DMC01D724 [CARLOGAVAZZI]
Timers Multifunction;型号: | DMC01D724 |
厂家: | Carlo Gavazzi |
描述: | Timers Multifunction |
文件: | 总6页 (文件大小:241K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Timers
Multifunction
Types DMC01, PMC01
• Time range 0.1 s to 100 h
• 7 knob selectable functions
Op - Delay on operate, manual start
Oa - Delay on operate, automatic and manual start
In - Interval, manual start
Ia - Interval, automatic and manual start
Nr - Interval with no time reset, manual start
Na - Interval with no time reset, automatic and
manual start
Dr - Delay on release
• Knob selection of time range
• Knob adjustable time setting
• External adjustable time setting available
• Repeatability: ≤ 0.2%
DMC01C
DMC01D
PMC01
• DC supply for PNP/NPN and Namur sensors
• Output: 8 A SPDT or 2 x 8 A SPDT relay
• For mounting on DIN-rail in accordance with DIN/EN
50 022 or Plug-in
• 22.5 mm or 45 mm Euronorm or 36 mm Plug-in
module housing
• LED indication for relay status and power supply ON
Product Description
Ordering key
DMC 01 C B23
Multi-voltage timer with 7 15 VDC, 10 mA (1 relay) or 24 Housing
knob selectable functions VDC, 15 mA (2 relays) supply Function
and 7 knob selectable time for PNP/NPN sensors and 8.2 Type
ranges within 0.1s and VDC supply for Namur sensor.
Item number
100h. Remote time setting For mounting on DIN-rail Output
available.
(DMC01) or Plug-in (PMC01).
Power Supply
Type Selection
Mounting
Output
Housing
Supply: 24 VDC
Supply: 24 or 48 VAC
Supply: 115 or 230 VAC
For DIN-rail 1 x SPDT D - 22.5 mm DMC 01 C 724
DMC 01 C B48
DMC 01 D B48
DMC 01 C B23
DMC 01 D B23
For DIN-rail 2 x SPDT D - 45 mm
DMC 01 D 724
Mounting
Output
Housing
Supply: 24 VDC
Supply: 24 VAC
Supply: 115 VAC
PMC 01 C 115
PMC 01 D 115
Supply: 230 VAC
Plug-in
Plug-in
1 x SPDT P - Housing
2 x SPDT P - Housing
PMC 01 C 724
PMC 01 D 724
PMC 01 C 024
PMC 01 D 024
PMC 01 C 230
PMC 01 D 230
Time Specifications
Time ranges
Knob selectable
Reset
Manual reset of time
and/or relay
0.1 to 1 s
1
6
to 10 s
to 60 s
Close the trigger contact
Pulse duration
≥ 10 ms
60 to 600 s
0.1 to 1 h
Power supply interruption
1 relay versions:
2 relays versions:
≥ 700 ms
≥ 200 ms
1
to 10 h
10 to 100 h
PNP/NPN sensor supply output
1 relay versions:
Setting accuracy
Repeatability
Time variation
≤ 5%
≤ 0.2%
15 VDC, 10 mA
24 VDC, 15 mA
pins + and - or 6 and 7
pin + or 6 positive
2 relays versions:
Within rated power supply
≤ 0.05%/V
Within ambient temperature ≤ 0.2%/°C
Namur sensor connection
8.2 VDC, 1kΩ
pins + and S or 6 and 5
pin + or 6 positive
External time setting
Linear remote potentiometer 10 kΩ
Max length of pot. cable
3 m
Specifications are subject to change without notice (18.06.07)
1
DMC01, PMC01
Output Specifications
General Specifications
Output
1 or 2 x SPDT relay
Power ON delay
≤ 100 ms
Rated insulation voltage
Contact Ratings (AgSnO2)
250 VAC (RMS)
Reaction time from trigger
Delayed contact(s)
Instantaneous contcat
< 10 ms
< 20 ms
µ
Resistive loads
AC 1
DC 12
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
Indication for
Power supply ON
Output relays ON
Small inductive loads AC 15
DC 13
LED, green
LED, yellow (flashing when
timing)
Mechanical life
Electrical life
≥ 30 x 106 operations
≥ 105 operations
Environment
Degree of protection
Pollution degree
(EN 60529)
IP 20
3 (DMC01), 2 (PMC01)
(IEC 60664)
-20 to 60 °C, R.H. < 95%
-30 to 80 °C, R.H. < 95%
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency
Dielectric strength
Dielectric voltage
< 7200 operations / h
Operating temperature
Storage temperature
2 kVAC (RMS)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Housing
Dimensions
DMC01C
DMC01D
PMC01
22.5 x 80 x 99.5 mm
45 x 80 x 99.5 mm
36 x 80 x 94 mm
Supply Specifications
Power supply
Rated operational voltage
through terminals:
Overvoltage cat. III
(IEC 60664, IEC 60038)
Weight
120 to 260g depending on
model
Screw terminals
Tightening torque
(DMC01)
Max 0.5 Nm according to
IEC EN 60947
A1, A2 or A1, A3 (DMC01)
B48
24 or 48 VAC 15%
45 to 65 Hz
115 or 230 VAC 15%
45 to 65 Hz
Approval
CE Marking
EMC
Immunity
Emission
UL, CSA
Yes
B23
724
24 VDC 20%
Electromagnetic Compatibility
According to EN 61000-6-2
According to EN 61000-6-3
2, 10 (PMC01)
024
115
230
724
24 VAC 15%,45 to 65 Hz
115 VAC 15%,45 to 65 Hz
230 VAC 15%,45 to 65 Hz
24 VDC 20%
Timer Specifications
According to EN 61812-1
Voltage interruption
≤ 10 ms
Rated operational power
AC supply:
5 VA
2 W
DC supply:
Function/Range/Time Setting
Adjust the function setting To access the DIP switches
the DIP switches 1 to 6 as open the grey plastic cover
In - Interval, manual start
scale: 1 to 10 with respect
Ia - Interval,
automatic to the chosen range.
shown below (1 to 4 for using
a
screwdriver as
and manual start
Nr - Interval with no time
reset, manual start
Na - Interval with no time
reset, automatic and
manual start
Lower knob:
DMC01Cxxx).
shown below.
Setting of time range
Note 1: DIP switch 5 must
be kept ON when using
PMC01Dxxx.
Upper knob:
External
(DMC01D, PMC01C):
Time setting on relative
scale: 1 to 10 with respect
to the chosen range.
potentiometer
Selection of function:
Op - Delay on operate,
manual start
Note 2: DIP switch 6 does
not have any effect on the
PMC01Cxxx working mode.
Dr - Delay on release
Oa - Delay on operate,
automatic and manual Centre knob:
start Time setting on relative
Sensor type selection
DMC01D,
PMC01C,
PMC01D
ON ON OFF OFF: PNP/NPN sensor,
Open collector
DMC01C
or contact
OFF OFF ON ON: Namur sensor
Time setting (DMC01D and PMC01C)
ON:
OFF:
Centre knob on front
External trimmer
Second relay
ON:
OFF:
Instantaneous
DPDT
2
Specifications are subject to change without notice (18.06.07)
DMC01, PMC01
Mode of Operation
Function Op: Delay on
operate, manual start
Function Ia: Interval, auto- Function Dr: Delay on Example 2: Interval with
matic and manual start
release
NPN or Namur proximity
sensor.
The time period begins as The relay operates and the The relay operates as soon
soon as the trigger contact time period begins as soon as the trigger contact is Using the Interval function
is closed. as the power supply is con- closed. The time period and a NPN or Namur prox-
At the end of the set delay nected. begins when the trigger con- imity sensor, DMC01 and
time the relay operates and The relay releases at the end tact is opened. The relay PMC01 can be used to
doesn't release until the trig- of this period or when the releases at the end of the monitor the actual presence
ger contact is closed again power supply is disconnect- set delay time or when the of an object (i.e. a can) in
or the power supply is dis- ed. The relay operates again power supply is disconnect- the right place on a convejor
connected. When the trigger when the trigger contact is ed. The relay operates again belt. In fact the sensor trig-
contact is closed, the relay closed. If the trigger contact when the input contact is gers the timer each time it
releases and a new time is closed before the end of closed again. If it is closed detects an object on the
period starts.
the delay time, the relay before the end of the delay belt, so the relay keeps ON
keeps ON and a new time time the relay keeps ON, a as long as there is no gap
period starts.
new time period begins as on the belt. As soon as there
soon as the contact is is a gap on the belt, the
Function Oa: Delay on
operate, automatic and
manual start
opened again.
relay switches OFF and an
alarm can be activated.
Function Nr: Interval with
no time reset, manual start
The time period begins as
Example1:
Delay
with
on
soon as the power supply is The relay operates and the operate
remote Yellow LED working mode
connected.
At the end of the set delay as the trigger contact is
time the relay operates and closed. The relay releases at Using the delay on operate
doesn't release until the trig- the end of this period or function, DMC01D or Relay ON:
ger contact is closed or the when the power supply is PMC01C can be used to set See operation diagrams
power supply is disconnect- disconnected. The relay the working delay of an Incorrect knobs position:
time period begins as soon control time setting:
Timing:
Slow blinking
ed. When the trigger contact operates again when the equipment (i.e. a pump) by a
is closed, the relay releases trigger contact is closed knob placed on a panel. It is
Fast blinking
and
starts.
a
new time period again.
only necessary to connect
an external potentiometer to
the suitable pins (T1, T2, T3
for DMC01D or 8. 9. 11 for
PMC01C) and mount the
knob on the control panel.
Function Na: Interval with
Function
manual start
In:
Interval, no time reset, automatic
and manual start
The relay operates and the The relay operates and the
time period begins as soon time period begins as soon Note:
as the trigger contact is as the power supply is con-
closed. The relay releases at nected.
The external potentiometer
the end of this period or The relay releases at the end must be connected before
when the power supply is of this period or when the the product operates. The
disconnected. The relay power supply is disconnect- cable length must be below
operates again when the ed. The relay operates again 3 m
trigger contact is closed when the trigger contact is
again. If the trigger contact closed.
is closed before the end of
the delay time, the relay
keeps ON and a new time
period starts.
Specifications are subject to change without notice (18.06.07)
3
DMC01, PMC01
Operation Diagrams
Function Op - Delay on operate, manual start
Function Oa - Delay on operate, automatic and manual start
Power supply
Power supply
Trigger input
Trigger input
ON
ON
Relay 1 ON
Relay 1 ON
OFF
ON
OFF
Relay 2 ON ON
(delayed)
Relay 2 ON
(delayed)
OFF
ON
OFF
ON
Relay 2 ON
(instant.)
Relay 2 ON
(instant.)
OFF
OFF
LED
LED
Function In - Interval, manual start
Power supply
Function Ia - Interval, automatic and manual start
Power supply
Trigger input
Trigger input
ON
ON
Relay 1 ON
Relay 1 ON
OFF
ON
OFF
ON
Relay 2 ON
(delayed)
Relay 2 ON
(delayed)
OFF
ON
OFF
ON
Relay 2 ON
(instant.)
Relay 2 ON
(instant.)
OFF
OFF
LED
LED
Function Nr - Interval with no time reset, manual start
Power supply
Function Na - Interval with no time reset, automatic and manual start
Power supply
Trigger input
Trigger input
ON
Relay 1 ON
ON
Relay 1 ON
OFF
OFF
Relay 2 ON
(delayed)
Relay 2 ON
(delayed)
ON
ON
OFF
OFF
Relay 2 ON
(instant.)
Relay 2 ON
ON
ON
(instant.)
OFF
OFF
LED
LED
Function Dr - Delay on release
Power supply
Trigger input
ON
Relay 1 ON
OFF
Relay 2 ON
(delayed)
ON
OFF
Relay 2 ON
(instant.)
ON
OFF
LED
4
Specifications are subject to change without notice (18.06.07)
DMC01, PMC01
Wiring Diagrams
DMC01C - Contact input
PMC01C - Contact input
DMC01C - Open collector input
DMC01D - PNP / NPN sensor input
DMC01D - Namur sensor input
PMC01C - Open collector input
PMC01D - PNP / NPN sensor input
PMC01D - Namur sensor input
Specifications are subject to change without notice (18.06.07)
5
DMC01, PMC01
Dimensions
DIN-rail
DIN-rail
22.5
99.5
45
99.5
28.5
28.5
Plug-in
94
90
36
28.5
6
Specifications are subject to change without notice (18.06.07)