 |
厂家: | C&D TECHNOLOGIES |
描述: | 50 WATT SINGLE OUTPUT HALF BRICK DC/DC CONVERTER |
文件: | 总4页 (文件大小:459K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Corporate: www.cdtechno.com
Product: www.cdpowerelectronics.com
VKA60xS
60 Watt Single Output Half Brick DC/DC Converter
ꢀ Operation to +100°C Baseplate
Temperature
ꢀ 18-36 V & 33 - 75V Input Range
ꢀ High Efficiency: 87% Typical at
5V
ꢀ Primary Remote On/Off, Choice of
Pos/Neg Logic
ꢀ 100µS Transient Response 50-
ꢀ Adjustable Output Voltage
ꢀ Continuout Short-Circuit Protection
ꢀ Thermal Shutdown
100%Load Step
ꢀ 420 kHz Fixed-Frequency
Operation
ꢀ Remote Sense
ꢀ Case Ground Pin
The VKA60xS Series DC/DC
converters present an economical and
practical solution for distributed
power system architectures which
require high power density and
efficiency while maintaining system
modularity and upgradeability. With
the ability to operate over a wide
input voltage range of 18 to 36 and
33 to 75 volts, these modules are
ideal for use in battery backup
applications common in todays'
telecommunication and electronic
data processing applications. The
output is fully isolated from the
input, allowing for a variety of
polarity and grounding configura-
tions.
load steps in 100µSeconds to within
1% nominal Vout.
The patented fixed frequency
architecture combined with surface
mount technology results in a com-
pact, efficient and reliable solution to
DC/DC conversion requirements.
Safety per UL1950, EN 60950 and
CSA 22.2 #234
The VKA60xS's proprietary
control circuitry responds to 50-100%
PRODUCT SELECTION CHART
MODEL
INPUT
VOUT
IOUT
EFFICIENCY
VOLTAGE
(VDC)
3.3V
5.0V
(A)
MIN
80
85
87
88
89
81
86
88
89
89
TYP
81
86
88
89
90
82
87
89
90
90
VKA60LS03
VKA60LS05
VKA60LS12
VKA60LS15
VKA60LS24
VKA60MS03
VKA60MS05
VKA60MS12
VKA60MS15
VKA60MS24
12.0
12.0
5.0
24VDC
(18-36)
12.0V
15.0V
24.0V
3.3V
4.0
2.5
12.0
12.0
5.0
48VDC
(33-75)
5.0V
12.0V
15.0V
24.0V
4.0
2.5
SPECIFICATIONS, ALL MODELS
Specifications are at TCASE = +40°C nominal input voltage unless otherwise specified.
PARAMETER
CONDITIONS
MIN
TYP
MAX
UNITS
INPUT
Voltage Range
VKA60LS
VKA60MS
18
33
24
48
36
75
VDC
VDC
Maximum Input Current
VKA60LS
VIN = 16VDC
VIN = 27VDC
Peak - Peak
DC to 1KHz
4.4
2.6
A
A
mA
dB
mA
VKA60MS
Reflected Ripple Current
Input Ripple Rejection
No Load Input Current LS/MS
Power Dissipation LS/MS
No Load
20
60
50/100
50
3.6/4.8
0.18/0.4
W
W
Standby, Primary On/Off Disabled LS/MS
Inrush Charge
VIN = VINmax.
VKA60LS
VKA60MS
0.520
0.360
mC
mC
Quiescent Operating Current
Primary On/Off Disabled
8
12
mA
PARAMETER
CONDITIONS
MIN
TYP
MAX
UNITS
OUTPUT
Rated Power
Set point Accuracy
Line Regulation
0
60
1
0.05
0.05
W
%
%
High Line to Low Line
No Load to Rated Load
0.02
0.02
.02
Load Regulation
%
Output Temperature Drift
Output Ripple, p-p
Output Current Limit Inception
Output Short-Circuit Current (2)
Output Overvoltage Limit
Transient Response
Peak Deviation
%/°C
VOUT, Nom
lOUT, Nom
lOUT, Nom
V
DC to 20MHz BW
test
1%
130%
110%
135%
125%
50 to 100% Load Step
di/dt = 1.0A/µSec
2%
VOUT, Nom
Settling Time
VOUT, 1% of Nominal Output
100
µSec
PARAMETER
ISOLATION
CONDITIONS
MIN
TYP
MAX
UNITS
Input to Output
Peak Test for 2 Seconds
1500
1500
500
10
VDC
VDC
VDC
MΩ
Input to Baseplate
Output to Baseplate
Resistance
Capacitance
Leakage Current
GENERAL
2000
180
pF
µA, rms
VISO = 240VAC, 60Hz
Efficiency, Line, Load, Temp. (3)
Switching Frequency
Remote Sense Compensation
Output Voltage Adjust Range
Remote On/Off Control Inputs
Primary
400
420
440
0.5
KHz
V
VOUT, Nom
12V & higher(4)
-50% / +25%
Open Collector/Drain
Sink Current-Logic Low
Vlow
1.0
0.4
mA
V
Vhigh
Turn-on Time
Open Collector
12.5
Within 1% of Rated Output
10.0
mSec
g (oz.)
Weight
85 (3.0)
TEMPERATURE
Operation/Specification
Storage
Shutdown Temperature
Thermal Impedance, case-ambient
Lead Solder Temperature
Case Temperature
Case Temperature
Case Temperature
-40
-55
+100
+25
+25
+100
+125
+115
°C
°C
°C
°C/W
°C
7.1
10 Seconds max
+300
NOTES: (1) See Typical Performance Curves, page 3
(2) Continuous Mode
(3) See graphs for Efficiency vs. Output Load, VIN, TCASE
(4) 3.3V Models Limited in Trim Down Range
(5) Consult Factory for Details
Product: www.cdpowerelectronics.com
2
VKA60xS Rev C 3/2001
VKA60 xSzz -
Device Family
Indicates 60 Watt Regulated Unit
Model Number
Selected from Table of Electrical Characteristics
Where:
x = Input Voltage (L = 24VDC; M = 48VDC)
zz = Output Voltage (03=3.3V, 05=5V, etc.)
Lead Length
0.200" - No Number
0.145" - (6)
0.110" - (8)
Remote On-Off Logic:
Positive - No Number
Negative - (1)
Product: www.cdpowerelectronics.com
3
VKA60xS Rev C 3/2001
MECHANICAL
NOTES:
All dimensions are in inches (millimeters).
PIN PLACEMENT TOLERANCE: 0.005"
MECHANICAL TOLERANCE: 0.015"
Marked with: specific modeL ordered, date code, job code.
0.530 MAX
[13.46]
0.20 [5.1]
.040 [1.02] DIA.
7 PLACES
MATERIAL: Units are encapsulated in a low thermal
resistancemoldingcompoundwhichhasexcellentchemical
resistance and electrical properties in high humidity
environmentsandoverawideoperatingtemperaturerange.
The encapsulant and outer shell of the unit have UL94V-0
ratings. Lead material is solder plated to allow ease of
solderability.
.081 [2.06] DIA.
2 PLACES
0.20 [5.1]
0.50 [12.7]
.400 [10.16]
0.40 [10.16]
2.000
[50.80]
0.700
[17.78]
1.000
[25.40]
VKA60xS
1.000
[25.40]
2.40
[61.0]
MAX
1.400
1.400
[35.56]
[35.56]
MOUNTING INSERTS M3 X 0.5 THRU, 4 PLACES
MAX. TORQUE, 8 IN/LBS
1.900
0.19 [4.8]
[48.26]
2.28
[57.91]
MAX
OUTPUT ADJUST VOLTAGE
OVP NOTE
Special attention should be given to the peak voltage
deviation during a dynamic load step when trimming
the output above the original set point to avoid
tripping the overvoltage protection circuit. Should an
OVP condition occur, the converter will go into a
latch condition and must be externally reset before it
will return to normal operation.
This feature allows the user to accurately adjust the
module's output voltage set point to a specified level.
This is achieved by connecting a resistor or potentiometer
from the TRIM terminal to either the +Vout terminal (for
increased Vout) or the -Vout terminal (for decreased
Vout). The formulae below describe the trim resistor
value to obtain a Vout change of ∆%. VO is output
voltage prior to adjustment (3.3V, 5V, 12V, 15V, or 24V).
Vo(100 + ∆%)
1.225∆%
(100 + 2∆%)
∆%
_
Radj - up =
kΩ
(
)
100
∆%
Radj - down =
(
- 2
)
kΩ
C&D Technologies (Power Electronics) Ltd.
Shannon, Co. Clare, Ireland
Tel: +353.61.474.133 Fax:+353.61.474.141
Power Electronics Division, United States
3400 E Britannia Drive, Tucson, Arizona 85706
Tel: 800.547.2537 Fax: 520.770.9369
C&D Technologies, (NCL)
Milton Keynes MK14 5BU UK
Tel: +44 (0)1908 615232 Fax: +44 (0)1908 617545
Any data, prices, descriptions or specifications presented herein are subject to revision by C&D Technologies, Inc. without notice. While such information is believed to be
accurate as indicated herein, C&D Technologies, Inc. makes no warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or
completeness of such information. Further, because the product(s) featured herein may be used under conditions beyond its control, C&D Technologies, Inc. hereby
disclaims all warranties, either express or implied, concerning the fitness or suitability of such product(s) for any particular use or in any specific application or arising from
any course of dealing or usage of trade. The user is solely responsible for determining the suitability of the product(s) featured herein for user’s intended purpose and in
user’s specific application. C&D Technologies, Inc. does not warrant or recommend that any of its products be used in any life support or aviation or aerospace applications.
Product: www.cdpowerelectronics.com
4
VKA60xS Rev C 3/2001
相关型号:
VKA60MS05-1C
DC-DC Regulated Power Supply Module, 1 Output, 60W, Hybrid, ROHS COMPLIANT, HALF BRICK PACKAGE-9
MURATA
VKA60MS05-61C
DC-DC Regulated Power Supply Module, 1 Output, 60W, Hybrid, ROHS COMPLIANT, HALF BRICK PACKAGE-9
MURATA
VKA60MS05-6C
DC-DC Regulated Power Supply Module, 1 Output, 60W, Hybrid, ROHS COMPLIANT, HALF BRICK PACKAGE-9
MURATA
VKA60MS05-8C
DC-DC Regulated Power Supply Module, 1 Output, 60W, Hybrid, ROHS COMPLIANT, HALF BRICK PACKAGE-9
MURATA
©2020 ICPDF网 联系我们和版权申明