ROG4K [CARLOGAVAZZI]
EM210 energy analyzer current sensor (20-4000 A);型号: | ROG4K |
厂家: | Carlo Gavazzi |
描述: | EM210 energy analyzer current sensor (20-4000 A) |
文件: | 总5页 (文件大小:730K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
ROG4K
EM210 energy analyzer current sensor (20-4000 A)
Benefits
• Adaptability and flexibility. Effective for a wide range
of currents and available in three different lengths, it can
be installed in existent applications and/or with reduced
space, on single cables, on cable bundles or high
capacity busbars.
• Accuracy. The lack of a ferromagnetic core improves
measurement accuracy in a wide range of currents and
eliminates possible interferences.
• Simplified system. The current calculation integrator is
included in the EM210 analyzer, thus neither additional
wiring nor space are required; the sensor is directly
connected to the analyzer.
• Fast installation. The opening/closing mechanism
makes installation fast even in existent applications. The
analyzer only requires two cables to be connected per
sensor and the installation is made easy by the color
(black, orange, blue) on the connection cable.
Description
Current sensor based on the Rogowski principle,
to be used in combination with the EM210 analyzer
(versions EM210 72D MV5 and EM210 72D MV6)
to measure current in single-phase, two-phase
and three-phase systems.
Compact, flexible and lightweight, it is suited to
all applications and can be installed in all types of
switchboards.
Supplied in a kit made up of three different colored
pieces to make phase identification easy, it comes
with coils with three different diameters and lengths
and measures a wide current interval (from 20 to
4000 A).
Operating principle
The Rogowski sensor is an alternating current measurement device.
Unlike current sensors with ferromagnetic core, the linearity of the Rogowski sensor makes it specifically
indicated to measure high currents.
Its operating principle is very simple: a voltage signal dependent on the primary current trend, which can be
reconstructed using an integration process, is generated at the ends of the coil positioned around a conductor.
Unlike traditional Rogowski sensors, ROG4K does not require an external integrator with additional power
supply since measurement is entirely controlled by the analyzer.
Applications
Indicated for retail and industrial solutions, especially for retrofitting and/or contexts with reduced available
space where installing a current sensor with ferromagnetic core is difficult.
It is especially indicated to measure:
• industrial or building system load
• single machine load with high current absorption
02/05/2018 ROG4K DS ENG
Carlo Gavazzi Controls S.p.A.
1
ROG4K
Structure
C
A
D
B
Area
A
B
C
D
Description
Analyzer connection cable
Coil opening/closing mechanism
Colored sensor identification
Coil
02/05/2018 ROG4K DS ENG
Carlo Gavazzi Controls S.p.A.
2
ROG4K
Features
General
Coil and EM210 connection cable: thermoplastic rubber, self-extinguishing degree V-0 (UL
94)
Material
Opening/closing mechanism: PA6, self-extinguishing V-0 (UL 94)
Protection degree
IP52
Type: 1000 V (UL Style 20940)
External diameter: 5 mm
EM210 connection cable Cables: 2, section 0.1288 mm2 (26 AWG)
Length: 2 m (customizable up to 50 m, upon request subject to minimum quantities)
Cat. III1000 V @50/60 Hz
Cat. IV600 V @50/60 Hz
Overvoltage category
Pollution degree
Insulation
2
double electrical insulation
Cable
Busbar
Mounting
Dimensions (mm) and weight
External coil diam- Maximum conduc-
Code key
Coil length (mm)
Coil thickness (mm)
Weight (g)
eter (mm)
tor diameter (mm)
ROG4K1002M4003X 400
ROG4K1002M6003X 600
ROG4K1002M9003X 900
12
12
12
139
203
299
115
179
275
130
160
200
Environmental specifications
Operating temperature
Storage temperature
Maximum altitude
From -20 to +70 °C/from -4 to +158 °F
From -20 to +70 °C/from -4 to +158 °F
2000 m
NOTE: R.H. < 85 % non-condensing.
Conformity
Directives
Standards
2014/35/EU (LVT - Low Voltage)
EN61010-1
Approvals
02/05/2018 ROG4K DS ENG
Carlo Gavazzi Controls S.p.A.
3
ROG4K
Electrical specifications
Primary current
From 20 to 4000 A
Output signal
100 mV/kA @50 Hz
Operating frequency
Accuracy
From 45 to 65 Hz
±1%
Linearity
±0.2%
±2% (primary conductor near the opening/closing mechanism)
±0.5% maximum
Position sensitivity
External field influence
Temperature drift
Internal resistance
Dielectric strength
±0.07% per °C
30 Ω/400 mm
7.4 kV ac for 1 minute (connection cable wires and coil)
Connection Diagrams
Fig. 1 Current connection
Fig. 2 Connection with EM210, K=white, L=brown
02/05/2018 ROG4K DS ENG
Carlo Gavazzi Controls S.p.A.
4
ROG4K
References
Order code
ROG4K 100 2M
3X
Enter the code, replacing the symbol
with the coil length (3 digits). Lengths available: 400, 600, 900 mm.
Note: different cable lengths and kits with single coil available upon request (subject to minimum order
quantities).
Further reading
Information
Document
Where to find it
Instruction manual
Analyzer Datasheet
Instruction manual - ROG4K
EM210 Datasheet
www.productselection.net
www.productselection.net
Analyzer installation and use instruc-
tions
EM210 installation and use instructions www.productselection.net
CARLO GAVAZZI compatible components
Purpose
Component name/code key
Notes
1 pulse output, see relevant
datasheet
EM21072DMV53XOXX
EM21072DMV53XOSX
EM21072DMV63XOXX
EM21072DMV63XOSX
Measure and view connected load consumption
(230 V L-N, 400 V L-L ca)
1 pulse output, 1 RS485 port, see
relevant datasheet
1 pulse output, see relevant
datasheet
1 pulse output, 1 RS485 port, see
relevant datasheet
Measure and view connected load consumption
(120 V L-N, 230 V L-L ca)
COPYRIGHT ©2017
Content subject to change. Download the PDF: www.productselection.net
02/05/2018 ROG4K DS ENG
Carlo Gavazzi Controls S.p.A.
5
相关型号:
ROK-186MH+
Double Balanced Mixer, 5MHz Min, 2500MHz Max, 9.5dB Conversion Loss-Max, ROHS COMPLIANT, CASE QQ96, 12 PIN
MINI
ROK-2500LH+
Double Balanced Mixer, 1MHz Min, 2500MHz Max, 9dB Conversion Loss-Max, CASE PP230, 4 PIN