EM111-DINAV81XO1PFA70 [CARLOGAVAZZI]

Energy Management Energy Analyzer Type EM111;
EM111-DINAV81XO1PFA70
型号: EM111-DINAV81XO1PFA70
厂家: Carlo Gavazzi    Carlo Gavazzi
描述:

Energy Management Energy Analyzer Type EM111

文件: 总12页 (文件大小:437K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Energy Management  
Energy Analyzer  
Type EM111  
• Single phase energy analyzer  
• Class 1 (kWh) according to EN62053-21  
• Class B (kWh) according to EN50470-3  
• Accuracy ±0.5% RDG (current/voltage)  
• Current measurement via CT up to 300 A (AV5)  
• Rated primary current: 32 A (AV7, AV8)  
• Max primary current: 45 A (AV7, AV8)  
• Max cable cross section: 6 mm2  
• Backlit LCD display with integrated touch key-pad  
• Energy readout on display: 7 digit  
• Variable readout on display: 4 digit  
• Energy measurement: kWh and kvarh (imported/exported);  
kWh+ by 2 tariffs  
• System variables, kW, kvar, V, A, PF, Hz, kWdmd, kWdmd peak  
• Self power supply  
• Dimensions: 1-DIN module  
• Protection degree (front): IP51  
• Pulse output (optional, by open collector PNP)  
• RS485 Modbus port (optional)  
• M-Bus port (optional)  
Digital input (for tariff management)  
• Easy connection or wrong current direction detection  
• Compliant with the international accuracy standard IEC/  
EN62053-21, and the IEC/EN61557-12 performance  
requirements (active power and active energy).  
Certified according to MID Directive (option PF only): see  
“how to order” below  
Product description  
Single-phase  
energy applications up to 32 A (direct programmed to consider only to the active energy being  
analyzer with backlit LCD connection) or up to 300 A the imported one. Housing for measured, RS485 Modbus  
display with integrated touch (CT connection), with dual DIN-rail mounting, with IP51 port or M-Bus port.  
keypad. Particularly indicated tariff management availability. front degree protection. The  
for active energy metering It can measure imported meter is optionally provided  
and for cost allocation in and exported energy or be with pulse output proportional  
How to order  
Model  
Range code  
System  
EM111-DIN AV8 1 X O1 PF B  
Certified according to MID Directive, Module B  
and Module D of Annex II, for legal metrology  
relevant to active electrical energy meters (see Annex V,  
MI003, of MID). Can be used for fiscal (legal) metrology.  
MID  
Power supply  
Output  
Option  
Measurement  
Type Selection  
Range code  
System  
Power supply  
Output  
AV8: 230VLN AC - 5(45)A  
(Direct connection up  
to 32 A)  
1:  
1-phase 2-wire  
X:  
Self power supply  
O1: pulse output  
S1:  
RS485 Modbus port  
M1: M-Bus port  
Option  
Measurement  
PF:  
Certified according to  
MID Directive. Can  
be used for fiscal  
(legal) metrology.  
A:  
The power is always integrated (both in case of positive imported and negative  
exported power) and the total energy meter is certified according to MID. Operating  
temperature: from –25 to +55°C/from –13 to +131°F  
B:  
Only the total positive energy meter is certified according to MID. Operating  
temperature: from –25 to +55°C/from –13 to +131°F  
A70: The power is always integrated (both in case of positive imported and negative  
exported power) and the total energy meter is certified according to MID. Operating  
temperature: from –25 to +70°C/from –13 to +158°F  
B70: Only the total positive energy meter is certified according to MID. Operating  
temperature: from –25 to +70°C/from –13 to +158°F  
Specification are subject to change without notice EM111 DS 020221  
1
EM111  
How to order  
Model  
EM111-DIN AV8 1 X O1 X  
STANDARD  
Range code  
System  
Power supply  
Output  
Not certified according to MID Directive. Cannot be used  
for fiscal (legal) metrology.  
Option  
Type Selection  
Range code  
System  
1: 1-phase 2-wire  
Power supply  
Output  
AV8: 230VLN ac - 5(45)A  
(Direct connection up  
to 32 A)  
X:  
Self power supply  
O1: pulse output  
S1:  
RS485 Modbus port  
M1: M-Bus port  
AV7: 120VLN ac - 5(45)  
A (Direct connection  
up to 32 A). Available  
on request (MOQ 100  
pcs)  
AV5: 230VLN ac - 5(6)A  
(CT connection), S1  
output only  
Option  
X:  
none  
Specification are subject to change without notice EM111 DS 020221  
2
EM111  
Input specifications  
Rated Inputs  
Current type  
AV7, AV8  
PF  
0.001  
0.001 kWh or kvarh  
0.001 kWh or kvarh  
Energies (positive)  
Energies (negative)  
Energy additional errors  
Influence quantities  
Temperature drift  
Sampling rate  
1-phase loads, direct  
connection up to 32 A  
1-phase loads, CT  
connection (5A)  
Note: max CT ratio = 60  
(300 A)  
AV5  
According to EN62053-21  
≤200ppm/°C  
4096 samples/s @ 50Hz  
4096 samples/s @ 60Hz  
Nominal current range  
AV7, AV8  
Display and touch key-pad  
Type  
5(45)A, Ib 5 A, Imax 45 A,  
Imin 0.25 A  
5 (6) A, In 5A, Imax 6 A,  
Imin 0.25  
Backlit LCD, 7-digit, h 6  
mm  
Energy: 7 digit. Variables: 4  
digit  
2 (Enter/DOWN and UP).  
Max. 9 999 999  
Min. 0.00  
AV5  
Read-out  
Nominal voltage  
AV5, AV8  
AV7  
Touch key  
Max. and Min. indication  
230 VLN -30% +20 %  
120 VLN -20% +20%  
EM111 with direct  
Note  
Memory energy storage  
connection (AV7, AV8) can  
be used up to 45 A if a 6  
mm2 section wire complies  
with local regulations and/  
or installation needs.  
Energy  
10^10 cycles. Energy value  
is saved every time the less  
significant digit increases.  
10^10 cycles. When a  
parameter is modified, only  
the relevant memory cell is  
overwritten  
Programming parameters  
Accuracy  
(@25°C ±5°C, R.H. ≤60%,  
45 to 65 Hz)  
Energies  
LEDs  
Flashing red light pulses  
according to EN50470-3,  
EN62052-11  
1000 pulses/kWh (min.  
period: 90ms, max.  
frequency: 11 Hz)  
Depending on CT ratio:  
CT ≤ 25: 1000 pulse/kWh  
25 < CT < 60: 100 pulses/kWh  
Fix orange light: wrong  
current direction only with  
PFB option or with “B”  
measurement selection in  
case of X option  
Active energy  
Class 1 according to  
EN62053-21  
Class B (kWh) according to  
EN50470-3 (AV8 only)  
Class 2 according to  
EN62053-23  
Pulse weight  
AV7, AV8  
AV5  
Reactive energy  
Start-up current  
AV7, AV8  
AV5  
20 mA, positive or negative  
10 mA, positive or negative  
Self-consumption is not  
measured.  
Note  
Start-up voltage  
AV5, AV8  
161 VLN  
96 VLN  
Display  
0.1 A  
0.1 V  
0.01 kW or kVar  
0.1 Hz  
Current overloads  
Continuous  
AV7  
AV7, AV8  
AV5  
AV7, AV8  
AV5  
45 A  
6 A  
1350 A  
120 A  
Resolution  
Current  
Voltage  
Power  
Frequency  
PF  
For 10ms  
Voltage Overloads  
Continuous  
For 500ms  
1.2 Un  
2 Un  
0.01  
Energies (positive)  
Energies (negative)  
0.01 kWh or kvarh  
0.01 kWh or kvarh  
Serial communication  
0.001 A  
0.1 V  
0.1 kW or kvar  
0.1Hz  
Input impedance  
Voltage input  
Current input  
2.8 Mohm  
< 0.5 VA  
Current  
Voltage  
Power  
Frequency  
Specification are subject to change without notice EM111 DS 020221  
3
EM111  
Digital input specifications  
Digital inputs  
Free of voltage contact  
Overload  
In case a voltage is  
Function  
Tariff management (switch  
between t1-t2)  
1
erroneously applied to the  
digital input, the input is not  
damaged up to 30 V ac/dc.  
Number of inputs  
Contact measurement voltage 5 V  
Input impedance  
1kohm  
Contact resistance  
≤ 1kohm, close contact  
≥ 100kohm, open contact  
Output specifications  
RS485 serial port  
RS485 by screw  
connection.  
Other  
Available functions: wild  
card, header, initialisation  
SND_NKE, and req_udr  
management. Management  
of primary address  
modification via M-Bus.  
VIF, VIFE, DIF and DIFE:  
see protocol  
Function  
For communication  
of measured data,  
programming parameters  
Modbus RTU (slave  
function)  
9.6, 19.2, 38.4, 57.6, 115.2  
kbaud, even or no parity,  
1 to 247 (default: 1)  
Protocol  
Baud rate  
Note  
not available with AV5  
range code  
Address  
Driver input capability  
1/8 unit load. Maximum 247 Static output  
transceivers on the same  
bus.  
1 s  
Purpose  
For pulse output  
proportional to the active  
energy (kWh)  
Data refresh time  
Read command  
50 words available in 1  
read command  
M-Bus by screw  
connection.  
For communication of  
measured data  
M-Bus according to  
EN13757-3  
Pulse rate  
Selectable in multiple of  
100  
Max 1000 or 3000 pulses/  
kWh according to pulse ON  
duration  
Selectable: 30ms or 100 ms  
according to EN62052-31  
open collector PNP  
VON 1 VDC max. 100mA  
VOFF 80 VDC max.  
not available with AV5  
range code  
M-Bus port  
Function  
Pulse ON duration  
Protocol  
Output type  
Load  
Baud rate  
Meters in the M-Bus network 250  
Primary address  
Secondary address  
0.3, 2.4, 9.6 kbaud  
Selectable  
Univocally defined in each  
unit  
Note  
Secondary address  
from 50000000 to  
69999999  
Specification are subject to change without notice EM111 DS 020221  
4
EM111  
General specifications  
Operating temperature  
Metrology  
EN62053-21, EN50470-3  
(PF option only)  
IEC/EN61557-12 (active  
power and active energy,  
MID models only)  
PF option (standard or with  
suffixes from 01 to 60)  
From –25 to +55°C/from  
–13 to +131°F  
PF option  
Approvals  
CE, MID (PF option only),  
cULus (AV7 option only)  
(with suffixes from 61 to 99)  
From –25 to +70°C/from  
–13 to +158°F  
Connections  
Cable cross-section area  
Measuring inputs: max. 6  
mm2 with/without metallic  
cable ferrule; Max. screw  
tightening torque: 1.1 Nm  
1.5 mm², Min./Max. screws  
tightening torque: 0.4 Nm  
X option  
From –25 to +65°C/from  
–13 to +149°F indoor,  
(R.H. from 0 to 90%  
noncondensing @ 40°C)  
Other terminals  
Storage temperature  
-30°C to +80°C (R.H. <  
90% noncondensing @  
40°C)  
Housing  
Dimensions (WxDxH)  
Material  
17,5 x 63 x 91,5 mm  
PBT, self-extinguishing: UL  
94 V-0  
Overvoltage category  
Cat. III  
Insulation (for 1 minute)  
4000 VAC RMS between  
measuring inputs and  
digital/serial output (see  
table) 4000 VAC RMS  
Sealing covers  
Included  
Mounting  
DIN-rail  
Protection degree  
Front  
Dielectric strength  
4000 VAC RMS for 1  
minute  
IP51  
Screw terminals (cable inputs) IP20  
EMC  
According to EN62052-11  
EN62052-11  
Weight  
Approx. 80 g (packing  
Standard compliance  
Safety  
included)  
Power supply specifications  
Power supply  
self power supply  
Power consumption  
≤ 1.0W, ≤ 8VA  
Specification are subject to change without notice EM111 DS 020221  
5
EM111  
Insulation (for 1 minute) between inputs and outputs  
Measuring input  
Digital or serial output  
Digital input  
Measuring input  
Digital or serial output  
Digital input  
-
4 kV  
4 kV  
4 kV  
4 kV  
-
-
-
-
AV5 model  
CT input  
Voltage input  
Serial output  
4 kV  
2 kV  
-
Voltage input  
4 kV  
MID compliance (PF option only)  
Accuracy  
0.9 Un ≤ U ≤ 1.1 Un; 0.98 fn ≤ f ≤ 1.02 fn; fn: 50 Hz;  
cosj: 0.5 inductive to 0.8 capacitive.  
Class B  
Considering listed Ib or In values  
Operating temperature PF option (standard or with suffixes from 01 to 60): from –25 to +55°C/from –13 to +131°F  
PF option (with suffixes from 61 to 99): from –25 to +70°C/from –13 to +158°F  
X option: from –25 to +65°C/from –13 to +149°F indoor (R.H. from 0 to 90% non-condensing @  
40°C)  
EMC compliance  
E2  
Mechanical compliance M2  
Accuracy (according to EN62053-21 and EN62053-23) - AV5 model  
kWh, accuracy (RDG) depending on the current  
kvarh, accuracy (RDG) depending on the current  
Percentage error limits for class index B  
Error  
+1.5%  
+1%  
+2.5%  
+2%  
0%  
0%  
-1%  
-2%  
-1.5%  
-2.5%  
PF=1 0.25A(Imin) 0.5A(Itr) 5A(In)  
(0.05Iref) (0,1I )  
PF=L0.5  
6A(Imax  
6A(Imax  
)
)
sinj =1 0.25A  
(0.05In)  
0.5A  
(0.1In)  
1A  
5A(In)  
5A(In)  
6A(Imax  
6A(Imax  
)
)
0.5Ar(eIftr) 5A(In)  
(0,1Iref)  
sinj=0.5 0.5A  
(0.1In)  
(0.25In)  
or C0.8  
Class 1 accuracy limits (Active energy)  
Class 2 accuracy limits (Reactive energy)  
5(6)A Start-up current: 10mA  
5(6)A Start-up current: 10mA  
Specification are subject to change without notice EM111 DS 020221  
6
EM111  
Accuracy (according to EN50470-3 and EN62053-23) - AV7/AV8 model  
kWh, accuracy (RDG) depending on the current  
kvarh, accuracy (RDG) depending on the current  
Percentage error limits for class index B  
Error  
+1.5%  
+1%  
+2.5%  
+2%  
0%  
0%  
-1%  
-2%  
-1.5%  
-2.5%  
PF=1 0.25A(Imin) 0.5A(Itr) 5A(In)  
0.05A(Iref) (0,1I )  
PF=L0.5  
45A(Imax  
45A(Imax  
)
)
sinj =1 0.25A  
(0.05Ib)  
0.5A  
(0.1Ib)  
1A  
5A(Ib)  
5A(Ib)  
45A(Imax  
45A(Imax  
)
)
0.5Ar(eIftr) 5A(In)  
(0,1Iref)  
sinj=0.5 0.5A  
(0.1Ib)  
(0.25Ib)  
or C0.8  
Class 1 accuracy limits (Active energy)  
Class 2 accuracy limits (Reactive energy)  
5(45)A Start-up current: 20mA  
5(45)A Start-up current: 20mA  
Measurement accuracy according to IEC/EN61557-12 (MID versions)  
Active power  
Performance class 1  
Active energy  
Performance class 2  
Display pages  
No  
Variable  
“Full” mode  
“Easy” mode  
Note  
0
kWh+ (imported)  
X
X
In PF version (MID) this is the only certified energy meter.  
In PFA version and in X version with Measurement menu set to “A”,  
this is considering the total energy without considering the current  
direction.  
1
2
3
4
5
6
7
kWh- (exported)  
X
X
X
X
X
X
X
X
X
X
X
In PFB version and in X version with Measurement menu set to “B”  
kW  
V
A
PF  
Hz  
kvarh+ (imported)  
In PFA version and in X version with Measurement menu set to  
“A”, this is considering the total positive reactive energy without  
considering the current direction.  
8
kvarh- (exported)  
kvar  
X
X
X
In PFB version and in X version with Measurement menu set to “B”  
9
10  
kW dmd  
11  
12  
13  
kW dmd peak  
kWh (t1)  
X
X
X
X
X
Only relevant to kWh+, with Tariff menu set to ON  
Only relevant to kWh+, with Tariff menu set to ON  
kWh (t2)  
X= available  
Specification are subject to change without notice EM111 DS 020221  
7
EM111  
List of available menus  
Menu name and description  
Range  
Default setting  
PASS  
Password request  
New password  
From 0000 to 9999  
From 0000 to 9999  
From 1 to 60  
A; b  
0000  
0000  
1
nPASS  
Ct RatIo (AV5)  
MEASurE  
Current transformer ratio  
Measurement type (A=easy connection;  
A
B=bidirectional, imported and exported energy).  
Not available in PFA and PFB versions (MID)  
P int  
Integration time for Wdmd calculation  
1 to 30 min  
Full or Easy  
1
Mode  
Selection of complete or simplified set of variables on  
display  
Full  
Tariff  
Tariff enabling  
Yes/No  
No  
PULSE (O1 option)  
Selection of pulse ON duration  
30 or 100 ms  
30  
Selection of the pulse weight (multiplies of 100 pulses/ 100 to 1000 (if duration  
1000  
kWh)  
is 100ms) 100 to 3000 (if  
30 ms)  
Address (S1 option) Modbus serial address  
1 to 247  
01  
Baud (S1)  
Parity (S1)  
Modbus baud rate  
9.6; 19.2; 38.4; 57.6,  
115.2 kbps  
9.6  
Modbus parity  
No/even  
1 to 250  
No  
0
PrI Add  
M-Bus primary address  
(M1 option)  
Baud (M1)  
RESEt  
M-Bus baud rate  
0.3; 2.4; 9.6 kbps  
2.4  
No  
Allow the reset of tariff meters and W dmd peak (kWh/ Yes/No  
kvarh partial meter reset available only via serial  
communication)  
End  
Exit to measuring mode  
Note: after the confirmation of a new parameter value, the value is stored in the memory without the need to exit the  
programming mode.  
Specification are subject to change without notice EM111 DS 020221  
8
EM111  
Additional available information on the display (*)  
Type  
Page  
Description  
Info page 1  
Info page 2  
YEAr (2013)  
Year of production  
SErIAL (dddnnnA)  
Serial number (ddd= day of the year; nnn=progressive  
number; A= production line, internal use only)  
Info page 3  
Info page 4  
Info page 5  
Info page 6  
Info page 7  
Info page 8  
Info page 9 (O1)  
rEV (A.01)  
Ct RatIo  
MEASurE  
P int  
Firmware revision  
Current transformer ratio  
Measurement type  
Integration time for Wdmd calculation  
Set of variables on display  
Tariff enabling  
ModE  
tArIFF  
PULSE  
Pulse ON duration  
Pulse weight  
Info page 9 (S1)  
Info page 10 (S1)  
Info page 11 (S1)  
Info page 9 (M1)  
Info page 10 (M1)  
Info page 12  
AddrESS  
bAud  
Modbus serial address  
Modbus baud rate  
Modbus parity  
PArItY  
PrI Add  
bAud  
M-Bus primary address  
M-Bus baud rate  
ChECkSuM  
FW checksum  
(*) can be reached by pressing simultaneously the 2 touch keys  
Specification are subject to change without notice EM111 DS 020221  
9
EM111  
AV7, AV8 wiring diagrams  
1-ph, 2-wire  
1-ph, 2-wire (F 315mA)  
Fig.2  
Fig.1  
AV5 wiring diagrams  
Fig.3  
1-ph, 2-wire  
L
N
1
2
L
1-CT connection  
Specification are subject to change without notice EM111 DS 020221  
10  
EM111  
Input/output communication  
Open collectors output  
Digital Input  
Fig.4  
Fig.5  
Vdc Out GND  
Vdc GND Out  
The load resistance (Rc) must be designed so that the closed con-  
tact current is under 100 mA (Von is equal to 1 V dc). DC voltage (Voff)  
must be less than or equal to 80 V.  
RS485 Modbus communication port  
M-Bus communication port  
Fig.6  
Fig.7  
Additional instruments with RS485 are connected in parallel. The  
serial output must only be terminated on the last network device  
connecting terminals A- and T. For connections longer than 1000 m  
use a signal repeater. Maximum 247 transceivers on the same bus.  
Specification are subject to change without notice EM111 DS 020221  
11  
EM111  
Front panel description  
5
4
1. Display  
Backlit LCD display with touch key-pad.  
Upper part: enter  
1
2. LED  
LED proportional to kWh reading  
3
2
3. Serial number and MID data  
Area reserved to serial number and MID-relevant data in  
PF versions  
Dimensions (mm)  
43  
175  
28  
3
5
49  
60  
Specification are subject to change without notice EM111 DS 020221  
12  

相关型号:

EM111-DINAV81XO1PFB

Energy Management Energy Analyzer Type EM111
CARLOGAVAZZI

EM111-DINAV81XO1PFB70

Energy Management Energy Analyzer Type EM111
CARLOGAVAZZI

EM111-DINAV81XS1PFA

Energy Management Energy Analyzer Type EM111
CARLOGAVAZZI

EM111-DINAV81XS1PFA70

Energy Management Energy Analyzer Type EM111
CARLOGAVAZZI

EM111-DINAV81XS1PFB

Energy Management Energy Analyzer Type EM111
CARLOGAVAZZI

EM111-DINAV81XS1PFB70

Energy Management Energy Analyzer Type EM111
CARLOGAVAZZI

EM11513200J0G

Barrier Strip Terminal Block
AMPHENOL

EM11516200J0G

Barrier Strip Terminal Block
AMPHENOL

EM11519000J0G

Barrier Strip Terminal Block
AMPHENOL

EM11519200J0G

Barrier Strip Terminal Block
AMPHENOL

EM11714200J0G

Barrier Strip Terminal Block
AMPHENOL

EM11715200J0G

Barrier Strip Terminal Block,
AMPHENOL