DMB01DM24 [CARLOGAVAZZI]
Timers Multifunction;型号: | DMB01DM24 |
厂家: | Carlo Gavazzi |
描述: | Timers Multifunction |
文件: | 总4页 (文件大小:138K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Timers
Multifunction
Types DMB01, PMB01
• Time range 0.1 s to 100 h
• 7 knob selectable functions:
Op
In
-
-
-
-
-
-
-
delay on operate
interval
Io
interval on trigger open
double interval
delay on release
symmetrical recycler ON first
symmetrical recycler OFF first
Id
Dr
R
Rb
• Knob selection of time range
• Knob-adjustable time setting
• Automatic or manual start
• Repeatability: ≤ 0.2%
• Output: 8 A SPDT or 8 A DPDT relay
• For mounting on DIN-rail in accordance with DIN/EN
50 022 or Plug-in
DMB 01
PMB 01
• 22.5 mm Euronorm or 36 mm Plug-in module housing
• Combined AC and DC power supply
• LED indication for relay status and power supply ON
Product Description
Multi-voltage timer with 7 100h. For mounting on DIN-
knob selectable functions rail (DMB01) or Plug-in
and 7 knob selectable time (PMB01).
Ordering Key
Housing
Function
Type
Item number
Output
Power supply
DMB 01 C M24
ranges within 0.1s and
Type Selection
Mounting
DIN-rail
Plug-in
Output
Housing
Supply: 24 VDC and 24 to 240 VAC
Supply: 24 to 240 VAC/DC
SPDT
DPDT
SPDT
DPDT
D-Housing
P-Housing
DMB 01 C M24
PMB 01 C M24
DMB 01 D M24
PMB 01 D M24
Time Specifications
Output Specifications
Time ranges
Output
Rated insulation voltage
Contact Ratings (AgSnO2)
Resistive loads
SPDT or DPDT relay
250 VAC (rms)
Knob Selectable
0.1 to 1 s
1
6
to 10 s
to 60 s
µ
AC 1
DC 12
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
60 to 600 s
0.1 to 1 h
Small inductive loads AC 15
DC 13
1
to 10 h
10 to 100h
Mechanical life
Electrical life
≥ 30 x 106 operations
Setting accuracy
Repeatability
Time variation
Within rated power supply
Within ambient temperature
≤ 5%
≤ 0.2%
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency
Dielectric strength
Dielectric voltage
< 7200 operations/h
≤ 0.05%/V
≤ 0.2%/ºC
2 kVAC (rms)
Reset
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Manual reset of time and/or relay Close the trigger contact
between pins A1 and Y1
or 2 and 5
≥ 100 ms
≥ 200 ms
Pulse duration
Power supply interruption
Automatic start
Connect pins A1 and Y1
or 2 and 5
Specifications are subject to change without notice (18.06.07)
1
DMB01, PMB01
Supply Specifications
General Specifications
Power supply
Overvoltage cat. III
(IEC 60664, IEC 60038)
Power ON delay
Indication for
Power supply ON
Output relays ON
≤ 100 ms
Rated operational voltage
through terminals:
(DMB01C) A1, A2
(PMB01C) 2, 10
LED, green
LED, yellow
(flashing when timing)
24 VDC 15% and
24 to 240 VAC
+10%/-15%, 45 to 65 Hz
24 to 240 VAC/DC
+10%/-15%, 45to65Hz
Environment
Degree of protection
Pollution degree
(EN 60529)
IP 20
3 (DMB01), 2 (PMB01)
(IEC 60664)
(DMB01D) A1, A2
(PMB01D) 2, 10
Voltage interruption
≤ 10 ms
Rated operational power
AC supply
Operating temperature
Storage temperature
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
4 VA
1.5 W
DC supply
Housing
Dimensions
DMB01 22.5 x 80 x 99.5 mm
PMB01 36 x 80 x 94 mm
Function and Time Setting
Weight
Approx. 130 g
Screw terminals
Upper knob:
Centre knob:
Tightening torque
Max. 0.5 Nm according to
IEC EN 60947
Setting of function:
Op - delay on operate
In - interval
Time setting on relative
scale: 1 to 10 with respect
to the chosen range.
Approvals
UL, CSA
RINA (DMB01 only)
Io - interval on trigger
open
Id - double interval
Dr - delay on release
Lower knob:
Setting of time range.
CE Marking
EMC
Immunity
Emission
Yes
Electromagnetic Compatibility
According to EN 61000-6-2
According to EN 61000-6-3
R
- symmetrical recycler
(ON first)
Rb - symmetrical recycler
(OFF first)
Timer Specifications
According to EN 61812-1
Mode of Operation
Function Op
keeps ON and a new time the relay operates again for Function R
period starts.
Delay on operate
the set delay period. If the Symmetrical recycler, ON-
The time period begins as
trigger contact is opened time period first
soon as the trigger contact Function Io
is closed. Interval on trigger open
before the end of the first The relay operates and the
time period the second one time period begins as soon
At the end of the set delay The relay operates and the begins; if the trigger contact as the input contact is
time the relay operates and time period begins as soon is closed before the end of closed. After the set delay
doesn't release until the trig- as the trigger contact is the second time period the period the relay releases for
ger contact is closed again opened. At the end of the relay keeps ON and the first the same time period. This
or the power supply is dis- set delay or when the power time period begins again.
connected. If the trigger supply is disconnected the
contact is closed before the relay releases. The relay Function Dr
end of the delay time, the operates again when the Delay on release
device resets and a new trigger contact is opened The relay operates as soon
sequence continues with
equal ON- and OFF-time
periods until the power sup-
ply is interrupted.
time period starts.
again. If the trigger contact as the trigger contact is Function Rb
is opened before the end of closed. The time period Symmetrical recycler,
the delay time the relay begins when the trigger con- OFF-time period first
keeps ON and a new time tact is opened. The relay The time period begins as
Function In
Interval
The relay operates and the period begins.
time period begins as soon
as the trigger contact is Function Id
closed. The relay releases at Double interval
releases at the end of the soon as the input contact is
set delay time or when the closed. The relay is OFF
power supply is disconnect- during the set delay period,
ed. The relay operates again after this time it operates for
the end of this period or The relay operates and the when the input contact is the same time period. This
when the power supply is time period begins as soon closed again. If it is closed sequence continues with
disconnected. The relay as the trigger contact is before the end of the delay equal OFF- and ON-time
operates again when the closed. The relay releases at time the relay keeps ON, a periods until power supply is
trigger contact is closed the end of this period or new time period begins as interrupted.
again. If the trigger contact when the power supply is soon as the contact is
is closed before the end of disconnected.
When the opened again.
the delay time, the relay trigger contact is opened
2
Specifications are subject to change without notice (18.06.07)
DMB01, PMB01
Mode of Operation (cont.)
Additional Load
ger contact without damag- Yellow LED working mode
Incorrect knobs position:
Fast blinking
It's possible to wire an addi- ing the device (see wiring Timing: Slow blinking
tional load (i.e.
between pins Y1 and A2, or
5 and 10, driven by the trig-
a
relay) diagram).
Relay ON: See operation
diagrams
Operation Diagrams
Function Op - Delay on operate - Manual start
Function In - Interval - Manual start
Power supply
Power supply
Trigger input
Trigger input
T
T
T
T
ON
Relay ON
ON
Relay ON
OFF
OFF
LED
LED
Function Op - Delay on operate - Automatic start
Function In - Interval - Automatic start
Power supply
Power supply
T
T
T
T
ON
Relay ON
ON
Relay ON
OFF
OFF
LED
LED
Function Io - Interval on trigger open
Function Id - Double interval
Power supply
Power supply
Trigger input
Trigger input
T
T
T
T
Relay ON
ON
Relay ON
ON
OFF
OFF
LED
LED
Function Dr - Delay on release
Function R - Symmetrical recycler (ON first)
Power supply
Power supply
Trigger input
Trigger input
T
T
T
T
T
Relay ON ON
ON
Relay ON
OFF
OFF
LED
LED
Specifications are subject to change without notice (18.06.07)
3
DMB01, PMB01
Operation Diagrams (cont.)
Function Rb - Symmetrical recycler (OFF first)
Power supply
Trigger input
T
T
T
T
ON
Relay ON
OFF
LED
Wiring Diagrams
DMB 01
PMB 01
L(+)
L(+)
m
m
m
m
26
28
8
9
16
18
4
3
A1
2
S
S
Y1
5
A2
10
25
11
15
1
DMB01C... DMB01D...
DMB01D...
PMB01C... PMB01D...
PMB01D...
N(-)
N(-)
Dimensions
DIN-rail
Plug-in
94
90
22.5
99.5
36
28.5
28.5
4
Specifications are subject to change without notice (18.06.07)