EDCC0.5 [COOPER]
Electric Fuse, Time Delay Blow, 0.5A, 600VAC, 300VDC, 200000A (IR), Inline/holder;型号: | EDCC0.5 |
厂家: | COOPER BUSSMANN, INC. |
描述: | Electric Fuse, Time Delay Blow, 0.5A, 600VAC, 300VDC, 200000A (IR), Inline/holder |
文件: | 总2页 (文件大小:242K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
EDCC
Class CC, 600Vac, 0.5 to 30A
Time-Delay Fuses
Dimensions (inches)
• Can be used where either a time-delay or a fast-acting
fuse is needed, making selection easier and reducing
spare fuse inventories for substantial cost reduction.
Catalog Symbol: EDCC
Time-Delay
• Superior Motor Protection for small horsepower motor
circuits.
Current-Limiting
Volts: 600Vac (or less)
300Vdc (or less)
Amps: 0.5 to 30A
IR: 200kA RMS Sym.
• Proper sizing can provide Type “2” coordinated
protection for NEMA and IEC motor controllers.
• Motors receive maximum protection against burnout
from overloads and single phasing.
20kAIC (0.5 – 2.25A and 20-30A)
Agency Information: CE, UL Listed, Std. 248-4, Class CC,
Guide JDDZ, File E162363, CSA Certified, HRCI-CC, C22.2
No. 248.4, Class 1422-02, File 53787
Catalog Numbers (amps)
EDCC0.5
EDCC0.6
EDCC0.8
EDCC1
EDCC1.125
EDCC1.25
EDCC1.4
EDCC1.6
EDCC1.8
EDCC2
EDCC2.25
EDCC2.5
EDCC2.8
EDCC3
EDCC4
EDCC4.5
EDCC5
EDCC5.6
EDCC6
EDCC6.25
EDCC7
EDCC8
EDCC9
EDCC10
EDCC12
EDCC15
EDCC20
EDCC25
EDCC30
Features
• A superior all-purpose, space-saving branch circuit fuse
that meets most protection requirements up to 30 amps.
13
1
• Very compact; physical size is only ⁄32" x 1 ⁄
2"
EDCC3.2
EDCC 3.5
(10.3 x 38.1mm) with rejection tip.
EDCC7.5
• Faster response to damaging short-circuit currents and
higher interrupting rating than mechanical overcurrent
protective devices.
Carton Quantity and Weight
• Maximum 200kA interrupting rating for available fault
current in today's large capacity systems. Helps ensure
that future growth will not obsolete the system.
Carton
Quantity
10
Weight per Carton
Amps
0.5-30
lbs
kg
0.09
0.19
• Time-delay to avoid unwanted fuse openings from surge
currents.
Class CC Fuse Blocks (600V) Catalog Data
• Fast speed of response under short-circuit conditions for
a high degree of current-limitation.
Screw
Pressure
Screw
Pressure
Plate
Box
Quick-
Quick-
Poles Terminal
Terminal Connect
Connect
• The EDCC fuse can be sized close to full load ratings
for maximum overload and short-circuit protection.
1
2
3
BC6031S BC6031P BC6031B BC6031SQ BC6031PQ
BC6032S BC6032P BC6032B BC6032SQ BC6032PQ
BC6033S BC6033P BC6033B BC6033SQ BC6033PQ
Form No. EDCC
Page 1 of 2
Data Sheet #1300
07-10-07
BU-SB07255
EDCC
Class CC, 600Vac, 0.5 to 30A
Time-Delay Fuses
Current Limitation Curves
Time-Current Characteristic Curves– Average
Melt
Current-Limiting Effects
EDCC Apparent RMS Symmetrical Let-Through Current
Prosp.
SCC
1.25
100
140
165
210
260
290
315
340
350
390
420
525
2.2A
135
210
255
340
435
525
610
650
735 1050
785 1130
830 1210
1100 1600
15A
240
350
420
540
680
800
870
915
20A
305
25A
380
30A
1000
435
3000
440
575
580
710
5000
570
690
870
10,000
20,000
30,000
40,000
50,000
60,000
80,000
100,000
200,000
700
1000
1305
1520
1700
1820
1980
2180
2400
3050
870
1090
1300
1390
1520
1650
1780
2000
2520
1030
1150
1215
1300
1500
1600
2000
*RMS Symmetrical Amps Short-Circuit
NOTE: To calculate I (I ) multiply I value x 2.3.
RMS
p
peak
The only controlled copy of this document is the electronic read-only version maintained by Cooper Bussmann. All other copies of this document are by definition uncontrolled. This bulletin
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right,
without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, with-
out notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Form No. EDCC
07-10-07
BU-SB07255
Page 2 of 2
Data Sheet #1300
相关型号:
EDCC1.125
Electric Fuse, Time Delay Blow, 1.125A, 600VAC, 300VDC, 200000A (IR), Inline/holder
COOPER
©2020 ICPDF网 联系我们和版权申明