KWS-R-60 [COOPER]

250V KWN-R and 600V KWS-R Class RK1 fuses;
KWS-R-60
型号: KWS-R-60
厂家: COOPER BUSSMANN, INC.    COOPER BUSSMANN, INC.
描述:

250V KWN-R and 600V KWS-R Class RK1 fuses

电路保护
文件: 总4页 (文件大小:1148K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
BUSSMANN  
Effective August 2015  
Supersedes July, 2015  
Technical Data 10413  
SERIES  
250V KWN-R and 600V KWS-R Class RK1 fuses  
Agency information  
•ꢀ  
CE  
•ꢀ  
UL Listed, Std. 248-12, Class RK1, Guide JDDZ,  
File E4273  
•ꢀ  
CSA Certified, C22.2 No. 248.12,  
Class 1422-02, File 53787  
250V KWN-R catalog numbers (amp)  
KWN-R-1  
KWN-R-3  
KWN-R-5  
KWN-R-6  
KWN-R-10  
KWN-R-15  
KWN-R-20  
KWN-R-25  
KWN-R-30  
KWN-R-40  
KWN-R-50  
KWN-R-60  
600V KWS-R catalog numbers (amp)  
KWS-R-1  
KWS-R-3  
KWS-R-5  
KWS-R-6  
KWS-R-10  
KWS-R-15  
KWS-R-20  
KWS-R-25  
KWS-R-30  
KWS-R-35  
KWS-R-40  
KWS-R-50  
KWS-R-60  
Catalog symbols:  
•ꢀ  
KWN-R-(amp) 250V  
•ꢀ  
KWS-R-(amp) 600V  
KWN-R and KWS-R Carton quantity  
Description:  
Amp rating  
Carton qty.  
1–60  
10  
250V KWN-R and 600V KWS-R fast-acting  
Limitron™ fuses are UL Listed as Class RK1  
fuses. They are dual voltage rated and can be  
applied at 250Vac/dc and 600Vac/dc respectively  
with interrupting ratings of 200kA AC and 20kA  
DC.  
Ratings  
•ꢀ  
Volts  
•ꢀ 250Vac/dc KWN-R  
•ꢀ 600Vac/dc KWS-R  
•ꢀ  
Amps 1-60A  
•ꢀ  
Interrupting rating  
•ꢀ 200kA AC  
•ꢀ 20kA DC  
250V KWN-R and 600V KWS-R Class RK1 fuses  
Technical Data 10413  
Effective August 2015  
Features:  
Dimensions - in:  
•ꢀ  
High DC voltage ratings for critical industrial or commercial  
applications that have specific current limitation requirements.  
250V KWN-R  
2"  
( 0.318  
•ꢀ  
10X better current limitation than basic circuit breakers and non-  
current limiting fuses helps prevent damage caused by short-  
circuit events  
200kA AC Interrupting ratings comply with NEC® Section 110.9  
•ꢀ  
for today’s large capacity systems  
0.56" ( 0.00ꢀ8  
•ꢀ  
20kA DC interrupting ratings help meet the needs of protecting  
higher ampacity DC circuits  
1/10 to 30A  
•ꢀ  
Incorporates Class R rejection feature. Installation in a rejection  
base fuse block is recommended as it helps prevent a lesser-  
rated fuse from being installed. However, both KWN-R and  
KWS-R fuses can be inserted in non-rejection type fuse holders  
to physically and electrically replace fast-acting Class H, RK1, K5,  
RK5 and other fast-acting fuses.  
3"  
( 0.318  
Recommended fuse blocks:  
Fuse amps  
1-pole  
2-pole  
3-pole  
0.ꢀ1" ( 0.00ꢀ8  
250V KWN-R  
0-30  
RM25030-1_  
RM25060-1_  
RM25030-2_  
RM25060-2_  
RM25030-3_  
RM25060-3_  
35 to 60A  
35-60  
600V KWS-R  
600V KWS-R  
0-30  
RM60030-1_  
RM60060-1_  
RM60030-2_  
RM60060-2_  
RM60030-3_  
RM60060-3_  
35-60  
5"  
( 0.31ꢀ  
See data sheet No. 10289 for details.  
Fuse reducers for Class R fuses:  
0.81" ( 0.008ꢀ  
Catalog numbers (pairs)  
Equipment  
fuse clips  
Desired fuse  
(case) size  
1/10 to 30A  
250V  
600V  
60A  
30A  
30A  
60A  
60A  
NO.263-R  
NO.213-R  
NO.216-R  
NO.226-R  
NO.663-R  
NO.216-R  
NO.616-R  
NO.626-R  
100A  
200A  
5.5"  
( 0.31ꢀ  
For additional information on Class R fuse reducers, see data sheet  
No. 1118.  
1.06" ( 0.008ꢀ  
35 to 60A  
2
Eaton.com/bussmannseries  
250V KWN-R and 600V KWS-R Class RK1 fuses  
Technical Data 10413  
Effective August 2015  
Time-current curves — average melt  
KWN-R and KWS-R  
AMP RATING  
300  
100  
10  
1
0.1  
0.01  
CURRENT IN AMPS  
3
Eaton.com/bussmannseries  
250V KWN-R and 600V KWS-R Class RK1 fuses  
Technical Data 10413  
Effective August 2015  
Current limitation curves  
KWN-R and KWS-R  
B
400,000  
100,000  
10,000  
60  
30  
A
1000  
RMS SYMMETRICAL CURRENTS IN AMPS  
A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 x SYM RMS AMPS)  
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document  
are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help  
the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or  
limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin.  
Once a product has been selected, it should be tested by the user in all possible applications.  
Eaton  
1000 Eaton Boulevard  
Cleveland, OH 44122  
Eaton.com  
Bussmann Division  
114 Old State Road  
Ellisville, MO 63021  
United States  
Eaton.com/bussmannseries  
© 2015 Eaton  
All Rights Reserved  
Printed in USA  
Eaton is a registered trademark.  
Publication No. 10413 — BU-SB15296  
August 2015  
All other trademarks are property  
of their respective owners.  

相关型号:

KWS10-12

Single output 5W ~ 15W AC-DC on-board type power supply
LAMBDA

KWS10-12

AC-DC Regulated Power Supply Module, 1 Output, 10W, SMD-5
INFINEON

KWS10-15

Single output 5W ~ 15W AC-DC on-board type power supply
LAMBDA

KWS10-15

AC-DC Regulated Power Supply Module, 1 Output, 10W, SMD-5
INFINEON

KWS10-5

Single output 5W ~ 15W AC-DC on-board type power supply
LAMBDA

KWS10-5

AC-DC Regulated Power Supply Module, 1 Output, 10W
INFINEON

KWS10A-12

Single Output 5W to 25W AC-DC PCB-Mount Power Supplies
TDK

KWS10A-12-KS

AC-DC Power Supplies
TDK

KWS10A-12-KW

AC-DC Power Supplies
TDK

KWS10A-12/KS

AC-DC Power Supplies
TDK

KWS10A-12/KW

AC-DC Power Supplies
TDK

KWS10A-15

Single Output 5W to 25W AC-DC PCB-Mount Power Supplies
TDK