SPUBAT12 [CARLOGAVAZZI]
Smart Power Supply and UPS Type SPUBC 24V 5A;型号: | SPUBAT12 |
厂家: | Carlo Gavazzi |
描述: | Smart Power Supply and UPS Type SPUBC 24V 5A |
文件: | 总4页 (文件大小:537K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Smart Power Supply and UPS
Type SPUBC 24V 5A
• Single phase input 115Vac / 230Vac / 277Vac
• Smart power management
• Rated output 5A with permanent 10A overboost
• Max battery charging current 5A
• Suitable for Lead Acid open or sealed, Lead gel
• Automatic Battery diagnostic and battery care
• Boost, Trikle/float and recovery charging cycles.
• Battery reversed polarity, element short circuit or
disconnection
• 2 relay outputs for remote status and operation
indication
• cURus recognized and CE approved
Product Description
The new Carlo Gavazzi regardless of the setting.
battery faults such as battery
By means of built in jumpers
it is possible to set preset
curves.
They are programmed for
two charging levels, boost
and float/trikle, but can be
changed to single charging
level by the user.
In addition to the SPUBC,
Carlo Gavazzi, also provides
a selection of Racks for DIN
rail mounting of the battery,
with battery included upon
request from 1.2Ah up to
12Ah capable of providing,
depending upon load, from a
few minutes to several hours
of charge reserve.
SPUBC puts you in the On the SPUBC24120 the sulphatation, elements in
driving seat of your power rated output current is short circuit, accidental
management requirements, 5A, although, after the reverse polarity connection
allocating power, in the most battery is charged, the and battery disconnection
efficient way, between the power supply can provide or bad connection. All these
load and the battery.The 10A. SPUBC implements can be easily detected and
maximum available current
for battery charging is set by called
a
comprehensive process removed during installation
“Battery Care” and operation by the
means of a front trimmer. It that applies algorithms to “diagnostic LED” Blinking
can go from 20% to 100%, obtain rapid and automatic Code. Continuous battery
which means that it possible charging, battery charge efficiency
monitoring,
to charge with up to 5A. The optimization over time, reduces battery damage risk
priority though is always the flat battery recovery and and allows safe operation in
load. If the load requires real time diagnostic during permanent connection.
80% of current, the current installation and operation. This device is suitable for a
available for the battery is The
Real
Time
auto- selection of most common
only the remaining 20% diagnostic system, monitors battery types.
Approvals
Ordering Key
SPUBC 24 120
Power supply UPS battery charger
Battery and Output Voltage Vdc
Output power W
Output Data
Power dissipation @ Max. Load 17W
Output voltage
Nominal current
Rated output current
Efficiency
24Vdc
5A
5A
Short circuit protection
Over load protection
Overvoltage output protection
Thermal protection
Yes
Yes
Yes (typ. 35Vdc)
Yes
(@50% of rated current)
≥90%
Turn on delay
1S (Max)
Max Capacitive load startup Unlimited
1
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 17/06/2015
Smart Power Supply and UPS
Type SPUBC 24V 5A
Input Data
Nominal input voltage
Voltage range
115 ~ 230 ~ 277Vac
90 ÷ 305Vac
Frequency
Input current (115 - 230Vac) 2.8 ~ 1.3A
Internal fuse (not replaceable) 4A
47 ÷ 63Hz
Inrush current
(Vn - In nom. Load) I2t
≤ 11A ≤ 5ms
External fuse MCB curve B
10A
General Data
Insulation voltage
IN / OUT
IN / GND
Dimensions W x H x D
Weight
65 x 115 x 135mm
0.6Kg approx.
-25°C ~ 70°C
3000Vac
1605Vac
500Vac
Operating temperature
a
OUT / GND
Derating T >50°C
-2.5% (In)/°C
Protection Degree
EN/IEC 60529
Storage temperature
Ambient Humidity
-40°C ~ +85°C
RH 95%
IP20
Pollution degree
Connection wires size
Protection class
(with PE connected)
2
not condensing
Natural air flow, convection
2.5mm (24-14AWG)
I (IEC61140)
Cooling
Battery Charger (@ 25°C Ambient, Inom)
Charging current Adjustment 20 ~ 100% Inom
Boost charge
28.8Vdc
Reverse battery protection
Sulfated battery check
Detection of battery element
in short circuit
Quiescent current
Charging Profile
Yes
Yes
Max. Boost charge duration 15h
Min. duration boost charge
Trickle charge
1min.
27.5Vdc
Yes
≤ 5mA
3 stage
Boost / Trickle
MTBF IEC 61709
Recovery charge
Max. Charging current
> 300.000h
2 ~ 16Vdc
5A 5%
Remote input control
Power Supply Output (@ 25°C Ambient, Inom)
Max current output load
Total discharge protection
Flat battery alarm
15A x 4s Max
19 ~ 20Vdc batt
20 ~ 21Vdc batt
Output voltage
Output Current
Continuos current
(without battery)
Continuos current
(with battery)
22 ~ 28.8Vdc
1.1 x In A 5%
5A
10A
Signal Outputs
Mains or backup power
Low battery
Battery fault
Yes
Yes
Yes
Relay outputs
Type
Max. AC Load AC1
Max. DC Load DC1
Min. Load
2 x SPDT
1A @ 60Vac
1A @ 30Vdc
1mA @ 5Vdc
Signal Port RJ45 (RJ 45 Auxiliary Output behind the label; remove the window label to find the connector)
Battery temp. Compensation Yes. It is possible connect a
temperature sensor, for
Can Bus
No
ambient temperature
charging compensation.
Remote monitoring display
Yes. It is possible connect
an external display to remote
N° 3 led of the internal device.
2
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 17/06/2015
Smart Power Supply and UPS
Type SPUBC 24V 5A
Signals and Terminals
F
G
M
A: Mains Terminals (input)
B: Battery and load terminals
C: Backup mode output
D: Battery status output
E: Backup mode LED
G: Diagnosis LED
H: Battery configuration jumpers
J: Charging level adjustment (from 20 to 100%)
K: Fast charge enabling jumper
L: Remote battery start
F: Battery status LED
M: Local battery start
Output Power Connections
Normal connection
Parallel connection “Redundancy”
DC BUS
+
-
SPD24RM20 / SPM2RM2410
DC BUS
+
-
+
-
+
AC
+
-
-
+
-
+
+
-
+
-
+
AC
DC
-
Battery
Battery
+
-
+
DC
+
AC
Battery
Battery
-
+
-
+
DC
Battery
Battery
Parallel connection “Double Power”
Series connection
DC BUS
MASTER
DC BUS
+
-
+
-
+
AC
-
DC
+
AC
+
-
-
DC
+
-
Aux2
+
Battery
Battery
AC
DC
-
+
-
+
AC
DC
Aux2
-
Battery
Battery
+
-
Battery
Battery
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 17/06/2015
3
Smart Power Supply and UPS
Type SPUBC 24V 5A
Buffering Time / Battery Capacity
Battery
capacity
1.2Ah
SPUBATxx1A2
3.2Ah
SPUBATxx3A2
7.2Ah
SPUBATxx7A2
12Ah
SPUBATxx12
100Ah
Load
1.5A
3A
20’
8’
60’
30’
15’
10’
7’
200’
120’
55’
400’
240’
100’
60’
-
-
-
5A
3’
7.5A
10A
2’
30’
-
no
20’
45’
20h
Accessories
Max.
Charging Weight
current
Ordering
Code
Battery
Capacity
Width Height Depth
Description
Type
Voltage
mm
mm
mm
SPUBAT241A2
SPUBAT243A2
SPUBAT247A2
SPUBAT1A2
SPUBAT3A2
SPUBAT7A2
SPUBAT12
DIN Rail Rack with 1.2Ah Battery
DIN Rail Rack with 3.2Ah Battery
Lead Acid VRLA
24V
24V
24V
1.2Ah
3.2Ah
7.2Ah
0.3A
1.5Kg
62
82
185
200
210
175
200
210
210
120
160
130
120
160
130
210
Lead Acid VRLA
0.8A
3Kg
DIN Rail Rack with 7.2Ah Battery
Lead Acid VRLA
1.7A
5.5Kg
145
62
Empty DIN Rail Rack for 1.2Ah Battery
Empty DIN Rail Rack for 3.2Ah Battery
Empty DIN Rail Rack for 7.2Ah Battery
Empty DIN Rail Rack for 12Ah Battery
-
-
-
-
12V or 24V Designed for 1.2Ah
12V or 24V Designed for 3.2Ah
12V or 24V Designed for 7.2Ah
12V or 24V Designed for 12Ah
-
-
-
-
?
?
?
?
82
145
210
4
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 17/06/2015
相关型号: