MV155F1DBX50E [COOPER]
Electric Fuse, 50A, 15500VAC, 50000A (IR), Inline/holder;型号: | MV155F1DBX50E |
厂家: | COOPER BUSSMANN, INC. |
描述: | Electric Fuse, 50A, 15500VAC, 50000A (IR), Inline/holder |
文件: | 总5页 (文件大小:97K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
®
Bu s s m a n n
E-Ra t e d Me d iu m Vo lt a g e Fu s e s
Fo r Tra n s fo rm e r a n d Fe e d e r P ro t e c t io n
1 5 .5 k V
MV1 5 5
CATALOG SYMBOL: MV155
E-RATED MEDIUM VOLTAGE FUSES:
Meets E requirements per ANSI C37.46
Meets Full Range requirements per ANSI C37.40
FOR TRANSFORMER AND FEEDER PROTECTION
VOLTAGE RATING: 15.5 kV
INTERRUPTING RATING: 50 kA Maximum Sym.
CURRENT LIMITING
CONSTRUCTION: Silver ribbon element surrounded by
silica filler housed in a fiberglass tube and plated endcaps.
An epoxy paint protects the fuse tube from the surround-
ing environment.
Electrical Characteristics
FEATURES:
Ampere
Rating
Min/
Melt I2t
Max.
Physical Size (inches)
• Standard Clip Center Lengths and Barrel Diameters.
The new line of Bussmann 15.5 kV medium voltage fuses
have standard clip center distances of 15 or 18 inches
and barrel diameters of 2 or 3 inches which allow fuses to
retrofit exisiting hardware.
Part Numbers†
Clear I2t
Length
Dia. Clip Center Barrels
MV155F1CBX5E
MV155F1CBX7E
5A
7A
180
2900
8000
850
MV155F1CBX10E 10A
MV155F1CBX15E 15A
MV155F1CBX20E 20A
MV155F1CBX25E 25A
MV155F1CBX30E 30A
MV155F1DBX10E 10A
MV155F1DBX15E 15A
MV155F1DBX20E 20A
MV155F1DBX25E 25A
MV155F1DBX30E 30A
MV155F1DBX40E 40A
MV155F1DBX50E 50A
MV155F1DBX65E 65A
MV155F1DBX80E 80A
MV155F1DBX100E 100A
MV155F2DBX125E 125A
850
8000
2070
2370
4650
9490
850
12000
23000
31000
45000
8000
18.75
2
15
1
• Blown Fuse Indication with Indicator.
• 100% Tested for Reliability. All medium voltage fuses
2
are pulsed twice with 90% of their minimum melt I t to
guarantee undamaged elements. This test does not affect
undamaged elements. A damaged element completely
2070
2370
4650
9490
9490
13600
30700
54600
116200
123000
12000
23000
31000
45000
45000
90000
181000
270000
600000
677000
2
opens when subjected to 90% of the minimum melt I t,
allowing it to be detected by a resistance check.
• Full Range Fuses. Bussmann medium voltage fuses
provide full range protection and are capable of interrupt-
ing fault currents of 50,000A sym.
• Time Current Curves and Dimensional Data:
MV155F1CB series, see page 2;
MV155F1DB and MV155F1DC series, see page 3.
• Peak Arc Voltage Curves and Peak Let-Through
Data, see page 4.
18.75
3
15
1
MV155F2DBX150E 150A
MV155F2DBX175E 175A
MV155F2DBX200E 200A
MV155F1DCX65E 65A
MV155F1DCX80E 80A
MV155F1DCX100E 100A
MV155F2DCX125E 125A
MV155F2DCX150E 150A
MV155F2DCX175E 175A
MV155F2DCX200E 200A
218700
314700
465100
30700
1287000
1689000
2405000
181000
270000
600000
677000
1287000
1689000
2405000
18.75
21.75
21.75
3
3
3
15
18
18
2
1
2
• Fuse Clips, see page 4.
54600
116200
123000
218700
314700
465100
† To order with the optional striker pin, see Part Number Construction chart below.
Part Number Construction
Medium Voltage
Voltage Rating
Number of Barrels
Barrel Diameter
Clip Center Distance
Indication Type Ampere Rating
Example
MV
155
F
1
C
B
X
5E
055 = 5.5 kV
155 = 15.5 kV
F = Full Range
1
2
C = 2 inches
D = 3 inches
A = 12 inches
B = 15 inches
C = 18 inches
X = Indicator only
S = Striker Pin
Form No. MV155
Page 1 of 5
Data Sheet: 6701
2-26-03
SB03044
®
Bu s s m a n n
E-Ra t e d Me d iu m Vo lt a g e Fu s e s
Fo r Tra n s fo rm e r a n d Fe e d e r P ro t e c t io n
1 5 .5 k V - MV1 5 5 F1 CB S e rie s
MV1 5 5
Time-Current Characteristics
Total Clearing
Time-Current Characteristics
Minimum Melt
AMPERE
RATING
AMPERE
RATING
100
100
10
10
1
1
.1
.1
.01
.01
CURRENT IN AMPERES
CURRENT IN AMPERES
MV155F1CBX
18.61"
17.77"
2.03"
.21"
.63"
INDICATOR
Ø2.095"
POSITION OF BLOWN
INDICATOR AFTER
OPERATING.
15.00"
CLIP CENTER
Form No. MV155
Page 2 of 5
2-26-03
SB03044
Data Sheet: 6701
®
Bu s s m a n n
E-Ra t e d Me d iu m Vo lt a g e Fu s e s
Fo r Tra n s fo rm e r a n d Fe e d e r P ro t e c t io n
1 5 .5 k V - MV1 5 5 F1 DB & MV1 5 5 F1 DC S e rie s
MV1 5 5
Time-Current Characteristics
Minimum Melt
Time-Current Characteristics
Total Clearing
1000
100
10
1000
100
10
1
1
.1
.1
DOUBLE BARREL
FUSE ASSY.
DOUBLE BARREL
FUSE ASSY.
SINGLE BARREL
FUSE ASSY.
SINGLE BARREL
FUSE ASSY.
.01
.01
10
CURRENT IN AMPERES
CURRENT IN AMPERES
MV155F1DBX
Double Barrel
Dimensions
18.61"
17.77"
.21"
2.40"
.63"
INDICATOR
Ø3.38"
Ø1.30"
Ø2.96"
POSITION OF BLOWN
INDICATOR AFTER
OPERATING.
15.00"
CLIP CENTER
3.50"
6.68"
MV155F1DCX
21.61"
20.77"
2.40"
.21"
.63"
INDICATOR
Ø2.96"
Ø1.30"
Ø3.38"
POSITION OF BLOWN
INDICATOR AFTER
OPERATING.
18.00"
CLIP CENTER
Form No. MV155
Page 3 of 5
2-26-03
Data Sheet: 6701
SB03044
®
Bu s s m a n n
E-Ra t e d Me d iu m Vo lt a g e Fu s e s
MV1 5 5
Fo r Tra n s fo rm e r a n d Fe e d e r P ro t e c t io n
1 5 .5 k V - P e a k Arc Vo lt a g e & P e a k Le t -Th ro u g h Da t a
Max. Peak Let-Through Current Curves
MAXIMUM PEAK ARC VOLTAGE FOR
"E" RATED FULL RANGE POWER FUSE
(BUSSMANN)
B
100
50
40
200A
175A
150A
125A
100A
80A
65A
50A
30&40A
10
25A
20A
15A
07&10A
30
20
05A
1
10
0
A
.1
10
.1
1
AVAILABLE CURRENT IN KILOAMPERES (RMS Symmetrical)
CIRCUIT VOLTAGE (KV)
Recommended Fuse Clips for Medium Voltage Fuses
Part
No.
Fuse
Diameter
Clip Dimensions
A
B
C
D
E
F
G
A3354710
A3354730
2”
3”
3.74” 1.97” 2.00” 1.18” 4.53” 1.50” .39”
4.13” 2.44” 3.00” 1.18” 5.63” 1.50” .39”
Fuseclips are for single barrel applications up to 200E only.
C
A
G
F
E
D
B
Form No. MV155
Page 4 of 5
Data Sheet: 6701
2-26-03
SB03044
®
Bu s s m a n n
E-Ra t e d Me d iu m Vo lt a g e Fu s e s
Fo r Tra n s fo rm e r a n d Fe e d e r P ro t e c t io n
1 5 .5 k V - Cro s s Re fe re n c e Da t a
MV1 5 5
Catalog Number Cross Reference
Bussmann
Gould (New)
Gould (Old)
Westinghouse
General Electric
---- ----
MV155F1CBXxxxE
MV155F1DBXxxxE
MV155F1DCXxxxE
MV155F2DCXxxxE
A155F1CORO-xxxE
A155F1DORO-xxxE
A155F1DORO-xxxE
A155F2DORO-xxxE
A1550X-xxxE-1B
A1550X-xxxE-1F
A1550X-xxxE-1D
A1550X-xxxE-1D
----
15HLE-xxxE
----
9F62DDDxxx 9F60FMHxxx
----
----
----
----
----
Bussmann Medium Voltage Cross Reference
Clip
Center
Overall
Length
Sym.
kA
E Ratings Available
S = Single Barrel D = Double Barrel
kV
Dia.
Manufacturer
5
S
S
7
S
S
10 15 20 25 30 40 50 65 80 100 125 150 175 200 250 300 350 400 450
2”
15”
18-3/4”
17-3/100” 50
50
Bussmann
Gould†
Bussmann
Gould†
Westinghouse†
General Electric†
Bussmann
Gould†
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
15.5 kV
18-3/4”
18-7/8”
18-7/8”
18-7/8”
21-3/4”
21-3/4”
50
40
50
40
50
50
S
S
S
S
S
S
S
S
S
D
S
S
S
S
S
D
S
S
S
S
S
D
S
S
S
S
D
D
D
D
D
15.5 kV
15.5 kV
3”
3”
15”
18”
S
D
S
D
D
S
D
D
D
D
D
D
D
D
D
D
D
D
† Gould, Westinghouse and General Electric are General Purpose Fuses.
Current-limiting medium voltage fuses are classified into three categories:
Full Range - defined by ANSI as “a fuse capable of interrupting all currents from the maximum rated interrupting current down to
the minimum continuous current that causes melting of the fusible element(s), when the fuse is applied at the maximum ambient
temperature specified by the manufacturer.” It is able to interrupt any normal 60 cycle current that will melt its element.
General Purpose - defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting
current down to the current that causes melting of the fusible element in one hour.” Not all currents fall within this range. It is
possible to receive an overcurrent lower than the value given by the one hour criterion.
Back-up - defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting current
down to the rated minimum interrupting current.” The minimum rated interrupting current is the lowest current that the fuse will be
able to clear properly. This creates a need to place a low current interrupting device in series with the back-up rated fuse.
All Bussmann MV series medium voltage fuses are E-rated and offer Full Range Protection.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled.This bulletin is intended to clear-
ly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any prod-
ucts and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected,
it should be tested by the user in all possible applications.
Form No. MV155
Page 5 of 5
2-26-03
SB03044
Data Sheet: 6701
相关型号:
MV155F1DBX65E
Electric Fuse, Medium Blow, 65A, 15500VAC, 15500VDC, 50000A (IR), Inline/holder
COOPER
MV155F1DCX65E
Electric Fuse, Medium Blow, 65A, 15500VAC, 15500VDC, 50000A (IR), Inline/holder
COOPER
MV155F1DCX80E
Electric Fuse, Medium Blow, 80A, 15500VAC, 15500VDC, 50000A (IR), Inline/holder
COOPER