SILD865170 [CELDUC]

AC Semiconductor Contactor pitch 22,5mm with Diagnostic compact size and DIN rail mounting.; AC半导体接触器间距22,5mm与诊断紧凑的尺寸和DIN导轨安装。
SILD865170
型号: SILD865170
厂家: celduc-relais    celduc-relais
描述:

AC Semiconductor Contactor pitch 22,5mm with Diagnostic compact size and DIN rail mounting.
AC半导体接触器间距22,5mm与诊断紧凑的尺寸和DIN导轨安装。

半导体
文件: 总5页 (文件大小:512K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
S/CLP/SILD865170/F/25/03/2005  
celpac  
page 1 /5 GB  
AC Semiconductor Contactor  
pitch 22,5mm with Diagnostic  
compact size and DIN rail mounting.  
SILD865170  
Output : 150-510VAC 32A(*)  
Input : 3,5-32VDC - I<10mA  
Diagnostic : 30VDC - 100mA  
Ready to use Single-Phase Relay: " Install it & Forget it!"  
Zero cross model : 150-510VAC  
50A back to back thyristors on output  
TMS2 technology - I2t value > 1500A2s  
2
2
I t values on request to 5 000A s.  
PATENTED !  
Model with diagnostic : status of the SSR and the load .  
Normally closed status output .  
Without external power supply .  
Status visualization by yellow LED (*) .  
Status output can be chained.  
Very high immunity : Voltage protection on output  
and input- 4kV according IEC61000-4-4 & 5  
Large control range : 3,5-32VDC with an input  
current < 10 mA on all the range.  
Green LED visualization on the input.  
IP20 housing  
Low zero cross voltage ( <15V)  
Mounting and dismounting on DIN rail without any  
tool or directly mountable on panel.  
28A  
Designed in conformity with EN60947-4-3  
(*) see conditions (thermal curve page 4)  
(IEC947-4-3) and EN60950  
-UL-cUL  
400VAC 50hz  
(*) : was Red on the first pieces.  
Dimensions :  
-
Output  
status  
+
diag  
SSR  
Typical  
application:  
9kW resistor  
+
Input  
Control  
(AC-51 load)  
-
on 400 VAC  
CHARGE/LOAD  
celduc  
Proudtoserveyou  
All technical caracteristics are subject to change without previous notice.  
Caractéristiques sujettes à modifications sans préavis.  
r e l a i s  
S/CLP/SILD865170/F/25/03/2005  
celpac  
page 2 /5 GB  
Control characteristics (at 25°C)  
Input : Ic = f( Uc)  
DC  
Paramètre / Parameter  
Control voltage  
Symbol Min  
Nom Max Unit  
12  
10  
8
Uc  
Ic  
3,5  
<10  
2
5-12-24 32  
V
mA  
V
Control current (@ Uc )  
Release voltage  
<10  
<10  
Uc off  
6
Input LED  
Reverse voltage  
Clamping voltage  
green  
32  
42  
4
Urv  
Uclamp  
V
V
2
Input immunity : EN61000-4-4  
Input immunity : EN61000-4-5  
2kV  
2KV  
0
0
2
4
6
8
10 12 14 16 18 20 22 24 26 28 30 32  
Uc ( VDC)  
Output characteristics (at 25°C)  
Parameter  
Conditions  
Symbol  
Ue  
Uemin-max  
Up  
Typ.  
400  
150-510  
1200  
Unit  
V rms  
V rms  
V
Load voltage  
Operating range  
Peak voltage  
Clamping voltage  
Zero cross level  
Latching voltage  
AC-51 nominal current : permanent  
AC-53 nominal current  
Non repetitive overload current  
On state voltage drop (typical value)  
Dynamic resistance (typical value)  
Uclamp  
Usync  
Ua  
820 (@1mA)  
V
V
V
A rms  
A rms  
A
V
mΩ  
14  
14  
32  
12  
550  
0,9  
8
Ie nom  
( see Fig. 2 page 4 ) Ie AC-51  
Ie AC-53  
Itsm  
Vt  
tp=10ms (Fig. 3)  
@ 25°C  
rt  
Output Power dissipation (typical value)  
Pd  
0,81xIe+0,08xIe2  
W
Thermal resistance between junction to air  
Off state leakage current  
Minimum load current  
Turn on time  
Turn off time  
Operating frequency range  
Off state dv/dt  
Rthj/a  
Ilk  
Iemin  
ton max  
toff max  
f
dv/dt  
di/dt  
I2t  
3,3 (2,5)  
<5  
100  
10  
10  
40-440  
500  
50  
K/W  
mA  
mA  
ms  
ms  
Hz  
V/µs  
A/µs  
A2s  
@Ue, 50Hz  
Uc nom DC ,f=50Hz  
Uc nom DC ,f=50Hz  
Maximum di/dt non repetitive  
I2t (<10ms)  
1500  
Conducted immunity level  
Conducted immunity level  
Short circuit protection  
IEC 1000-4-4 (burst)  
IEC 1000-4-5(schocks)  
FERRAZ  
4kV criterion A  
4kV criterion A  
gRC 25A/32A/50A/63A 14x51  
General characteristics (at 25°C)  
Input to output insulation  
Output to status insulation  
Output to case insulation  
Insulation resistance  
Rated impulse voltage  
Ui  
Ui  
Ui  
Ri  
4000  
2500  
4000  
VRMS  
VRMS  
VRMS  
MΩ  
100 (@500VDC)  
Uimp  
4000  
V
Protection level / CEI529  
Pollution degree  
-
-
IP20  
2
Vibration resistance 10 -55 Hz according to CEI68 :  
Shocks resistance according to CEI68 ( on DIN rail / with screws)  
Ambient temperature (with no icing or condensation)  
Storage temperature (with no icing or condensation)  
Ambient humidity  
Weight  
double amplitude  
1,5  
30/50  
-40 /+80  
-40/+100  
40 to 85  
mm  
g
°C  
°C  
%
-
-
HR  
260  
g
Conformity  
Conformity  
EN60947-4-3 (IEC947-4-3)  
UL/cUL pending  
celduc  
www.celduc.com  
r
e
l
a
i
s
Rue Ampère B.P. 4  
42290 SORBIERS - FRANCE  
E-Mail : celduc-relais@celduc.com  
Fax +33 (0) 4 77 53 85 51  
Service Commercial France Tél. : +33 (0) 4 77 53 90 20  
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19  
S/CLP/SILD865170/F/25/03/2005  
celpac  
page 3 /5 GB  
Status output answer characteristics (at 25°C)  
Paramètre / Parameter  
Conditions  
Us  
Symbol Min  
Nom Max Unit  
Voltage range  
Output current  
On resistance  
1
12-24  
0,1  
32  
0,1  
2
V
A
Id  
0
Rdson  
Open delay (faults) - fig. 1  
Total open delay (faults) - fig. 1  
Closed mains delay  
Closed mains delay  
Maximum cable length for open load ( maximum load due to capacitor)  
Uenom  
to1  
to2  
tc1  
tc2  
70  
ms  
ms  
ms  
ms  
m
Uenom, Uc=0V  
Uenom, Uc=Ucnom  
Uenom, Uc=Ucnom  
120  
20  
20  
40  
Diagnostic description  
Control  
Control  
LED  
Mains  
Load  
SSR  
Status LED Output status  
Notices  
The red LED luminosity depends on :  
- Ue voltage.  
0
1
No  
No  
x
x
x
x
Open  
Open  
- Control : ON,OFF  
- Load type.  
The status outputs can be connected in  
serial for only one information.  
0
1
Yes  
Yes  
OK  
OK  
OK  
OK  
closed  
closed  
NPN/ PNP output is possible with status  
( insulation with the control) and no power  
supply for the relay.  
In case of using with a mains voltage  
0
0
1
1
Yes  
Yes  
Yes  
Yes  
Open  
OK  
OK  
Open  
Open  
Open  
Open  
lower than specifications, the SSR works  
correctly, but an alarm status can be given  
with control OFF.  
In this case, the status works only with  
control ON with the diagnostic of open  
load or SSR short-circuit.  
short-circuit  
OK  
Open  
OK  
short-circuit  
ABSENCE RESEAU  
/ OPEN MAINS  
Reaseau  
/ Mains  
* Status (static output) is normally closed  
without failure on the relay and the load,  
and the yellow LED is switched ON :  
That means there is  
- voltage across the SSR without control.  
- current inside the SSR with control .  
Synoptic :  
ON  
OFF  
Commande  
/ Control  
CHARGE COUPEE  
THYRISTORS EN COURT-  
CIRCUIT  
/ SHORT-CIRCUIT SCR  
/ OPEN LOAD  
Courant  
/ Current  
* In case of failure on the load ( opened)  
or on the SSR (short-circuited) :  
- the status is opened .  
ton  
tc1  
toff  
Ouvert/ Sortie d'état /  
Open  
Status output  
- the yellow LED is switched OFF .  
Fermé/  
Closed  
to1  
to1  
to2  
tc2  
to1  
to2  
tc1  
to2  
Led de commande  
/ Control LED  
Led d'état  
/ Status LED  
Mains  
150-510V  
Ic  
1 L1  
A1  
Important :  
Fuse  
In case of long wiring cable between the SSR  
and the load ( > 25 meters), it is possible than  
the diagnostic system can't detect an open load.  
Uc  
Control  
Status  
green  
A2  
Id  
Vds  
Load  
red  
2 T1  
celduc  
www.celduc.com  
r
e
l
a
i
s
Rue Ampère B.P. 4  
42290 SORBIERS - FRANCE  
E-Mail : celduc-relais@celduc.com  
Fax +33 (0) 4 77 53 85 51  
Service Commercial France Tél. : +33 (0) 4 77 53 90 20  
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19  
S/CLP/SILD865170/F/25/03/2005  
celpac  
page 4 /5 GB  
Thermal specifications.  
The curve "1" gives the limits of the product. The tem-  
perature reached are acceptable for the components. These  
values are in compliance with most of SSRs manufacturers.  
In a cabinet with a minimum of ventilation or a non perma-  
nent current, these values are correct.  
45  
40  
35  
30  
25  
20  
15  
10  
5
1
The curve "2" gives the limits of the product according  
to EN60947-4-3 with a maximum rise temperature of 50°C  
(@40°C) for a permanent working and in air calm ( test  
during 8 hours).  
2
For a non permanent current, you can calcule the aver-  
age power = Pd x duty cycle and check the rise tempera-  
ture : Tj = Pd x Rthj/a (Pd and Rthj/a are given page 2)).  
The junction temperature must not exceed 125°C at the  
maximum ambient temperature. The maximum current is  
limited to the size of the thyristors = 50A.  
0
0
5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85  
The thermal constant (Cth) of the product is 7 minutes.  
That means the rise temperature is only 63% of the stabi-  
lized temperature after a running time of  
7 minutes.  
Tambient(°C)  
fig 2  
Fig.3 Surge current : Itsm (Apeak) = f(t) for 50A models with Itsm =550A  
Overload current.  
1 - No repetitive Itsm is given without voltage  
reapplied . This curve is used for the  
determination of the protection.  
600  
1
400  
2 - Repetitive Itsm is given for inrush current  
with initial Tj = 70¡C. In normal working , this  
curve musn’t be exceed. Be carefull, the  
repetition of the surge current decrease the  
lifetime SSR’s .  
No repetive surge current without voltage reapplied.  
2
200  
Repetive surge current with voltage reapplied.  
0
fig 3  
0,01  
0,1  
1
10  
t (s)  
Mounting and dismounting on DIN rail without any tool.  
Panel Mounting  
M5  
M4  
Mounting  
88 2mm  
DIN rail connected to  
protection wire (ground) .  
Dismounting  
12,7mm  
Warning ! semiconductor relays don't provide any galvanic insulation between the load and the mains. Always use in conjunction  
with an adapted circuit breaker with isolation feature or a similar device in order to ensure a reliable isolation in the event of wrong function  
and when the relay must be insulated from the mains (maintenance ; if not used for a long duration ...).  
celduc  
www.celduc.com  
r
e
l
a
i
s
Rue Ampère B.P. 4  
42290 SORBIERS - FRANCE  
E-Mail : celduc-relais@celduc.com  
Fax +33 (0) 4 77 53 85 51  
Service Commercial France Tél. : +33 (0) 4 77 53 90 20  
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19  
S/CLP/SILD865170/F/25/03/2005  
celpac  
page 5 /5 GB  
wires  
torques  
screwdriver  
Connections .  
L
L
(mm2)  
For the output terminals, the wire cross sections must be  
adapted to the load current and to the overcurrent protection device  
characteristics. The relay rated voltage must be adapted to the mains  
rated voltage.  
screwdriver  
control  
1 x(0,75-->2,5)  
L = 6mm  
0,4N.m  
(0,6N.m max)  
3,5x0,5mm  
celpac use screw clamp connections.  
Power  
1x(1,5-->16) 1 x(1,5-->10)  
L = 10mm  
1,2N.m  
(1,8N.m max)  
Pozidriv2/  
0,8x5,5 (1x6)  
Mounting  
Only in vertical position:  
The user should protect heat sensitive materials as well as persons against any contacts with the  
heatsink. For non vertical mounting , the load current must be 50% lower than the rated one . For a  
good cooling, the SSR needs an air convection. Less convection air produces an abnormal heating.  
Keep a distance between the upper SSR and the lower SSR. In case of no space between two SSR (ze-  
ro space between two SSRs) , please reduce the load current. For further details refer to below :  
Derating current with no space between SSRs  
AC-51 nominal currents are given with a space of 22,5mm between each SSR, for a  
permanent current during a minimum time of 8 hours in air calm according to IEC60947-4-3. In case  
of non permanent currents or in case of SSRs are mounted with no space, you must check the heatsink  
temperature never exceed 90°C. When the SSRs are mounted side to side ( no space between each re-  
lay) a derating current of 25% must be take into account.  
vertical  
position  
80mm  
A forced cooling ( fan inside the cabinet) improves significantly the thermal performances.  
Typical application :  
LOADS  
SILD product is designed mainly for AC-51 résistive load. AC-53 motor current are also given .  
For other loads, check the inrush current at turn ON and possible overvoltages at turn OFF or  
consult us :  
* AC-55b : Incandescent lamps : Inrush current is generally 10 times In during few 10ms. So limit  
the nominal current at about 15A.  
* AC-55a : Electric discharge lamp : These loads often have overcurrent at turn ON and overvoltage  
at turn OFF, so we advise to use 400VAC SSR on 230VAC mains.  
* AC-56a : Transformers loads : Very high inrush current up to 100 times In . We advise to use ran-  
dom SSR.  
* AC-56b : Capacitors loads : Very high current at turn ON and overvolatge at turn OFF, please  
consult us with 1600V peak SSR with high inrush current.  
Fuse  
Fusible  
diagnostic  
outputs in  
serie  
+
-
+
-
+
-
Protection :  
Diag  
Diag  
L1  
T1  
L1  
T1  
To protect the SSR against a short-circuit of the load , use a fuse with a I2t value = 1/2 I2t value  
specified page 2. A test has been made with FERRAZ fuse ( see page 2).  
It is possible to protect SSR by MCB ( miniature circuit breaker). In this case, see application note (  
SSR protection) and use a SSR with high I2t value (5000A2s minimum).  
EMC :  
Immunity :  
We give in our data-sheets, the immunity level of our SSRs according to the main standards for  
this type of products : EN61000-4-4 &5. You can see the high immunity level in comparison with the  
products on the market.  
-
+
A1  
- +  
Emission:  
A2  
control  
A2 A1  
SSRs are complex devices which must be interconnected with other equipment (loads,  
cables,etc.) to form a system. Because the other equipment or the interconnections may not be under  
the control of celduc, it shall be the responsibility of the system integrator to ensure that systems  
containing SSRs comply with the requirements of any rules and regulations applicable at the system  
level.. Consult celduc laboratory which can make some tests in your application.  
control  
Load  
Charge  
N
N
celduc  
www.celduc.com  
r
e
l
a
i
s
Rue Ampère B.P. 4  
42290 SORBIERS - FRANCE  
E-Mail : celduc-relais@celduc.com  
Fax +33 (0) 4 77 53 85 51  
Service Commercial France Tél. : +33 (0) 4 77 53 90 20  
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19  

相关型号:

SILM8030

SMT Power Inductor
DELTA

SILM8030-100

SMT Power Inductor
DELTA

SILM8030-101

SMT Power Inductor
DELTA

SILM8030-150

SMT Power Inductor
DELTA

SILM8030-220

SMT Power Inductor
DELTA

SILM8030-2R5

SMT Power Inductor
DELTA

SILM8030-330

SMT Power Inductor
DELTA

SILM8030-3R3

SMT Power Inductor
DELTA

SILM8030-470

SMT Power Inductor
DELTA

SILM8030-4R7

SMT Power Inductor
DELTA

SILM8030-680

SMT Power Inductor
DELTA