JDL300 [COOPER]

Electric Fuse, Time Delay Blow, 300A, 600VAC, 300VDC, 300000A (IR), Inline/holder;
JDL300
型号: JDL300
厂家: COOPER BUSSMANN, INC.    COOPER BUSSMANN, INC.
描述:

Electric Fuse, Time Delay Blow, 300A, 600VAC, 300VDC, 300000A (IR), Inline/holder

电路保护
文件: 总2页 (文件大小:321K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
JDL  
Class J 600 Volt, 70 to 600A  
Dual-Element, Time-Delay Fuses  
Dimensions (inches)  
Catalog Symbol: JDL  
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%  
rated current  
Current-Limiting  
Volts: 600Vac (or less)  
Amps: 70 to 600A  
IR: 200kA RMS Sym  
300kA RMS Sym. (self certified)  
Agency Information: CE, UL. Listed – Class J, Guide  
JDDZ, File E162363, CSA Certified, HRCI-J Class J per CSA  
C22.2 No. 248.8, Class 1422-02, File 53787  
Features  
• Lower watts loss reduces power consumption.  
• True dual-element fuses with a minimum 10 second  
time-delay at 500% overload.  
• Unique dimensions assure that another class of fuse  
with a lesser voltage rating, interrupting rating or  
current-limiting ability cannot be substituted.  
• Long time-delay minimizes needless fuse openings due  
to temporary overloads and transient surges.  
• Space-saving package for equipment down sizing.  
• Can often be sized for back-up protection against motor  
burnout from overload or single-phasing if other  
overload protective devices fail.  
Catalog Numbers (amps)  
JDL70  
JDL80  
JDL90  
JDL100  
JDL110  
JDL125  
JDL150  
JDL175  
JDL200  
JDL225  
JDL250  
JDL300  
JDL350  
JDL400  
JDL450  
JDL500  
JDL600  
• High interrupting rating to safely interrupt overcurrents  
up to 300kA (self certified).  
• High degree of current-limitation due to the fast  
speed-of-response to short-circuits.  
• Faster response to damaging short-circuit currents than  
mechanical overcurrent protective devices.  
Carton Quantity and Weight  
Carton  
Weight per Carton  
• Reduces let-through thermal and magnetic forces in  
order to protect low withstand rated components.  
Amps  
Quantity  
lbs  
kg  
70–100  
110–200  
225–400  
450–600  
5
5
1
1
1.69  
4.21  
1.67  
2.80  
0.77  
1.91  
0.76  
1.27  
• Proper sizing provides “No Damage” Type “2”  
coordinated protection for NEMA and IEC motor control  
in accordance with IEC Standard 947-4-1.  
• Dual-element fuses have lower resistance than ordinary  
fuses, hence they run cooler.  
Form No. JDL 70-600  
Page 1 of 2  
07-10-07  
BU-SB07255  
Data Sheet #1304  
JDL  
Class J 600 Volt, 70 to 600A  
Dual-Element, Time-Delay Fuses  
Current Limitation Curves  
Time-Current Characteristic Curves– Average  
Melt  
Class J Fuse Blocks (600V) Catalog Data  
Box Lug w/  
Maximum  
Amps  
Poles Retaining Clip  
Wire Size  
1/0 CU/AL  
70–100  
101–200  
201–400  
401–600  
3
1
1
1
J60100-3CR  
J60200-1CR  
J60400-1CR  
J60600-1CR  
250MCM CU/AL  
500MCM CU/AL  
(2) 500MCM CU/AL  
The only controlled copy of this document is the electronic read-only version maintained by Cooper Bussmann. All other copies of this document are by definition uncontrolled. This bulletin  
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, with-  
out notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without  
notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.  
Form No. JDL 70-600  
07-10-07  
BU-SB07255  
Page 2 of 2  
Data Sheet #1304  

相关型号:

JDL35

Electric Fuse, Time Delay Blow, 35A, 600VAC, 300VDC, 300000A (IR), Inline/holder
COOPER

JDL350

Electric Fuse, Time Delay Blow, 350A, 600VAC, 300VDC, 300000A (IR), Inline/holder
COOPER

JDL36150

Thermal Magnetic Circuit Breaker,
SCHNEIDER

JDL36175

Thermal Magnetic Circuit Breaker,
SCHNEIDER

JDL36175SA

Thermal Magnetic Circuit Breaker,
SCHNEIDER

JDL36200

Thermal Magnetic Circuit Breaker,
SCHNEIDER

JDL36200LV

Thermal Magnetic Circuit Breaker,
SCHNEIDER

JDL36225SA

Thermal Magnetic Circuit Breaker,
SCHNEIDER

JDL36250

Thermal Magnetic Circuit Breaker,
SCHNEIDER

JDL36250LC

Thermal Magnetic Circuit Breaker,
SCHNEIDER

JDL400

Electric Fuse, Time Delay Blow, 400A, 600VAC, 300VDC, 300000A (IR), Inline/holder
COOPER

JDL45

Electric Fuse, Time Delay Blow, 45A, 600VAC, 300VDC, 300000A (IR), Inline/holder
COOPER