DRC_17 [CRYDOM]
DIN Rail Mount;型号: | DRC_17 |
厂家: | CRYDOM INC., |
描述: | DIN Rail Mount |
文件: | 总11页 (文件大小:1965K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
DIN Rail Mount
DataSheet
DRC Series with
EMR Auxiliary Contacts
Start / Stop Reversing
• 7.6 Amp AC Semiconductor Motor Controller
• Load voltage range up to 600 VAC
• Fits standard 35mm DIN Rail
• LED input status indicator
• AC or DC control
• Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output
•
C-UL-US Listed, IEC Rated, CE & RoHS Compliant, Horsepower Rated
• Built-in Overvoltage Protection
• Ultra-efficient thermal management design (Patented)
See DRC Series models with Solid State Auxiliary Contacts
Solicon DRC Series with EMR Auxiliary Contacts are Solid State instantaneously upon application of the control voltage unless an
Contactors intended for frequently switching on and off three instantaneous change of direction is commanded, then it will
phase loads up to 5 HP, 600 VAC 7.6 Amps. They are available in delay the direction change by 100msec in order to prevent
both contactor versions DRC3P and reversing contactor versions simultaneous forward and reverse operations.
DRC3R.
All the models of Solicon DRC Series with EMR Auxiliary Contacts
The Solicon Contactor DRC3P is available in either instantaneous combine the benefits and advantages of a solid state contactor
turn-on (for Motor Control) or zero voltage turn-on (for Resistive with the functionality and simplicity of use of an
Loads). It is available in either 2 or 3 controlled leg versions. The electromechanical contactor thanks to the proprietary thermal
2 legs control version is particularly suitable for motor control management technology (Patented) and complete electrical
circuits where the neutral conductor is not utilized.
insulation (no grounding required); the embedded EMR auxiliary
contacts, normally open and/or normally closed, are intended to
be used at 110VDC/140VAC. All models include overvoltage
protection.
The Solicon Reversing Contactor DRC3R includes an interlock
control that allows only off, forward and reverse operation in a
safe mode while providing high space saving; it switches
PRODUCT SELECTION
Control Voltage
24 VAC/DC
1 NO + 1NC Auxiliary Contact
2 NO Auxiliary Contact
DRC3P48D440, DRC3P60D440
DRC3R40E440, DRC3R48E440
DRC3P48D433, DRC3P60D433
24 VDC
AVAILABLE OPTIONS
Operating Voltage
40: 400 VAC
Load Current per Phase
4: 7.6 Amp FLA
(3R function only)
48: 480 VAC
60: 600 VAC
(x2 Controlled Legs
& 3R function);
4.8 Amp FLA
Switching Mode
(3P function only)
Blank: Zero Voltage Turn-On
(3P function only)
Series
(x3 Controlled Legs only) R: Instantaneous Turn-On
4
DRC 3P 48
D
33
R
2
Function
Control Voltage
D: 18-30 VAC/DC
(3P function only)
E: 18-30 VDC
Auxiliary Contacts,
N.O. - N.C.
Controlled Legs
(3P function only)
3P: Contactor
3R: Reversing Contactor
33: 1 Normally Open EMR ; Blank: 3 Controlled Legs
1 Normally Closed EMR 2: 2 Controlled Legs
(3P function only)
(3R function only)
40: 2 Normally Open EMR
Required for valid part number
For options only and not required for valid part number
FDE-07-01 REV. A
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
DataSheet
(1)
OUTPUT SPECIFICATIONS
Description
DRC3P48D4x DRC3P48D4x2 DRC3P60D4x DRC3P60D4x2 DRC3R40E440 DRC3R48E440
Operating Voltage (47-63Hz) [VRMS]
Transient Overvoltage [Vpk] (2)(3)
Maximum Off-State Leakage Current @ Rated Voltage [mARMS]
Maximum Off-State dv/dt @ Maximum Rated Voltage [V/µsec]
48-530
1200
3.0
48-530
1200
3.0
48-600
1200
1.0
48-600
1200
1.0
48-415
1200
5.5
48-510
1600
5.5
500
500
500
500
500
500
Load Current, General Use UL508 /AC51 @40°C [ARMS] (4)
Load Current, Motor Controller UL508 /AC-53a @480VAC [ARMS] (4)
Minimum Load Current [ARMS]
5
4.8
0.15
7.6
7.6
0.15
5
4.8
0.15
7.6
7.6
0.15
7.6
7.6
0.15
7.6
7.6
0.15
Maximum Surge Current [Apk] 1 Cycle 60Hz
750
750
750
750
750
625
Maximum Surge Current [Apk] 1 Cycle 50Hz
716
2330
2560
716
2330
2560
716
2330
2560
716
2330
2560
716
2330
2560
597
1621
1779
Maximum I2t for Fusing (8.33msec)[A2sec]
Maximum I2t for Fusing (10msec)[A2sec]
Maximum On-State Voltage Drop @ Rated Current [VRMS]
Minimum Power Factor (with Maximum Load)
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 240 VAC
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 400 VAC
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 480 VAC
Motor Ratings @ 600 VAC [HP/kW]
1.15 per channel
1.15 per channel
1.15 per channel
0.7
1.15 per channel
0.7
1.3 per channel
1.3 per channel
0.5
1/.75
2/1.5
3/2.2
-
0.5
2/1.5
3/2.2
5/3.7
-
0.5
2/1.5
3/2.2
-
0.5
2/1.5
3/2.2
5/3.7
-
1/.75
2/1.5
3/2.2
3/2.2
2/1.5
3/2.2
5/3.7
5/3.7
-
INPUT SPECIFICATIONS (1)
Description
Control Voltage Range
Option D
18-30 VAC / VDC
Option E
18-30 VDC
Minimum Turn-On Voltage (5)
Must Turn-Off Voltage
18 VAC / VDC
4 VAC / VDC
18 VDC
4 VDC
Minimum Input Current (for on-state) [mA]
Maximum Input Current [mA]
Nominal Input Impedance [Ohms]
Maximum Delay to Turn-On [msec] (6)
Maximum Turn-Off Time [msec] (7)
12.5
32
12.5
32
Current Regulated
100 30
Current Regulated
20
30
20
AUXILIARY CONTACTS(1)
Description
Maximum Operating Voltage
Transient Overvoltage [Vpk]
Maximum Load Current [Adc/Arms] (8)
Maximum Contact Rating [W] (8)
Normally Open Suffix 40 [3P] Normally Closed / Normally Open Suffix 33 Normally Open Suffix 40 [3R]
110VDC/ 140VAC
110VDC/ 250VAC
250
110VDC/ 140VAC
250
0.5/0.35
10/7
250
0.5/0.35
10/7
0.3/0.25
33/62.5
Minimum Load Current [mA]
Maximum Delay to Turn-On [msec]
10
20
10
20
10
100 30
Maximum Turn-Off Time [msec]
30
20
108
105
30
20
108
105
20
Maximum Delay to Turn-On [msec]
100 30
Mechanical Life Expectancy [Ops.]
Electrical Life Expectancy [Ops.]
108
105
GENERAL SPECIFICATIONS(1)
Description
Parameters
Dielectric Strength, Input/Output/Base (50/60Hz) (9)
Minimum Insulation Resistance (@ 500 VDC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range (10)
Ambient Storage Temperature Range
3750 Vrms
109 Ohms
20 pF
-20 to 60 °C
-30 to 85 °C
Weight (typical)
2 Controlled Legs (6.9 oz [197 g]) / 3 Controlled Legs (8.0 oz [228 g])
Housing Material
UL94 V-0
Housing Color
Black and Light Gray
LED Status Indicator (color) (11)
Short Circuit Current Rating (12)
Pollution Degree
Forward (Green) / Reverse (Amber)
100kA
2
Protection Degree (13)
Humidity
IP20
85% non-condensing
Control and Auxiliary Contact Terminal Screw Torque Range (lb-in/Nm)
Load Terminal Screw Torque Range (lb-in/Nm)
Input Terminal Wire Capacity
12 / 1.36
15 / 1.7
18-12 AWG (IEC 1-4 mm2) (stranded /solid)
18-10 AWG (IEC 1-6 mm2 ) (stranded /solid)
Output Terminal Wire Capacity
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
DataSheet
(14)
THERMAL DERATE INFORMATION
DRC3P (3 controlled legs)
DRC3P (2 controlled legs) & DRC3R
Single unit (15)
Multiple units
Single unit (15)
Multiple units
6
5
4
3
2
1
0
8
7
6
5
4
3
2
1
0
20
30
40
50
60
20
30
40
50
60
Ambient Temperature (ºC)
Ambient Temperature (ºC)
EQUIVALENT CIRCUIT BLOCK DIAGRAMS/WIRING DIAGRAM
(16)
DRC3P CONTACTOR
DRC3R REVERSING CONTACTOR(17)
DRC3Pxx433
DRC3Pxx440
DRC3Rxx440
48-530 VAC, 50-60 Hz
48-600 VAC, 50-60 Hz
48-415 VAC, 50 - 60 Hz
48-510 VAC, 50 - 60 Hz
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
Short circuit and overload
current protection (see page 5)
Short circuit and overload
current protection (see page 5)
/ >
/ >
/ >
/ >
/ >
/ >
/ >
/ >
/ >
L1
A3
L2
L3
L1
L2
L3
L1
L2
L3
13
23
A1
13
21
A1
13
23
A1
CONTROL
INPUT
(Forward)
CONTROL
INPUT
(Reverse)
DRC3RXXX440XX
DRC3PXXX433XX
DRC3PXXX440XX
IND. CONT. EQ.
IND. CONT. EQ.
IND. CONT. EQ.
CONTROL
INPUT
CONTROL
INPUT
XXXX
INPUT
STATUS
XXXX
XXXX
INPUT
STATUS
INPUT
STATUS
14
24
A2
14
22
A2
14
24
A2
CONTROL
INPUT
T1
T2
T3
T1
T2
T3
T1
T2
T3
(Common)
Motor Controller /
AC-53a Application
T1
T2
T3
T1
T2
T3
T1
T2
T3
General Use /
AC-51 Application
Motor Controller /
AC-53a Application
T1
T2
T3
T1
T2
T3
T1
T2
T3
M
3
M
Overload current
protection needs to
be considered
3
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
DataSheet
EQUIVALENT CIRCUIT BLOCK DIAGRAMS/WIRING DIAGRAM
DRC3R
DRC3P
(3 controlled legs model)
Main Circuit
DRC3P
(2 controlled legs model)
Main Circuit
Reverse
Forward
Forward
13
Reverse
L1
L2
L3
A3
L1
L2
L3
A1
L1
L2
L3
A1
L1
L2
L3
A1
23
14
24
T1
T2
T3
A2
T1
T2
T3
A2
T1
T2
T3
A2
T3
T1
T2
A2
DRC3Rxx440
models only
DRC3Pxx440
(2 Normally Open)
DRC3Pxx433
(1 Normally Open - 1 Normally Closed)
Auxiliary Contacts
Auxiliary Contacts
13 23
13 21
14 24
14 22
INSTALLATION INSTRUCTIONS
To install on DIN rail
Install the contactor on the DIN rail (as shown in fig.1).
Wire the contactor to the input side. AWG #18 (1 mm2) minimum, AWG
#12 (4 mm2) x 2 maximum.
Wire the contactor to the output side. AWG #18 (1 mm2) minimum, AWG
#10 (6 mm2) x 2 (stranded/solid) maximum.
To remove from
DIN rail
Maximum recommended terminal screw torque input 12 lb-in (1.36 Nm)
& output 15 lb-in (1.7 Nm).
If multiple units are installed be sure to follow derating curves
fig. 1
WARNING! Removing product from 35 mm rail incorrectly by not using the
appropriate tool could damage the latching system
fig. 2 Terminal
screw type.
Top/Bottom view.
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
DataSheet
SHORT CIRCUIT AND OVERLOAD PROTECTION FOR ALL DEVICES
(Conforming to the IEC60947-4-2 and UL508)
IEC standard 60947-4-1 make a distinction between two different types of protection, (called “coordination”), which are designated types “1” and "2".
Any short-circuit that occurs is cleared safely by either type of coordination.
The only difference between the 2 categories concerns the extent of the SSR damage caused by the short-circuit.
Type "1" coordination requires that in the event of a short-circuit, the Solid State Contactor does not endanger personnel or installations,
but permanent damage to the SSC is permissible. In this case the SSC may need to be replaced. For this type of co-ordination,
the use of fusing or circuit breakers adequate to protect the system and wiring from short circuits, (but not specifically considering SSC protection), can be used.
Type "2" coordination requires that under a short-circuit condition, the circuit is interrupted, the SSC does not endanger persons or installations,
and in addition the SSR will be able to operate after the fault condition is repaired.
Type of coordination 1
Protection by Thermal Magnetic Circuit Breaker (18)
Thermal Magnetic Circuit Breaker Solid State Contactor
Solid State Contactor
3 controlled legs
Solid State Contactor
Reversing
Nominal Motor
Current
(Schneider Electric)
GV2ME04 / GV2P04
GV2ME05 / GV2P05
GV2ME06 / GV2P06
GV2ME07 / GV2P07
GV2ME08 / GV2P08
GV2ME10 / GV2P10
GV2ME14 / GV2P14
2 controlled legs
0.40-0.63 A
0.63-1 A
1-1.6 A
DRC3Pxx4x2
DRC3Pxx4x
DRC3Pxx4x
DRC3Pxx4x
DRC3Pxx4x
DRC3Pxx4x
DRC3Pxx4x (up to 4.8A)
-
DRC3Rxx4x
DRC3Pxx4x2
DRC3Rxx4x
DRC3Pxx4x2
DRC3Rxx4x
1.6-2.5 A
2.5-4 A
DRC3Pxx4x2
DRC3Rxx4x
DRC3Pxx4x2
DRC3Rxx4x
4-6.3 A
DRC3Pxx4x2
DRC3Rxx4x
6.3-10 A
DRC3Pxx4x2 (up to 7.6A)
DRC3Rxx4x (up to 7.6A)
Protection by overload relays and fuses (18)
Class gG fuses Solid State Contactor
Nominal Motor Overload Relay
Solid State Contactor Solid State Contactor
(Schneider Electric) (example from Littlefuse) 2 controlled legs
3 controlled legs
DRC3Pxx4x
DRC3Pxx4x
DRC3Pxx4x
DRC3Pxx4x
DRC3Pxx4x
DRC3Pxx4x(up to 4.8A)
-
Reversing
Current
0.40-0.63 A
0.63-1 A
1-1.6 A
LRD04
LRD05
LRD06
LRD07
LRD08
LRD10
LRD14
CY14X51G16
CY14X51G16
CY14X51G25
CY14X51G25
CY14X51G25
CY14X51G40
CY14X51G40
DRC3Pxx4x2
DRC3Rxx4x
DRC3Pxx4x2
DRC3Rxx4x
DRC3Pxx4x2
DRC3Rxx4x
1.6-2.5 A
2.5-4 A
DRC3Pxx4x2
DRC3Rxx4x
DRC3Pxx4x2
DRC3Rxx4x
4-6.3 A
DRC3Pxx4x2
DRC3Rxx4x
6.3-10 A
DRC3Pxx4x2 (up to 7.6A)
DRC3Rxx4x (up to 7.6A)
Type of coordination 2
Protection by overload relays and fuses (18)
Semiconductor fuses with less than 1621A2S
Nominal Motor Overload Relay
Solid State Contactor
2 controlled legs
Solid State Contactor Solid State Contactor
Ferraz (Cylindric)
SIBA (Cylindric)
50.058.06.40
50.058.06.40
50.058.06.40
50.058.06.40
50.058.06.40
50.058.06.40
50.058.06.40
(Schneider Electric) Littlefuse
3 controlled legs
Reversing
Current
0.40-0.63 A
0.63-1 A
1-1.6 A
LRD04
LRD05
LRD06
LRD07
LRD08
LRD10
LRD14
LA50QS40-4
LA50QS40-4
LA50QS40-4
LA50QS40-4
LA50QS40-4
LA50QS40-4
LA50QS40-4
A093909
A093909
A093909
A093909
A093909
A093909
A093909
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
1.6-2.5 A
2.5-4 A
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
DRC3Pxx4x2
DRC3Pxx4x
DRC3Rxx4x
4-6.3 A
DRC3Pxx4x2
DRC3Pxx4x (up to 4.8A)
-
DRC3Rxx4x
6.3-10 A
DRC3Pxx4x2 (up to 7.6A)
DRC3Rxx4x (up to 7.6A)
Note: All the Schneider Electric Thermal magnetic circuit breakers GV2 family (GV2ME and GV2P) is fully mechanical compatible with the DRC contactor using the GV2AF3 connection block.
All the Schneider Electric Overload relay LRD family is fully mechanical compatible with the DRC contactor without the need of any adapter.
The DRC Series can accept the LAD7C1 module (pre-wiring kit allowing direct connection of the NC contact of relay LRD to the contactor)
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
DataSheet
(19)
SWITCHING FREQUENCY/LOAD CHARACTERISTIC FOR ALL DEVICES
IL : Load Operating Current
IR : Rated Full Load Current [FLA]
ID : Direct-On-Line Inrush Current
tL : Load Operating Current Time
tD : Direct-On-Line Inrush Current Time
tC : Cycle Time
ID
IR
t
t
On : On Time
Off : Off Time
IL
tD
tL
tOn
tOff
tC
MAXIMUM ALLOWABLE NUMBER OF STARTS PER HOUR DEPENDING ON THE STARTING
TIME tD AND THE ON PERIOD tOn (as for standard IEC 60947-4-2) FOR ALL DEVICES
Without overload relay (limit given by the contactor itself)
Table 1
Table 2
Table 3
• Low inrush current (ID/IR < 4 )
• Full load (IL/IR= 1)
Table 4
• Low inrush current (ID/IR < 4 )
• 60% load (IL/IR= 0.6)
• High inrush current (ID/IR = 4 to 7.2)
• Full load (IL/IR= 1)
• High inrush current (ID/IR = 4 to 7.2)
• 60% load (IL/IR= 0.6)
tOn (sec)
tOn (sec)
tOn (sec)
tOn (sec)
tD (sec)
0.05
0.1
0.1
5000
3200
-
1
10
100
35
35
35
35
35
30
25
tD (sec)
0.05
0.1
0.1
6000
4100
-
1
10
100
35
35
35
35
35
35
35
tD (sec)
0.05
0.1
0.1
7450
4050
-
1
10
100
35
35
35
35
35
35
35
tD (sec)
0.05
0.1
0.1
1
10
100
35
35
35
35
35
35
35
2700
1950
950
500
290
350
350
320
280
160
110
75
3550
3000
1300
700
350
350
350
320
320
125
90
3200
2100
1200
650
350
350
350
320
280
180
90
9000
3550
3550
1700
850
350
350
350
350
350
240
180
5400
0.2
0.2
0.2
0.2
-
-
-
-
-
-
0.4
0.4
0.4
0.4
0.8
0.8
400
0.8
350
0.8
560
-
-
-
1.6
1.6
-
-
1.6
1.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3.2
3.2
3.2
3.2
With overload relay (limit given by the overload relay itself)
Table 5
Table 6
Table 7
• Low inrush current (ID/IR < 4 )
• Full load (IL/IR= 1)
Table 8
• Low inrush current (ID/IR < 4 )
• 60% load (IL/IR= 0.6)
• High inrush current (ID/IR = 4 to 7.2)
• Full load (IL/IR= 1)
• High inrush current (ID/IR = 4 to 7.2)
• 60% load (IL/IR= 0.6)
tOn (sec)
tOn (sec)
tOn (sec)
tOn (sec)
tD (sec)
0.05
0.1
0.1
1
10
330
280
255
150
60
100
30
28
26
24
20
16
tD (sec)
0.05
0.1
0.1
2800
1700
-
1
10
320
310
290
200
90
100
35
32
30
26
25
25
tD (sec)
0.05
0.1
0.1
1
10
100
35
34
33
32
30
25
20
tD (sec)
0.05
0.1
0.1
1
10
100
35
35
35
35
35
35
25
2200
1650
1000
550
250
80
1800
1300
650
300
200
5150
2850
2800
1920
1100
600
260
250
250
200
200
120
75
5600
3200
3200
2700
1400
700
350
350
350
350
280
170
80
1500
0.2
0.2
0.2
-
0.2
-
-
-
-
-
0.4
0.4
0.4
-
-
-
-
0.4
-
-
-
-
0.8
0.8
0.8
320
0.8
350
-
1.6
40
1.6
65
1.6
1.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3.2
3.2
3.2
3.2
Note: Please take into consideration the mechanical and electrical life expectancy of the EMR auxiliary contacts when selecting a DRC Series contactor for your
application.
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
DataSheet
TIMING DIAGRAM
TIMING DIAGRAM FOR DRC3R
Input/Output
1
2
3
4
5
6
7
8
9
10
Input A1
Input A3
100 msec
100 msec
FWD Direction
REV Direction
100 msec
interlock
Input A3
Input A1
STEP
DESCRIPTION
Initial Condition. A1 & A3 open
FWD
REV
1, 4, 10
Open
Close
Open
Close
Open
Open
Close
Close
Off
Off
2
A1 is activated, FWD Output waits for 100msec
FWD direction is activated
On
Off
Off
Off
On
Off
3, 9
4
A1 changes to off. FWD Output is disabled at the same time
A3 is activated. REV Outputs waits for 100msec
REV direction is On
5
6
7
Interlock fuction is activated. REV is disabled due to A1 & A3 both being active
A3 is open, A1 is closed, activation delayed 100msec
8
MECHANICAL SPECIFICATIONS
30.1
[89]
Tolerances: ±±0±ꢀ ꢁn ꢂ ±0. ꢃꢃ
All dꢁꢃensꢁons are ꢁn: ꢁnches [ꢃꢁllꢁꢃeters]
ꢀ091
[7309]
±0ꢀ3
[.08]
A3
13
23
A1
DRC3
IND. CONT. EQ.
ꢀ0.8
[6.0.]
1068
[4ꢀ07]
10ꢀ3
[3103]
ꢀ0ꢀ9
[.803]
3041
[8607]
XXXX
INPUT
STATUS
14
24
A2
3076
[9.06]
1078
[4.03]
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
DataSheet
ACCESSORIES FOR ALL DEVICES
Recommended Accessories
Motor Nominal
Bimetal
Electronic
Overload Relay
Thermal Magnetic Circuit Thermal Magnetic Circuit
Current
Overload Relay
Breaker (Push Button)
Breaker (Selector)
0.40 - 0.63 A
LRD04
LR97 D015xx
LR97 D015xx
LR97 D07xx
LR97 D07xx
LR97 D07xx
LR97 D25xx
LR97 D25xx
GV2ME04
GV2ME05
GV2ME06
GV2ME07
GV2ME08
GV2ME10
GV2ME14
GV2P04
GV2P05
GV2P06
GV2P07
GV2P08
GV2P10
GV2P14
0.63 - 1 A
LRD05
1 - 1.6 A
LRD06
1.6 - 2.5 A
LRD07
2.5 - 4 A
LRD08
4 - 6.3 A
LRD10
6.3 - 10 A
LRD14
Fully compatible with
Schneider Electric
thermal overload
relays &
thermal magnetic
circuit breakers
Note: All the Schneider Electric Thermal magnetic circuit breakers GV2 family (GV2ME and GV2P) is fully mechanical compatible with the DRC contactor using the GV2AF3 connection block.
All the Schneider Electric Overload relay LRD family is fully mechanical compatible with the DRC contactor without the need of any adapter.
The DRC Series can accept the LAD7C1 module (pre-wiring kit allowing direct connection of the NC contact of relay LRD to the contactor)
When the LAD7C1 module is used, the common terminal for the control input is not anymore the ”A2” terminal of DRC but it is the “96” terminal of the overload relay.
ID Marker Strips
CNLB, CNLN, CNL2
Packages of 10 plastic strips comprising 10
individual markers which can be placed for easy
identification during the use of multiple units.
Blank Strips
Part no.: CNLB
Numbered 1 to 10 Strips
Numbered 11 to 20 Strips
Part no.: CNLN
Part no.: CNL2
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
DataSheet
AGENCY APPROVALS, CONFORMANCES AND EMC
Approvals
E116949
Conformances
United States Standard for Industrial Control Equipment - UL 508 and
Canadian Standard Association for Industrial Control Equipment – C22.2 No. 14.
IEC 60068-2-6: Amplitude Range 10-55 Hz, Displacement 0.75 mm
IEC 60068-2-27: Peak Acceleration 15g, Duration 11ms.
Vibration Resistance
Shock Resistance
Electromagnetic Compatibility
Generic
Standard
Immunity Tests
Test Specification Level
Performance
Electrostatic Discharge
IEC 61000-4-2
8kV air discharge
Criterion A
Criterion A
6kV contact discharge
IEC 61000-6-2
Immunity for
Industrial
Fast transients (burst)
IEC 61000-4-4
Output
Input
2kV, 5kHz, 100kHz Criterion B
1kV, 5kHz, 100kHz Criterion A
1kV Line to Line Criterion B
2kV Line to Earth Criterion B
Environments
Surge
Output
IEC 61000-4-5
GENERAL NOTES
(1) All parameters at 25°C unless otherwise specified.
(2) For DRC3P relay will self trigger between 900-1200V, Not suitable for capacitive loads.
(3) For DRC3R over rated voltage internal self protection will be activated increasing leakage current.
(4) Mounted in the Vertical position.
(5) For low temperature operation consider nominal control voltage.
(6) For DRC3P Instantaneous Turn-on, turn-on time is 4 msec.
(7) When control signal is completely removed. For DRC3R the turn-off time is 20msec.
(8) Operating voltage / current on auxiliary contacts must not exceed the power rating (Resistive load).
(9) For input to auxiliary output the dielectric strength is 1060 Vrms.
(10) UL approval up to 40°C surrounding temperature.
(11) Reverse Amber Indicator is for DRC3R models only.
(12) 100kA, 480VAC, when protected with CC class fuses rated 600VAC, 20 A or equivalent.
(13) IP20 rating is not associated with the UL approval.
(14) Derate information is valid when DCR contactors are used with or without accessories, installed on top and/or bottom.
(15) Minimum spacing to obtain max. current is 22mm between adjacent units.
(16) For DRC3P models external loads can be connected in parallel to the control input.
(17) DRC3R internal safety interlock circuit prevents the product to work if any leakage current is present in the control input currently not enabled.
(18) Combinations of these Protective Devices and Solid State Contactor have not been evaluated by UL.
(19) Only main circuit, not apply for auxiliary contacts.
Rev. 071917
ECN 20277
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
DataSheet
DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / 危险危险
HAZARD OF
ELECTRIC
SHOCK,
EXPLOSION,
OR ARC FLASH.
RIESGO DE
DESCARGA
ELECTRICA O
EXPLOSION.
RISQUE DE
GEFAHR EINES
ELEKTRISCHE
N SCHLAGES
ODER EINER
EXPLOSION.
RISCHIO DI
SCOSSA
ELETTRICA O
DELL’ESPLOSIONE.
存在电击、
爆炸或电弧
闪烁危险
DESCHARGE
ELECTRIQUE
OU EXPLOSION
•
在操作此设
备之前请先
关闭电源。
• Eteindre
toutes les
sources
d'énergie de
cet appareil
avant de
travailler
dessus de cet
appareil
• Spenga tutta
l'alimentazione
che fornisce
questa
apparecchiatura
prima di lavorare
a questa
• Desconectar
todos los
suministros de
energia a este
equipo antes
de trabajar
• Disconnect all
power before
installing or
working with
this equipment.
• Stellen Sie
jeglichen
Strom ab, der
dieses Gerät
versorgt, bevor
Sie an dem
若不遵守这些说明,
可能会导致严重的
人身伤害甚至死亡。
con este equipo.
• Verify all
connections
and replace all
covers before
turning on
Gerät Arbeiten
durchführen
apparecchiatura
• Verificar todas
las conexiones
y colocar todas
las tapas antes
de energizer
• Verificare tutti
i collegamenti
e sostituire
tutte le coperture
prima
• Vor dem
Drehen auf
Energie alle
Anschlüsse
überprüfen
und alle
• Vérifier tous
connections, et
remettre tous
couverts en
olace avant de
mettre sous
power.
el equipo.
Failure to follow
these
instructions will
result in death
or serious injury.
dell’accensione
El
Abdeckungen
ersetzen.
L'omissione di
queste istruzioni
provocherà la
morte o
incumplimiento
de estas
instrucciones
puede provocar
la muerte o
lesiones serias.
De non-suivi de
ces instructions
provoquera la
mort ou des
lésions sérieuses
sérieuses.
Unterlassung
dieser
Anweisungen
können zum
Tode oder zu
schweren
lesioni serie
Verletzungen
führen.
WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告
RISQUE DE DOMMAGE MATERIEL ET DE
SURCHAUFFE DU BOITIER
GEFAHR VON MATERIALSCHÄDEN UND
GEHÄUSEERHITZUNG
RISK OF MATERIAL DAMAGE AND HOT
ENCLOSURE
• Les panneaux latéraux du produit peuvent être
chauds. Laisser le produit refroidir avant de le
toucher.
• Respecter les consignes de montage, et
notamment les couples de serrage.
• Ne pas laisser pénétrer de liquide ni de corps
étrangers à l'intérieur du produit.
• Die Seitenwände können heiß sein. Lassen Sie
das Produkt abkühlen, bevor Sie es berühren.
• Beachten Sie die Montageanweisungen,
• Führen Sie keine Flüssigkeiten oder
• The product's side panels may be hot, allow
the product to cool before touching.
• Follow proper mounting instructions including
torque values.
• Do not allow liquids or foreign objects to enter
this product.
Fremdkörper in das Produkt ein.
Le non-respect de cette directive peut entraîner,
des lésions corporelles graves ou des
dommages matériels.
Die Nichtbeachtung dieser Anweisung kann
Körperverletzung oder Materialschäden
zur Folge haben.
Failure to follow these instructions can result in
serious injury, or equipment damage.
RIESGO DE DAÑOS MATERIALES Y DE
SOBRECALENTAMIENTO DE LA UNIDAD
材料损和高温外壳的危险性
RISCHIO DI DANNI MATERIALI E D'INVOLUCRO
CALDO
• 产品的一侧面板可能很热,在其冷却前请
不要触碰。
• 遵照正确的安装说明,包括扭矩值。
• 请勿让液体及其他异物进入本产品。
• Los paneles laterales del producto pueden
estar calientes. Esperar que el producto se
enfríe antes de tocarlo.
• Respetar las instrucciones de montaje, y en
particular los pares de apretado.
• I pannelli laterali dell'apparecchio possono
scottare; lasciar quindi raffreddare il prodotto
prima di toccarlo.
• Seguire le istruzioni di montaggio corrette.
• Non far entrare liquidi o oggetti estranei in questo
apparecchio.
• No dejar que penetren líquidos o cuerpos
extraños en el producto.
La mancata osservanza di questa precauzione può
causare gravi rischi per l'incolumità personale o
danni alle apparecchiature.
如不能正确执行这些操作说明,
极有可能造成严重人体伤害或者设备的损坏。
Si no se respetan estas precauciones pueden
producirse graves lesiones, daños materiales.
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
DataSheet
ANNEX - ENVIROMENTAL INFORMATION
The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China
Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products.
Part
Name
Toxic or hazardous Substance and Elements
Lead
(Pb)
Mercury
(Hg)
Cadmium
(Cd)
Hexavalent
Chromium
(Cr (VI))
Polybrominated
biphenyls
(PBB)
Polybrominated
diphenyl ethers
(PBDE)
Semiconductor die
Solder
附件 - 环保信息
此附件所标示的包括电子信息产品污染图标的环保信息符合中华人民共和国电子行业标准 SJ/T11364 - 2006,
电子信息产品污染控制标识要求。
部件
名称
有毒有害物质或元素
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr (VI))
多溴联苯
(PBB)
多溴二苯醚
(PBDE)
半导体芯片
焊接点
50
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.