LPS-RK-10SPI [COOPER]

Dual-Element, Time-Delay Fuses w/Permanent Fuse Indication; 双元件延时型保险丝W /永久熔断指示
LPS-RK-10SPI
型号: LPS-RK-10SPI
厂家: COOPER BUSSMANN, INC.    COOPER BUSSMANN, INC.
描述:

Dual-Element, Time-Delay Fuses w/Permanent Fuse Indication
双元件延时型保险丝W /永久熔断指示

电路保护
文件: 总3页 (文件大小:147K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
®
Bussmann  
®
LOW-PEAK  
LPS-RK_SPI  
Dual-Element, Time-Delay Fuses w/Permanent Fuse Indication  
6-60 Amps  
Class RK1 – 600 Volt  
Dimensional Data  
5.5"  
(± 0.31)  
5"  
(± 0.31)  
.81" (±0.008)  
1.06" (±0.008)  
6A to 30A  
35A to 60A  
Features:  
• Current-limitation for maximum short-circuit protection.  
Type 2 protection for IEC and NEMA starters when  
properly sized.  
• Permanent fuse Indication  
• High inrush current motor protection.  
• Time-delay permits 130% FLA sizing for back-up motor  
protection.  
• Protection against single-phase motor damage.  
• Low watt loss power consumption.  
• Minimum voltage for indication is 75Vac.  
Catalog Symbol: LPS-RK_SPI  
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%  
rated current  
Current-Limiting  
Ampere Rating: 6 to 60A  
Voltage Rating: 600Vac (or less)  
300Vdc (or less)  
Interrupting Rating:  
Applications:  
• Branch distribution  
• Motors  
Transformers  
• Solenoids  
ac: 300,000A RMS Sym.  
• General purpose circuits  
dc: 100,000A  
Agency Information:  
CE logo denotes compliance with European Union Low Voltage Directive  
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact  
Bussmann Application Engineering at 636-527-1270 for more information.  
UL Listed, Special Purpose**, Guide JFHR, File E56412  
CSA Certified, (200,000AIR), Class RK1 per CSA C22.2,  
No. 248.12, Class 1422-02, File 53787  
**Meets all performance requirements of UL Standard 248-12 for Class RK1 fuses.  
Catalog Symbol and Amperes  
LPS-RK-6SPI  
LPS-RK-7SPI  
LPS-RK-8SPI  
LPS-RK-9SPI  
LPS-RK-10SPI  
LPS-RK-12SPI  
LPS-RK-15SPI  
LPS-RK-17⁄Ω™SPI  
LPS-RK-20SPI  
LPS-RK-25SPI  
LPS-RK-30SPI  
LPS-RK-35SPI  
LPS-RK-40SPI  
LPS-RK-45SPI  
LPS-RK-50SPI  
LPS-RK-60SPI  
Carton Quantity and Weight  
Weight*  
Ampere  
Ratings  
Carton  
Qty.  
Lbs.  
1.6  
Kg.  
6–30  
10  
10  
0.725  
1.178  
35–60  
2.6  
*Weight per carton.  
For non-indicating version, the LPS-RK_SP  
is available. See Data Sheet: 1001  
Form No. LPS-RK_SPI  
Page 1 of 3  
Data Sheet: 1061  
8-26-04  
SB04295  
®
Bussmann  
®
LOW-PEAK  
LPS-RK_SPI  
Dual-Element, Time-Delay Fuses w/Permanent Fuse Indication  
6-60 Amps  
Class RK1 – 600 Volt  
Time-Current Characteristic Curves–Average Melt  
RMS SYMMETRICAL CURRENT IM AMPERES  
Recommended fuseblocks  
for Class R 600V fuses  
See Data Sheet: 1111  
Form No. LPS-RK_SPI  
Page 2 of 3  
Data Sheet: 1061  
8-26-04  
SB04295  
®
Bussmann  
®
LOW-PEAK  
LPS-RK_SPI  
Dual-Element, Time-Delay Fuses w/Permanent Fuse Indication  
6-60 Amps  
Class RK1 – 600 Volt  
Current-Limitation Curve  
RMS SYMMETRICAL CURRENTS IN AMPERES  
A–B=ASYMMETRICALAVAILABLE PEAK  
(2.3 x SYMM RMS AMPS)  
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is  
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change  
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained  
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.  
Form No. LPS-RK_SPI  
Page 3 of 3  
Data Sheet: 1061  
8-26-04  
SB04295  

相关型号:

LPS-RK-11/2SP

LPS-RK — 600 Vac/300 Vdc, 1⁄10-60A, dual element, time-delay fuses
EATON

LPS-RK-11/4SP

LPS-RK — 600 Vac/300 Vdc, 1⁄10-60A, dual element, time-delay fuses
EATON

LPS-RK-11/8SP

LPS-RK — 600 Vac/300 Vdc, 1⁄10-60A, dual element, time-delay fuses
EATON

LPS-RK-110SP

Dual-Element, Time-Delay Fuses
COOPER

LPS-RK-110SP

LPS-RK — 600 Vac/300 Vdc, 70-600 A, dual element, time-delay fuses
EATON

LPS-RK-110SPI

Dual-Element, Time-Delay Fuses
COOPER

LPS-RK-125SP

Dual-Element, Time-Delay Fuses
COOPER

LPS-RK-125SP

LPS-RK — 600 Vac/300 Vdc, 70-600 A, dual element, time-delay fuses
EATON

LPS-RK-125SP-TP

Electric Fuse, Time Delay Blow, 125A, 600VAC, 300VDC, 300000A (IR), Inline/holder
COOPER

LPS-RK-125SPI

Dual-Element, Time-Delay Fuses
COOPER

LPS-RK-12SP

Electric Fuse, Time Delay Blow, 12A, 600VAC, 300VDC, 300000A (IR), Inline/holder,
COOPER

LPS-RK-12SP

LPS-RK — 600 Vac/300 Vdc, 1⁄10-60A, dual element, time-delay fuses
EATON