ESM-06-221-D [COSEL]
Single Phase EMI Filter, 250V, 60HzHz, ROHS COMPLIANT PACKAGE;型号: | ESM-06-221-D |
厂家: | COSEL CO., LTD. |
描述: | Single Phase EMI Filter, 250V, 60HzHz, ROHS COMPLIANT PACKAGE LTE |
文件: | 总2页 (文件大小:356K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Ordering information
Small, Low leakage current type : Screwless terminal type (1-Stage filter)
ESM -10 -000 -O
ESM series
1
2
3
4
1Model Name
2Rated Current
3Line to ground capacitor code:See table 1.1.
R
table1.1 Line to ground capacitor code
Line to ground
capacitor
(nominal value)
Not Provided
Leakage Current
(Input 125/250V 60Hz)
Code
000
101
221
331
471
5
A/ 10 A max
12.5 A/ 25 A max
25 A/ 50 A max
37.5 A/ 75 A max
50
A/100 A max
100pF
220pF
330pF
470pF
When the line to ground capacitor code is
different, the attenuation characteristic is
different.
*
4Options
D:DIN rail installation type
The dimensions change when the option is set.
Refer to External view.
*
DIN rail installation type is option
Electric cable is not appended.
Features of ESM series
Small, Low leakage current type(1-Stage filter)
-Small EMI/EMC Filters that change input-output terminal and protection earth terminal of EA series into
screwless terminal type
-Single Phase 250VAC
-Torque management is unnecessary with screwless
Specifications
No.
Items
ESM-03-000
ESM-06-000
ESM-10-000
ESM-16-000
1
Rated Voltage[V]
AC 1f250 / DC250
2
Rated Current[A]
3
6
10
16
3
Test Voltage (Terminal-Mounting Plate)
2,500 VAC (Cutoff Current = 20mA), 1minute at room temperature and humidity
4
Isolation Resistance (Terminal-Mounting Plate) 500 VDC 500MWmin at room temperature and humidity
5
Leakage current 125/250V 60Hz
DC resistance
5 A/10 A max
6
180mWmax
110mWmax
40mWmax
20mWmax
7
Safety agency approval temperatures
Operating temperature
Operating humidity
-25 to +85C(Refer to Derating Curve)
-40 to +85C(Refer to Derating Curve)
20 to 95%RH (Non condensing)
8
9
10
11
12
13
14
Storage temperature/humidity
Vibration
-40 to +85C/20 to 95%RH (Non condensing)
2
10 to 55Hz, 19.6m/s (2G), 3min. Period, 1hour each X, Y and Z axis
2
Impact
196.1m/s (20G), 11ms Once each X, Y and Z axis
Safety agency approvals
Case size (without projection) /Weight
UL1283, CSA C22.2 No.8 (C-UL), DIN EN60939 VDE0565 Teil3-1, ENEC (At only AC input)
39X30X85 mm [1.54X1.18X3.35 inches] (WXHXD) /170g max (Option : -D refer to external view)
Circuit Diagram
Derating Curve
Case
100
80
3
1
60
CY
LINE
LOAD
40
CY
4
2
20
0
-40
-30
-20
40
50 55 60
70
80
90
Ambient Temperature [C]
: Mounting Plate
CY : Line to ground capacitor
EA/ES-6
ESC,ESM,ESP series
External view
Standard Type
85
[3.35]
78
[3.07]
76.2
Screwless
[3]
Mounting Plate
Terminal
0.5
[2.95]
75
Input
26.5
[1.04]
24
Screwless
Terminal
Terminal
6-Check hole f2.1
[0.08]
Output
Protection Earth
[0.94]
Terminal
Name Plate
Screwless
Terminal
Input
Screwless
Terminal
Terminal
Protection Earth
2-f4.8
Output
[0.19]
Mounting Hole
6-Connection/release button
Terminal
Strip Gauge
¶ Tolerance : 1 [ 0.04]
¶ Weight : 170g max
¶ Mounting Plate : Iron (surface finishing:nickel plating) t=1.0 [0.04]
¶ Case : PBT
¶ Dimensions in mm, [ ]=inches
¶ Refer to instruction manual for details.
DIN rail installation Type
+2
-1
[0.33]
8.5
85
[3.35]
78
Screwless
Terminal
Mounting Plate
[3.07]
76.2
[3]
Input
Screwless
Terminal
26.5
[1.04]
Terminal
6-Check hole f2.1
Protection Earth
Output
24
[0.08]
[0.94]
Terminal
Name Plate
Screwless
Terminal
Input
Screwless
Terminal
Terminal
Protection Earth
6-Connection/release button
Output
Terminal
Strip Gauge
¶ Tolerance : 1 [ 0.04]
¶ Weight : 170g max
¶ Mounting Plate : Iron(surface finishing:nickel plating) t=1.0 [0.04]
¶ Case : PBT
¶ Dimensions in mm, [ ]=inches
¶ Refer to instruction manual for details.
DIN rail
Note when installing the EMI/EMC
¡
Filter on a DIN rail.
When the EMI/EMC Filter is grounded through
the DIN rail, the proper noise attenuation may not
be achieved.
DIN rail
Name Plate
Be sure to connect the protection earth (PE) of
the EMI/EMC Filter body to the earth.
It can connect the ground to either one only.
EA/ES-8
相关型号:
©2020 ICPDF网 联系我们和版权申明