BK1-MDQ-1/4-V [COOPER]

Electric Fuse, Time Delay Blow, 0.25A, 250VAC, 35A (IR), Through Hole;
BK1-MDQ-1/4-V
型号: BK1-MDQ-1/4-V
厂家: COOPER BUSSMANN, INC.    COOPER BUSSMANN, INC.
描述:

Electric Fuse, Time Delay Blow, 0.25A, 250VAC, 35A (IR), Through Hole

电路保护 电熔丝
文件: 总2页 (文件大小:259K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
1
1
4
" x 1 ⁄ " Fuses  
4
MDQ Series Dual-Element, Time-Delay, Glass Fuse  
Description  
• Dual-element, time-delay  
1⁄  
4
" x 1 1⁄  
" (6.3 x 32mm) physical size  
4
• Glass tube, nickel-plated brass endcap construction  
• UL Listed product meets standard 248-14  
• Available with axial leads  
Electrical Characteristics  
Rated Current % of Amp Rating  
Opening Time  
None  
60 minutes maximum  
120 seconds maximum  
100%  
1
16 - 30A  
135%  
200%  
Dimensions - mm (in)  
Agency Information  
• UL Listed Card: MDQ-116 - 7A (Guide JDYX,  
File E19180)  
• UL Recognition Card: MDQ-7.5 - 15A  
(Guide JDYX2, File E19180)  
with axial leads  
• CSA Component Acceptance Card:  
MDQ-116 - 15 (Class 1422-01)  
Ordering  
• Specify packaging, product, and option code  
(i.e., Bk-MDQ-BV-1)  
Specifications  
Voltage  
Interrupting  
Rating  
Amps  
35  
Typical DC Cold  
Resistance  
(Ω)**  
Product Code  
Rating  
Vac  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
250  
32  
MDQ-1/16  
MDQ-1/10  
MDQ-1/8  
MDQ-3/16  
MDQ-2/10  
MDQ-1/4  
MDQ-3/10  
MDQ-3/8  
MDQ-1/2  
MDQ-3/4  
MDQ-1  
MDQ-1-1/4  
MDQ-1-1/2  
MDQ-2  
MDQ-2-1/4  
MDQ-2-1/2  
MDQ-3  
MDQ-4  
MDQ-5  
MDQ-6  
MDQ-6-1/4  
MDQ-7  
MDQ-8  
MDQ-9  
MDQ-10  
MDQ-15  
83.30000  
35.00000  
21.50000  
10.00000  
8.65000  
5.77500  
4.20000  
2.35000  
1.40000  
0.39685  
0.37400  
0.36000  
0.27000  
0.13250  
0.11450  
0.10050  
0.05715  
0.03510  
0.02650  
0.01715  
0.01690  
0.01375  
0.01200  
0.00888  
0.00720  
0.00410  
35  
35  
35  
35  
35  
35  
35  
35  
35  
35  
100  
100  
100  
100  
100  
100  
200  
200  
200  
200  
200  
1,000  
1,000  
1,000  
1,000  
32  
32  
32  
** DC Cold Resistance (Measured at <10% of rated current)  
0308 BU-SB07472  
Page 1 of 2  
Data Sheet 2044  
Time-Current Curve  
CURRENT IN AMPERES  
CURRENT IN AMPERES  
Packaging  
Packaging Code Prefix  
Description  
BK  
BK1  
100 pieces of fuses packed into a cardboard carton  
1000 pieces of fuses packed into a cardboard carton  
Option Code  
Option Code Suffix  
Description  
B
V
Board Washable - Hermetically sealed to withstand aqueous cleaning  
Axial leads - copper tinned wire with nickel plated brass overcaps  
North America  
Europe  
Asia Pacific  
Cooper Electronic Technologies  
1225 Broken Sound Parkway NW  
Suite F  
Cooper Bussmann  
Cooper Electronic Technologies  
Cooper (UK) Limited  
Cooper Electronic Technologies  
1 Jalan Kilang Timor  
#06-01 Pacific Tech Centre  
Singapore 159303  
Cooper Electronic Technologies  
Avda. Santa Eulalia, 290  
08223  
P.O. Box 14460  
St. Louis, MO 63178-4460  
Tel: 1-636-394-2877  
Fax: 1-636-527-1607  
Burton-on-the-Wolds  
Boca Raton, FL 33487-3533  
Tel: 1-561-998-4100  
Fax: 1-561-241-6640  
Toll Free: 1-888-414-2645  
Leicestershire • LE12 5TH UK  
Tel: +44 (0) 1509 882 737  
Fax: +44 (0) 1509 882 786  
Terrassa, (Barcelona), Spain  
Tel: +34 937 362 812  
+34 937 362 813  
Tel: +65 278 6151  
Fax: +65 270 4160  
Fax: +34 937 362 719  
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is  
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change  
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained  
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.  
Life Support Policy: Cooper Bussmann does not authorize the use of any of its products for use in life support devices or systems without the express written approval of an officer of the Company. Life support  
systems are devices which support or sustain life, and whose failure to perform, when properly used in accordance with instructions for use provided in the labeling, can be reasonably expected to result in  
significant injury to the user.  
© 2008 Cooper Bussmann  
St. Louis, MO 63178  
www.cooperbussmann.com  
0308 BU-SB07472  
Page 2 of 2  
Data Sheet 2044  

相关型号:

BK1-MDQ-1/8-B

Electric Fuse, Time Delay Blow, 0.125A, 250VAC, 35A (IR), Inline/holder
COOPER

BK1-MDQ-1/8-V

Electric Fuse, Time Delay Blow, 0.125A, 250VAC, 35A (IR), Through Hole
COOPER

BK1-MDQ-10-B

Electric Fuse, Time Delay Blow, 10A, 32VAC, 1000A (IR), Inline/holder,
COOPER

BK1-MDQ-10-V

Electric Fuse, Time Delay Blow, 10A, 32VAC, 1000A (IR), Through Hole,
COOPER

BK1-MDQ-15-B

Electric Fuse, Time Delay Blow, 15A, 32VAC, 1000A (IR), Inline/holder,
COOPER

BK1-MDQ-15-V

Electric Fuse, Time Delay Blow, 15A, 32VAC, 1000A (IR), Through Hole
COOPER

BK1-MDQ-2-1/2-B

Electric Fuse, Time Delay Blow, 2.5A, 250VAC, 100A (IR), Inline/holder
COOPER

BK1-MDQ-2-1/2-V

Electric Fuse, Time Delay Blow, 2.5A, 250VAC, 100A (IR), Through Hole
COOPER

BK1-MDQ-2-1/4-V

Electric Fuse, Time Delay Blow, 2.25A, 250VAC, 100A (IR), Through Hole
COOPER

BK1-MDQ-2-B

TIME DELAY BLOW ELECTRIC FUSE, 2A, 250VAC, 100A (IR), INLINE/HOLDER
COOPER

BK1-MDQ-2-V

Electric Fuse, Time Delay Blow, 2A, 250VAC, 100A (IR), Through Hole,
COOPER

BK1-MDQ-2/10-B

Electric Fuse, Time Delay Blow, 0.2A, 250VAC, 35A (IR), Inline/holder,
COOPER