BSPD400600D1P
更新时间:2024-09-18 23:16:29
品牌:COOPER
描述:High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels
BSPD400600D1P 概述
High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels
BSPD400600D1P 数据手册
通过下载BSPD400600D1P数据手册来全面了解它。这个PDF文档包含了所有必要的细节,如产品概述、功能特性、引脚定义、引脚排列图等信息。
PDF下载BUSSMANN
Effective December 2015
Supersedes September 2014
Technical Data 10209
SERIES
BSPD surge protective devices
High capacity Type 1 and Type 2 SPDs for overvoltage protection
on switchgear and power distribution panels
Contents
Description
Page
Introduction
2
2
Applications
Features
2
Standards and certifications
Configuration
2
3
Enclosure options, dimensions, and weights
Voltage protection ratings
Specifications
3
4-5
6
Catalog number system
Technical support information
7
7
Technical Data 10209
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Effective December 2015
Factory sealed to improve electrical safety
Introduction
All BSPD units are factory-sealed to eliminate arc flash and
shock hazards, as the user/installer has no chance of coming
into contact with energized parts.The units also contain no
user-serviceable parts or wire lugs that require periodic
retightening to eliminate the need for periodic maintenance.
The BSPD surge protective devices are tested by Underwriters
Laboratory and Listed to UL® 1449, 3rd Edition to help ensure
equipment is protected with highly reliable surge protection
technology. Delta and Wye system units are available in three
configurations to increase application flexibility.The BSPD
Series is for installation external to an electrical enclosure or
panelboard. Application of BSPD Series units throughout a
facility will help ensure that equipment is protected.
Bussmann series SurgePOD technology eliminates the need
for additional fusing
BSPD uses Bussmann series SurgePOD modules that each
contain an internal element that safely disconnects upon
reaching an overvoltage breakdown condition.
Applications
BSPD units are available for common Delta and Wye system
voltages in a variety of surge current capacity ratings from
120kA to 400kA. Available in three configurations, the BSPD
Series’ features and options make it easy to specify units
for many electrical applications including service entrances,
distribution switchboards, panelboards and point-of-use. All
possible combinations of product attributes are available for
ordering in the catalog number system (see page 7).
Prewired
All BSPD units are factory wired for ease of installation. Simply
install any necessary conduit runs, mount the unit and make all
wire connections. No need for internal wiring or access to the
unit’s inside.
Compact size takes less space
Available in enclosures that are up to 50% smaller than other
products with comparable ratings the BSPD Series come in
NEMA® 1 and 4X enclosures that differ in size according to their
surge current capacity (Imax).
Features
•ꢀ
BSPD uses Bussmann series SurgePOD™ thermally
protected Metal Oxide Varistor (MOV) technology to safely
shunt overvoltages to ground while its thermal disconnect
capability eliminates the need for additional fusing
NEMA 1 BSPD units.
•ꢀ
The 120-200kA surge current capacity units are housed in a 74
square-inch enclosure that is only 3-1/2 inches deep.
200kA SCCR meets the highest NEC® requirements
•ꢀ
•ꢀ
The 300-400kA surge current capacity units are housed in a
74 square-inch enclosure that is only 6 inches deep.
•ꢀ
Models available to meet the overvoltage protection needs
of Wye and Delta electrical systems from 208 to 600 volts,
3-phase
NEMA 4X BSPD units.
•ꢀ
•ꢀ
The 120-200kA surge current capacity units are housed in a
BSPD has the highest nominal discharge current (In) of 20kA
per UL 1449 3rd Edition.This rating indicates the SPD’s ability
to handle a number of large-magnitude surges over a short
period of time and remain operational.
108 square-inch enclosure that is only 5-3/8 inches deep.
•ꢀ
The 300-400kA surge current capacity units are housed in a
108 square-inch enclosure that is only 7-11/16 inches deep.
•ꢀ
120kA to 400kA surge current capacity (Imax) ratings meet
the needs of larger switchgear and power distribution panel
applications
•ꢀ
Optional Form C contact relay, EMI/RFI filtering and surge
counter available to meet additional system requirements.
•ꢀ
200kA Short-Circuit Current Rating (SCCR)
•ꢀ
NEMA 1 or NEMA 4X enclosures
•ꢀ
RoHS compliant
•ꢀ
10 year warranty
Agency information
•ꢀ
Basic, standard and standard withsurge counter
configurations UL Listed, 1449 3rd Edition, File E316410,
Guide VZCA, CSA® Certified, Notice 516, File 243397
•ꢀ
Standard and standard with surge counter configurations are
also UL Recognized, 1283 5th Edition, File E316410, Guide
VZCA2, CSA component acceptance, Std. C22.2, No. 8-M1986,
File 243397
BSPD unit mounted externally to a Bussmann series
Quik-Spec™ Coordination Panelboard
2
Eaton.com/bussmannseries
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Technical Data 10209
Effective December 2015
Enhanced protection status indicators
Dimensions - in (mm) and weights
Unlike many SPDs that only have single-color indicators, all
BSPD units include green and red Light Emitting Diodes (LEDs)
that indicate the true protection status for each phase.
7.28
(184.9)
1.00
(25.4)
5.27
(133.9)
If power is removed from any one phase, the unit’s LEDs
continue to indicate the protection status on that phase —
regardless if power is applied to the phase.This feature ensures
proper indication.
Although many SPDs on the market have N-G surge protection,
they do not always have a means of monitoring and indicating
the protection status of that mode. All BSPD units for Wye
systems also contain green and red LED surge protection status
indicators for the Neutral-to-Ground (N-G) connection. Like the
phase protection status LEDs, the N-G protection status LEDs
show the true protection status in the N-G mode.
10.48
(266.2)
11.25
(285.8)
12.05
(306.1)
0.68
(17.3)
5.24
(133.1)
By specifying the BSPD, users are supplied with accurate
information concerning the surge protection status of their
electrical systems.
Ø0.20
(Ø5.1)
2.00
7.47
(189.7)
0.78
(19.8)
(50.8)
0.40
(10.2)
3.48
(88.4)
4.41
(112.0)
Configurations
The BSPD provides users with three configurations.These are:
•ꢀ
Basic (ULType 1 - can be installed in ULType 2 locations)
Figure 1. NEMA 1, 120kA-200kA Units,
Weight = 6.8 Lbs (3.1 kg)
•ꢀ
Standard (ULType 2)
•ꢀ
Standard with surge counter (ULType 2)
1.00
(25.4)
5.47
(138.9)
The proper configuration can be selected based on application
requirements or specification.
Table 1. configuration comparisons
Configuration
12.05
10.48
(266.2)
(306.1)
11.25
(285.8)
Standard
with
Basic
(Type 1)
Standard surge counter
0.67
(17.0)
5.24
(133.1)
Feature
(Type 2)
(Type 2)
Surge protection using
thermally protected MOV
technology
X
X
X
X
2.00
Ø0.20
(Ø5.1)
7.47
(189.7)
(50.8)
0.78
(19.8)
0.40
(10.2)
5.76
(146.3)
Green and red LED
protection status
indicators for each phase
X
X
X
X
6.69
(169.9)
Figure 2. NEMA 1, 300kA-400kA Units,
Weight = 13.5 Lbs (6.1 kg)
Green and red LED
protection status
indicators for the Neutral-
to-Ground protection
mode (Wye systems only)
X
Audible alarm with silence
button
X
X
X
X
Form C relay contact
EMI/RFI filtering,
providing up to 50dB of
noise attenuation from
10kHz to 100MHz
X
X
X
Surge counter with reset
button held in nonvolatile
memory
A
B
120-200kA
250-400kA
2.60 (66.0)
4.10 (104.1)
5.39 (137.0)
7.68 (195.0)
Figure 3. NEMA 4X, 120kA-400kA Units,
Weight = 120-200kA; 14.6 Lbs (6.6 kg),
250-400kA; 21.0 Lbs (9.5 kg)
Eaton.com/bussmannseries
3
Technical Data 10209
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Effective December 2015
Voltage protection ratings
ANSI/UL 1449 3rd Edition voltage protection ratings
Voltage Protection Rating (VPR) data for all units is included
in the following tables,The data varies based upon the
configuration and NEMA enclosure. VPR values for the Basic
configurations are on the left-hand side of the page.Tables
on the right-hand side contain VPR values for the Standard or
Standard with Surge Counter configurations.
NEMA 1: Basic
(cat. nos. ending with 1K)
NEMA 1: Standard or Standard w/ Surge Counter
(cat. nos. ending with 2K or 3K)
Table 5. 120-200kA
Table 2. 120-200kA
Voltage/
system
code
Protection mode
Voltage/
system
code
Protection mode
L-N
600
1200
1500
—
L-G
N-G
600
1200
1500
—
L-L
L-N
700
1200
1500
—
L-G
N-G
700
1200
1500
—
L-L
208Y
480Y
600Y
240D
480D
600D
800
1000
1800
2500
1000
2500
2500
208Y
480Y
600Y
240D
480D
600D
700
1200
2000
2500
1000
2500
2500
1200
1500
1000
2500
2500
1200
1500
1000
2000
2500
—
—
—
—
—
—
—
—
Table 6. 300kA
Table 3. 300kA
Voltage/
system
code
Protection mode
Voltage/
system
code
Protection mode
L-N
600
1000
1500
—
L-G
N-G
600
1000
1500
—
L-L
L-N
700
1200
1500
—
L-G
N-G
700
1200
1500
—
L-L
208Y
480Y
600Y
240D
480D
600D
700
1000
1800
2500
1000
2000
2500
208Y
480Y
600Y
240D
480D
600D
700
1000
1800
2500
1000
2000
2500
1200
1500
1000
1800
2500
1200
1500
1000
1800
2500
—
—
—
—
—
—
—
—
Table 7. 400kA
Table 4. 400kA
Voltage/
system
code
Protection mode
Voltage/
system
code
Protection mode
L-N
600
1000
1500
—
L-G
N-G
600
1000
1500
—
L-L
L-N
700
1200
1500
—
L-G
N-G
700
1200
1500
—
L-L
208Y
480Y
600Y
240D
480D
600D
700
1000
1800
2500
1000
2000
2500
208Y
480Y
600Y
240D
480D
600D
700
1000
1800
2500
1000
2000
2500
1200
1500
1000
1800
2500
1200
1500
1000
1800
2500
—
—
—
—
—
—
—
—
4
Eaton.com/bussmannseries
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Technical Data 10209
Effective December 2015
NEMA 4X: Basic
(cat. nos ending with 1P)
NEMA 4X: Standard or Standard w/ Surge Counter
(cat. nos. ending with 2P or 3P)
Table 8 120–200kA
Table 11. 120–200kA
Voltage/
system
code
Protection mode
Voltage/
system
code
Protection mode
L-N
700
1200
1500
—
L-G
N-G
700
1000
1500
—
L-L
L-N
900
1200
1500
—
L-G
N-G
700
1000
1500
—
L-L
208Y
480Y
600Y
240D
480D
600D
800
1200
2000
2500
1000
2500
2500
208Y
480Y
600Y
240D
480D
600D
900
1500
2500
2500
1000
2500
2500
1200
1500
1000
2000
2500
1200
1500
1000
2500
2500
—
—
—
—
—
—
—
—
Table 9. 300kA
Table 12. 300kA
Voltage/
system
code
Protection mode
Voltage/
system
code
Protection mode
L-N
L-G
N-G
L-L
L-N
700
1200
1500
—
L-G
N-G
700
1200
1500
—
L-L
208Y
480Y
600Y
240D
480D
600D
800
1200
2000
2500
1000
2000
2500
208Y
480Y
600Y
240D
480D
600D
800
1200
1500
—
900
700
1000
1500
—
1500
2000
2500
1000
2000
2500
1200
1500
1000
1800
2500
1200
1500
1000
2000
2500
—
—
—
—
—
—
—
—
Table 10. 400kA
Table 13. 400kA
Voltage/
system
code
Protection mode
Voltage/
system
code
Protection mode
L-N
700
1200
1500
—
L-G
N-G
700
1200
1500
—
L-L
L-N
800
1200
1500
—
L-G
N-G
700
1000
1500
—
L-L
208Y
480Y
600Y
240D
480D
600D
800
1200
2000
2500
1000
2000
2500
208Y
480Y
600Y
240D
480D
600D
900
1500
2000
2500
1000
2000
2500
1200
1500
1000
1800
2500
1200
1500
1000
2000
2500
—
—
—
—
—
—
—
—
Eaton.com/bussmannseries
5
Technical Data 10209
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Effective December 2015
5.0 Specifications
Table 14. specifications
Description
Specification
Available system voltages
120/208, 277/480 and 347/600
240, 480 and 600
50/60Hz
Three-phase Wye
Three-phase Delta
Input power frequency
Maximum continuous operating voltage (MCOV)
208Y, and 240D voltage/system type codes
480Y Voltage/system type code
600Y Voltage/system type code
480D Voltage/system type code
600D Voltage/system type code
Short-Circuit Current Rating (SCCR)
Nominal discharge current (In)
150 L-N,150 L-G, 150 N-G, 300 L-L
320 L-N, 320 L-G, 320 N-G, 640 L-L
420 L-N, 420 L-G, 420 N-G, 840 L-L
640 L-G, 640 L-L
840 L-G, 840 L-L
200kA
20kA
Surge current capacity per phase (Imax
)
120kA, 200kA, 300kA and 400kA ratings available
Type 1 (Basic configuration, can also be used inType 2 applications)
Type 2 (Standard and Standard With Surge Counter configurations)
SPDTypes
Enclosure types
Ports
NEMA 1, NEMA 4X 304 Stainless Steel
1
SPD Conductor length/gauge
48” (1.22m) 10AWG Stranded copper
Form C contact relay (Standard and standard with surge counter configurations only)
Contact ratings
150Vac or 125Vdc, 1A maximum
48 inches (1.22m) / 14AWG
Lead length/gauge
Power ON, normal state; N.O. contact = Open, N.C. contact = Closed
Power OFF, fault state; N.O. contact = Closed, N.C. contact = Open
Contact logic
Power consumption
Basic configuration
208Y and 240D voltage/system type codes
480Y and 480D voltage/system type codes
600Y and 600D voltage/system type codes
0.5W
1.1W
1.3W
Standard and Standard With Surge Counter configurations
208Y and 240D voltage/system type codes
480Y, and 480D voltage/system type codes
600Y and 600D voltage/system type codes
0.6W
1.7W
2.1W
Three-phase Delta; L-G, L-L
Three-phase Wye; L-N, L-G, N-G, L-L
Protection modes
Operating temperature / humidity
Operating altitude - ft (m)
-40 to +50°C (-40 to +122°F) / 5% to 95%, non-condensing
16,000 (5000)
Up to 50dB from 10kHz to 100MHz (standard and standard with surge counter
configurations)
EMI/RFI filtering attenuation
Weight - lbs (kg)
NEMA 1: 120kA-200kA - 6.8 (3.1), 30- 400kA -13.5 (6.1) NEMA 4X: 120-200kA - 14.6
(6.6), 300-400kA - 21.0 (9.5)
- Basic, Standard and Standard With Surge Counter configurations UL Listed 1449 3rd
Edition File E316410 Guide VZCA, CSA Certified Notice 516 File 243397
- Standard and Standard With Surge Counter configurations are also UL Recognized
1283 5th Edition File E316410 Guide VZCA2, CSA Component Acceptance Std. C22.2
No. 8-M1986 File 243397
Agency information
Seismic withstand capability
Warranty
Meets or exceeds the requirements specific to I.B.C. 2006, C.B.C 2007 and U.B.C zone 4
10Years (see warranty statement 3A1502 for details at www.cooperbussmann.com/
Surge)
6
Eaton.com/bussmannseries
BSPD SPDs for overvoltage protection on
switchgear and power distribution panels
Technical Data 10209
Effective December 2015
6.0 Catalog Number System
Table 15. BSPD part number system
All possible combinations of the BSPD attributes are available
for ordering.
BSPD 200 480D 2 K
Enclosure rating
Series
BSPD
K = NEMA 1
P = NEMA 4X
Voltage/system type code
kA Rating
per phase
208Y = 120/208 Wye (4W + G)
480Y = 277/480 Wye (4W + G)
600Y = 347/600 Wye (4W + G)
240D = 240 Delta (3W + G)
480D = 480 Delta (3W + G)
600D = 600 Delta (3W + G)
120kA
200kA
300kA
400kA
Configurations
1 = Basic
Green and red LEDs per phase to indicate protection status
Green and red LEDs on Wye units to indicate protection status of the Neutral-to-Ground mode
2 = Standard
Green and red LEDs per phase to indicate protection status
Green and red LEDs on Wye units to indicate protection status of the Neutral-to-Ground mode
Audible alarm with Silence button
Form C contact relay. See Table 3, Specifications
EMI/RFI filtering providing up to 50dB of noise attenuation from 10kHz to 100MHz
3 = Standard With Surge Counter
Green and red LEDs per phase to indicate protection status
Green and red LEDs on Wye units to indicate protection status of the Neutral-to-Ground mode
Audible alarm with silence button
Form C contact relay
EMI/RFI filtering providing up to 50dB of noise attenuation from 10kHz to 100MHz
Surge counter with reset button
Technical support information
If you have any questions or need additional information,
please contact the Eaton’s Bussmann Division
application engineers between the hours of 7:00 am and
5:00 pm central time at 855-287-7626 (855-Bussmann) or by
email, FuseTech@Eaton.com.
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this
document are by definition uncontrolled.This bulletin is intended to clearly present comprehensive product data and provide technical
information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of
any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any
technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
For Eaton’s Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton and Bussmann are valuable
trademarks of Eaton in the US and other
countries.You are not permitted to use the
Eaton trademarks without prior written
consent of Eaton.
Eaton.com/bussmannseries
Follow us on social media to get the
latest product and support information.
© 2015 Eaton
All Rights Reserved
Printed in USA
CSA is a registered trademark of the
Canadian Standards Group.
Publication No. 10209 – BU-SB14678
December 2015
UL is a registered trademark of the
Underwriters Laboratories, Inc.
7
BSPD400600D1P 相关器件
型号 | 制造商 | 描述 | 价格 | 文档 |
BSPD400600D2K | EATON | High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels | 获取价格 | |
BSPD400600D2K | COOPER | High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels | 获取价格 | |
BSPD400600D2P | EATON | High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels | 获取价格 | |
BSPD400600D2P | COOPER | High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels | 获取价格 | |
BSPD400600D3K | EATON | High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels | 获取价格 | |
BSPD400600D3K | COOPER | High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels | 获取价格 | |
BSPD400600D3P | EATON | High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels | 获取价格 | |
BSPD400600D3P | COOPER | High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels | 获取价格 | |
BSPD400600Y1K | EATON | High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels | 获取价格 | |
BSPD400600Y1K | COOPER | High capacity Type 1 and Type 2 SPDs for overvoltage protection on switchgear and power distribution panels | 获取价格 |
BSPD400600D1P 相关文章
- 2024-09-20
- 5
- 2024-09-20
- 8
- 2024-09-20
- 8
- 2024-09-20
- 6