NBC-16-681-D [COSEL]
LINE FILTER 250VDC/VAC 16A DIN;型号: | NBC-16-681-D |
厂家: | COSEL CO., LTD. |
描述: | LINE FILTER 250VDC/VAC 16A DIN LTE |
文件: | 总2页 (文件大小:445K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Ordering information
Single phase input type (2-Stage filter)
NBC -10 -472 -O
NBC/NBM series
1
2
3
4
1Series Name
2Rated Current
R
3
Line to ground capacitor code: Refer to table 1.1.
table1.1 Line to ground capacitor code
NBCNBM
Line to ground
capacitor
(nominal value)
Leakage Current
(Input 125/250V 60Hz)
Code
000
101
221
331
471
681
102
222
332
472
●
●
●
●
●
5
12.5
25
37.5
50
75.5
A / 10 A max Not Provided
A / 25 A max
A / 50 A max
A / 75 A max
A / 100 A max
A / 150 A max
100pF
220pF
330pF
470pF
680pF
●
●
●
●
●
0.13 mA / 0.25mA max
0.25 mA / 0.5 mA max
0.38 mA / 0.75mA max
0.5 mA / 1.0 mA max
1,000pF
2,200pF
3,300pF
4,700pF
When the line to ground capacitor code is
different, the attenuation characteristic is different.
*
DIN rail installation type is option
The terminal cover is retracted inside the unit
4Option
D:DIN rail installation type
The dimensions change when the option is set.
Refer to External view.
*
Features of NBC/NBM series
-Single Phase 250VAC (2-Stage filter)
-Quick and easy push-down terminal
Just connect the wires, push-down and tighten the screws with a screwdriver
NBC :High-attenuation type from 150kHz to 1MHz
NBM:Low leakage current, Withstand voltage 4,000 VAC
Specifications
NBC-06-472
NBM-06-471
AC 1f250 / DC250
6
NBC-10-472
NBM-10-471
NBC-16-472
NBM-16-471
NBC-20-472
NBM-20-471
NBC-30-472
NBM-30-471
No.
Items
1
2
Rated Voltage[V]
Rated Current[A]
10
16
20
30
NBC : 2,500 VAC (Cutoff Current = 20mA), 1minute at room temperature and humidity
NBM : 4,000 VAC (Cutoff Current = 20mA), 1minute at room temperature and humidity
3
Test Voltage (Terminal-Mounting Plate)
4
5
Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100MWmin at room temperature and humidity
Leakage current
Refer to table 1.1
6
Voltage drop
1.0V max
7
8
9
10
11
12
13
14
Safety agency approval temperatures
Operating temperature
Operating humidity
Storage temperature/humidity
Vibration
-25 to +85C(Refer to Derating Curve)
-40 to +85C(Refer to Derating Curve)
20 to 95%RH (Non condensing)
-40 to +85C/20 to 95%RH (Non condensing)
2
10 to 55Hz, 19.6m/s (2G), 3min. Period, 1hour each X, Y and Z axis
2
Impact
196.1m/s (20G), 11ms Once each X, Y and Z axis
Safety agency approvals
Case size (without projection) /Weight
UL1283, CSA C22.2 No.8 (C-UL), DIN EN60939 VDE0565 Teil3-1, ENEC (At only AC input)
53X41X92 mm [2.09X1.61X3.62 inches] (WXHXD) /270g max (Option : -D refer to external view)
Circuit Diagram
Derating Curve
Case
100
80
60
40
20
0
3
1
CY
LOAD
LINE
CY
2
4
-40
-30
-20
40
50 55 60
70
80
90
Ambient Temperature [C]
CY : Line to ground capacitor
: Mounting Plate
May 11, 2021
NB-3
NBC/NBM series
External view
As this product is adopted push-down type terminal block, this appearance is as follows.
1The terminal cover is retracted inside the unit.
2The screws for connecting the terminals are held in the up right position.
Standard Type
92
[3.62]
2.5
[0.1]
30.5
[1.2]
0.5
[3.23]
82
2-f4.8
2-Protection Earth
8
[0.31]
80
[0.19]
[3.15]
Mounting Hole
Input
Terminal
Output
Name Plate
Terminal
Output
Input
Terminal
Terminal
6-M4
Mounting Plate
Terminal cover
Terminal cover
¶ Closed the terminal cover
¶ Tolerance : 1 [ 0.04]
¶ Weight : 270g max
¶ Mounting Plate : Iron (surface finishing:nickel plating) t=1.0 [0.04]
¶ Case : PBT
¶ Dimensions in mm, [ ]=inches
¶ Terminal block screw tightening torque M4:1.6N-m (16.9kgf-cm) max
DIN rail installation Type
2.5
[0.1]
30.5
[1.2]
92
[3.62]
80
1.5
[0.32]
2-Protection Earth
8.2
8
[0.31]
[3.15]
Input
Terminal
Output
Name Plate
Terminal
Output
Input
Terminal
Terminal
6-M4
Terminal cover
Mounting Plate
Terminal cover
¶ Closed the terminal cover
¶ Tolerance : 1 [ 0.04]
¶ Weight : 270g max
¶ Mounting Plate : Iron (surface finishing:nickel plating) t=1.0 [0.04]
¶ Case : PBT
¶ Dimensions in mm, [ ]=inches
¶
Terminal block screw tightening torque M4:1.6N-m (16.9kgf-cm) max
DIN rail
Note when installing the EMI/EMC
¡
Filter on a DIN rail.
DIN rail
When the EMI/EMC Filter is grounded through
the DIN rail, the proper noise attenuation may not
be achieved.
Name Plate
Be sure to connect the protection earth (PE) of
the EMI/EMC Filter body to the earth.
It can connect the ground to either one only.
May 11, 2021
NB-4
相关型号:
©2020 ICPDF网 联系我们和版权申明