CFM21S150 [CINCON]
20 WATT SINGLE OUTPUT AC-DC MODULES;型号: | CFM21S150 |
厂家: | Cincon |
描述: | 20 WATT SINGLE OUTPUT AC-DC MODULES 输出元件 |
文件: | 总2页 (文件大小:307K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
V13
CFM21 SERIES
20 WATT SINGLE OUTPUT
︳
AC-DC MODULES
Features
* Universal Input Range 90~264VAC
* Miniature Size Low Profile 0.8”
* Industry-Standard Pin Out
* Efficiency to 85%
* Option for On-Board, Connecter,
Screw Terminal Or Encapsulated type
* Continuous Short Circuit Protection
* Over Voltage Protection
* No Load Input Power < 0.3W
* Leakage Current < 0.1mA
* UL60601-1/IEC60601-1/EN60601-1 Medical Safety
Approved
* UL60950-1/IEC60950-1/EN60950-1 ITE Safety Approved
OUTPUT
RATED
INPUT
VOLTAGE
OUTPUT
MIN.
MAX.
VOLTAGE
ACCURACY
RIPPLE &
NOISE
MODEL
% EFF.
VOLTAGE
LOAD
LOAD
POWER
CFM21S033 90~264 VAC
CFM21S050 90~264 VAC
CFM21S090 90~264 VAC
CFM21S120 90~264 VAC
CFM21S150 90~264 VAC
CFM21S240 90~264 VAC
3.3 V
5.0 V
9.0 V
12 V
15 V
24 V
0
0
0
0
0
0
4.0 A
4.0 A
2.3 A
1.7 A
1.4 A
0.9 A
13.2 W
20.0 W
20.7 W
20.4 W
21.0 W
21.6 W
50 mV
50 mV
1ꢀ
1ꢀ
1ꢀ
1ꢀ
1ꢀ
1ꢀ
75ꢀ
80ꢀ
81ꢀ
83ꢀ
84ꢀ
85ꢀ
90 mV
100 mV
100 mV
100 mV
Specifications are subject to change without notice.
1
V13
Specifications
CFM21 Series De-rating Curve
INPUT SPECIFICATIONS:
Voltage …....………........…........................................... 90~264Vac
Frequency ………………………………………….……………..... 47 to 63Hz
Input Current ……………………………………….……………..... 0.3 to 0.5A
Derating curve for Natural Convection
120%
100%
80%
60%
40%
20%
0%
-25
60
℃
Inrush Current …………….…Cold Start@25 ............. 40A max. @230Vac
Leakage Current …………………………………………………… 0.1mA max.
OUTPUT SPECIFICATIONS:
Voltage Accuracy: ........................................…………............... 1.0% max.
Line Regulation (note3) ….…………….…………...................…. 0.5% max.
70
CFM21 Series
Load Regulation (note4) ….…………………….…….........…...... 1.0% max.
Hold-up Time …………………………….…………..…… 10ms typ. @115Vac
Short Circuit Protection …………….………………………….…… Continuous
-25
70
-30
-10
10
30
50
70
Over Voltage Protection(TVS) …… 115%-140% of nominal output voltage
o
Ambient Temperature( C)
GENERAL SPECIFICATIONS:
Efficiency …………………………………………………………….. see Table
SAFETY AND EMISSION:
Switching Frequency ………………………………….…………..100KHz typ.
Isolation …………………………………………… Input to output = 5656VDC
CE Directive ……………………………….……… 2004/108/EC, 93/42/EEC
Emissions … EN60601-1/EN61204-3/EN55022/CISPR Class B, EN55024
Safety Approvals ……....................... UL60601-1,IEC60601-1,EN60601-1
UL60950-1,IEC60950-1,EN60950-1
℃
Operating Temperature ........................................ -25 ~ 70 (with de-rating)
℃
Storage Temperature ……………………………...….......……........ -40~85
Cooling ………………………………….………………… Natural Convection
NOTE:
1. Voltage accuracy is set of 100% rated load.
Humidity .................................................... 93% RH max. Non condensing
MTBF ……….…. MIL-STD-217F, GB ..………..……………… 650Khrs min.
Dimensions …………..........….. 2.38x1.60x0.80inches (60.5x40.6x20.4mm)
-T: 3.00x1.60x0.77inches (76.2x40.6x19.5mm)
2. Add a 0.1uF ceramic capacitor and a 10uF E.L. capacitor to output for
Ripple & Noise measuring @20MHz BW.
3. Line regulation is measured from high line to low line with full load.
4. Load regulation is measured from 10% to 100% full load.
5. T Version Connection: JST B3P-VH / B4P-VH or equivalent.
6. S Version Connection: DECA MB332-381A or equivalent.
-E: 2.53x1.74x0.80Inches (64.2x44.2x20.4mm)
-S: 3.00x1.60x0.77Inches (76.2x40.6x19.5mm
Weight ………………………………………….…… 50g, 55g(-T, -S), 105g(-E)
Mechanical Specification
CFM21SXXX
CFM21SXXX-T
CFM21SXXX-E
All Dimensions In Inches[mm]
Tolerance: Inches:x.xx= ±±.±2,x.xxx= ±±.±1
Millimeters:x.x= ±±.ꢀ,x.xx= ±±.2ꢀ
-Vo
ACN
ACL
+Vo
0.120 [3.06]
2.126 [54.00]
2.38 [60.5]
CFM21SXXX-S
Typical at 25˚C, nominal line and 75% load, unless otherwise Specified
2
相关型号:
©2020 ICPDF网 联系我们和版权申明