Panel Meters and Controllers
Autoranging Frequency Meter
Type LDI3 F1K
• 3-dgt µP-based frequency indicator
• 1.0 to 999 Hz
• Autoranging capability
• Degree of protection (front): IP 50 (IP 65 on request)
Product Description
Ordering Key
Model
Range code
Power supply
Setpoints
LDI3F1KD0XXXX
3-dgt µP-based meter for fre-
quency measurements with
autoranging capability. Ensures
a degree of protection (front) of
IP 50 (IP 65 on request).
Engineering unit
Option
Supply Specifications
Type Selection
AC supply
230 VAC, -15% +10%,
Power supply
Options
50/60 Hz (standard)
24 VAC, 48 VAC, 115 VAC,
-15% +10%, 50/60 Hz
(on request)
A:
B:
C:
D:
24 VAC, -15% +10%,
50/60 Hz
48 VAC, -15% +10%,
50/60 Hz
115 VAC, -15% +10%,
50/60 Hz
230 VAC, -15% +10%,
50/60 Hz (standard)
XX:
IX:
None (standard)
Degree of protection
IP 65
1)
1)
Power consumption
3.2 VA
XT:
Tropicalization
1)
1)
Power supply on request
General Specifications
Input Specifications
Rated input
500 VAC,
1 to 1000 Hz autoranging
Operating temperature
0 to 50°C (32 to 122°F)
(R.H. < 90% non-condensing)
Overload protection
Continous
For 1s
Storage temperature
-10 to 60°C (14 to 140°F)
(R.H. < 90% non-condensing)
1.2 x rated input
2 x rated input
Insulation reference voltage
Dielectric strength
Noise rejection
CMRR
300 Vrms to ground
Accuracy
(@ 25°C 5°C, R.H. ≤ 60%)
4000 Vrms for 1 m inute
0.1% f.s., 1 dgt
Temperature drift
Display
100 ppm/ºC
100 dB, 40 Hz to 60 Hz.
7-segment LED, h 14.2 mm,
3 digits
EMC
IEC 60801-2, IEC 60801-3,
IEC 60801-4 (level 2),
Sampling rate
1 time/s
EN 50 081-1, EN 50 082-1
Indication
Max:
Min:
Safety standards
Connector
Housing
Dimensions
Material
EN 61 010-1, IEC 61010-1,
VDE 0411
999
0.00
EEE
Screw-type
Over range:
Input voltage
Input impedance
9 to 500 VAC,
1/8 DIN, 48 x 96 x 83 mm
ABS,
self-extinguishing: UL 94 V-0
500 KΩ
Degree of protection
Front: IP 50 (standard),
IP 65 (on request)
Weight
Approvals
Approx 250 g
CE, CSA
Specifications are subject to change without notice
1
LDI3 F1K
Range Table
Terminal Board
Measurement
Dec. point Resolution
position
1.00 to 9.99 Hz
10.0 to 99.9 Hz
100 to 999 Hz
9.99
99.9
999
0.01 Hz
0.1 Hz
1 Hz
(Automatic selection)
Front Panel Description
2. Engineering unit
1
Screen for interchangeable unit label.The symbols in the
shaded areas are those available on the set of engineering
unit labels supplied with the LDI3 (engineering unit label to
be inserted by customer).
W = 08
kW = 09
MW = 10
var = 11
kvar = 12
Mvar = 13
Ω = 14
MΩ = 16
Hz = 17
% = 24 mm HG = 32
cm = 40
m = 41
mV = 01
V = 02
mbar = 25
bar = 26
l/min = 33
l/h = 34
kHz = 18
RPM = 19
m/s = 20
m/min = 21
kg = 42
kV = 03
µA = 04
mA = 05
A = 06
psi = 27 kg/min = 35
ata = 28 ton/h = 36
ate = 29 m3/min = 37
ppm = 43
kA = 44
2
cos φ = 45
m3 = 46
µs = 47
°C = 22 kg/cm2 = 30
m3/h = 38
1. Display
mW = 07
kΩ = 15
°F = 23 mm H2O = 31
mm = 39
3-dgt (maximum read-out 999).
Alphanumeric indication by means of 7-segment display
for:
- Displaying of the measured value, over-range.
Dimensions
F
S
83 mm
max. 10
96 mm
mm
92 mm
75 mm
2
Specifications are subject to change without notice