SC-30 [COOPER]
SC Class G, 600Vac/480Vac, 1â2-60A;![SC-30](http://pdffile.icpdf.com/pdf2/p00347/img/icpdf/SC-30_2137833_icpdf.jpg)
型号: | SC-30 |
厂家: | ![]() |
描述: | SC Class G, 600Vac/480Vac, 1â2-60A 电路保护 |
文件: | 总3页 (文件大小:401K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
![](http://public.icpdf.com/style/img/ads.jpg)
BUSSMANN
Effective December 2015
Supersedes August 2013
Technical Data 1024
SERIES
SC Class G, 600Vac/480Vac, 1⁄2-60A
size-rejecting fuses
Catalog numbers (amps)
SC-1⁄2
SC-1
SC-6
SC-30
SC-35
SC-40
SC-45
SC-50
SC-60
SC-7
SC-1-1⁄2
SC-2
SC-8
SC-10
SC-12
SC-15
SC-20
SC-25
SC-2-1⁄2
SC-3
SC-4
SC-5
Carton quantity:
Amp rating
1/2-20
Carton qty.
4
2
25–60
Dimensions - in (mm):
Catalog symbol:
•ꢀ
SC-(amp)
0.41”
(10.41mm)
A
(Length)
Description:
Basic protection Class G size-rejecting, current
limiting fuses. 1/2 to 6A Fast-acting, 7 to 60A
time-delay.Time-delay – 12 seconds (minimum)
at 200% of rated current.
Amp rating
1/2-15
A
1.31 (33.3)
1.41 (35.8)
1.62 (41.1)
2.25 (57.1)
20
Specifications:
25 to 30
35 to 60
Ratings
•ꢀ
Volts
Features:
•ꢀ 600Vac/170Vdc (½-20A)
•ꢀ 480Vac/300Vdc (25-60A)
•ꢀ
Meets basic protection requirements of
NEC®, Canadian Electrical Code (CEC), UL
and CSA.
•ꢀ
Amps 1/2-60A
•ꢀ
IR
•ꢀ
•ꢀ
•ꢀ
•ꢀ
•ꢀ
•ꢀ
Most economical overcurrent protection
solution compared to circuit breakers.
•ꢀ 100kA Vac RMS Sym.
•ꢀ 10kA Vdc
For use in various non-demanding, general
purpose applications.
Agency information
Compact branch-circuit units with high
interrupting rating and current-limitation.
UL® Listed, Std. 248-5, Class G,
Guide JDDZ, File E4273
CSA® Certified, C22.2 No. 248.5,
Class 1422-01, File 53787
•ꢀ
With up to a 600V rating, they can be used in
120/208V, 120/240V, and 277/480V circuits.
•ꢀ
Size rejection by length helps prevent
overfusing.
•ꢀ
CE
Fuses 7 amps and above have a degree of
overload time-delay that permits them to
pass temporary overloads.
•ꢀ
RoHS compliant
Technical Data 1024
SC Class G 600Vac/480Vac, 1⁄2-60A size-rejecting fuses
Effective December 2015
Time-current curves - average melt:
Amprating
300
100
10
1
0.1
0.01
2000
0.7 1
10
100
10 00
Currentinamps
2
Eaton.com/bussmannseries
SC Class G 600Vac/480Vac, 1⁄2-60A size-rejecting fuses
Technical Data 1024
Effective December 2015
Fo
Current-limitation curves:
Recommended fuse blocks:
Fuse amps
1⁄2-15
20
1-Pole
2-Pole
3-Pole
B
10,000
60
BG30011_
BG30021_
BG30031_
G30060-1C_
BG30012_
BG30022_
BG30032_
G30060-2C_
BG30013_
BG30023_
BG30033_
G30060-2C_
30
20
15
25-30
35-60
For additional information on the BG and G Series of Class G
fuse blocks, see data sheet No. 1006.
1000
A
100
RMS symmetrical currents in amps
A - B = Asymmetrical Available peak (2.3 x Sym. RMS amps)
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
For Eaton’s Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton and Bussmann are valuable
trademarks of Eaton in the US and other
countries.You are not permitted to use the
Eaton trademarks without prior written
consent of Eaton.
Eaton.com/bussmannseries
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
CSA is a registered trademark of the
Canadian Standards Group.
Follow us on social media to get the
latest product and support information.
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. 1024 – BU-SB13733
December 2015
NEC is a registered trademark of the
National Fire Protection Association, Inc.
UL is a registered trademark of the
Underwriters Laboratories, Inc.
3
相关型号:
©2020 ICPDF网 联系我们和版权申明