CTD-6S10001AXXX [CARLOGAVAZZI]
Accessories AC Split-Core Current Transformer;型号: | CTD-6S10001AXXX |
厂家: | Carlo Gavazzi |
描述: | Accessories AC Split-Core Current Transformer |
文件: | 总2页 (文件大小:296K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Accessories
AC Split-Core Current Transformer
Type CTD-6S
(
max 50x52 mm)
•Bus-bar type split core current transformer
• Class 1 accuracy
•Currents from 150 A to 1000 A
•Up to 6 Bus-bar isolated fixing screws
•Double screw terminals (up to 8-wire connections)
•Sealable terminal block covers
•Sealable fixing split-core screws
Product Description
Ordering Key
CTD-6S 1000 5A XXX
Split-core current transformer Rated primary currents from Model
with bus-bar mountng facility. 150 A to 1000 A.
Primary current
Secondary current
Option
Type Selection
Primary current
Secondary current
Option
From 150A to 1000A
(Refer to the Range Table)
1A (on request)
5A
XXX: none
XTX: tropicalization (on request)
Input Specifications
Working temperature
Storage temperature
Approvals
-25°C to +60°C (-13°F to
140°F) (R.H. < 90% non
condensing @ 40°C)
-30°C to +70°C (-22°F to
158°F) (R.H. < 90% non
condensing @ 40°C)
Operating frequency
Max. system voltage
Rated insulation level
Insulation class
Short-time current rating
Ith
Idyn
48 to 62 Hz
0.72 kV
3 kV/1 min. @ 50 Hz
E (max 75°C)
CE, cURus and CSA
Typical 100 In /1 s
2.5 Ith
The short-time thermal
current Ith is anyway limited
by the cable/bus-bar size
120%
≤ 5 (Class: 1 and 3)
Connection
Cable cross section area
Screw type
From 1.5 to 6 mm2
Min/Max screws tightening
torque relevant to terminal
block screws: From 1 to 2 Nm
Max screws tightening
torque relevant to the
cable/bus-bar fixing screws:
0,3 Nm
Extended current rating
Security factor (FS)
General Specifications
Protection degree
IP00 (without sealable terminal
covers)
IP20 (with sealable terminal
block covers + wire terminals)
Max. 50 mm
Max. 50x52 mm
From 450 to 700 g
Standards
Housing
According to EN61869-2
ABS, self-extinguishing:
UL 94 V-0
Cable diameter
Bus-bar size
Weight
Mounting
Standard accessories
Bus-bar mounting
Two terminal block screws.
Six cable/bus-bar
fixing screws.
Six plastic caps for
cable/bus-bar fixing screws.
Two sealable terminal block
covers.
1 A secondary current,
Tropicalization
Output Specifications
Special features
Rated secondary current
5 A or 1 A
Specifications are subject to change without notice CTD-6S DS ENG 140116
1
CTD-6S
Range Table
Model CTD-6S from 150A to 500A
Model CTD-6S from 600A to 1000A
Primary
Current
Primary
Current
Burden (VA)
Burden (VA)
A
CL 1
CL 3
1.5
2
A
CL 1
7.5
7.5
7.5
10
CL 3
15
150 (@60°C/140°F)
200 (@60°C/140°F)
250 (@60°C/140°F)
300 (@60°C/140°F)
400 (@60°C/140°F)
500 (@60°C/140°F)
-
600 (@60°C/140°F)
700 (@60°C/140°F)
750 (@50°C/122°F)
800 (@50°C/122°F)
1000 (@50°C/122°F)
1.5
1.5
1.5
2.5
5
15
3.75
5
15
15
5
10
15
10
Benefits
1
2
3
4
5
6
7
8
• Easy way to open and close the CT core by
the dedicate seleable screws (see figure 1).
• Bridging of current transformer output
without changing the connection of the
secondary, so to avoid any output
overvoltage during either the maintenance or
the installation procedure (see figure 2).
• Easy output and earth connection (see fig. 3).
• Multiple screws provided with isolation cap
screws to grant a strong and reliable fixing of the
current transformer to the bus-bar (see figure 4).
• Screw terminals compatible with any kind of
wire terminals and protection of screw
terminals using specific sealable covers to
assure always the best safety (see figure 5-
6-7-8).
Dimensions (mm)
Wiring Diagram
S1
S2
L
P1
P2
N
2
Specifications are subject to change without notice CTD-6S DS ENG 140116
相关型号:
©2020 ICPDF网 联系我们和版权申明