PDRC-75-24-2 [CUI]

AC-DC DIN RAIL POWER SUPPLY;
PDRC-75-24-2
型号: PDRC-75-24-2
厂家: CUI INC    CUI INC
描述:

AC-DC DIN RAIL POWER SUPPLY

文件: 总6页 (文件大小:499K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Additional Resources: Product Page  
date 06/17/2019  
page 1 of 6  
SERIES: PDRC-75 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY  
FEATURES  
• low profile for building automation  
• universal input (90~264 Vac)  
• integrated fuse and surge protection  
• 3,000 Vac input/output isolation voltage  
• DC On/Low LED indicators  
• over-voltage/current protection  
• UL/cUL, TUV, CE certified  
output  
voltage  
output  
current  
max  
output  
power  
max  
ripple  
efficiency2  
MODEL  
and noise1  
max  
typ  
(Vdc)  
5
(A)  
(W)  
(mVp-p)  
(%)  
PDRC-75-5  
12.0  
6.0  
5.0  
4.2  
3.8  
60  
72  
50  
50  
50  
50  
50  
80  
86  
86  
89  
89  
PDRC-75-12  
PDRC-75-15  
PDRC-75-24  
PDRC-75-24-23  
12  
15  
24  
24  
75  
100  
91  
Notes:  
1. At full load, nominal input, 20 MHz bandwidth oscilloscope.  
2. At nominal input.  
3. Model PDRC-75-24-2 is UL 1310 certified.  
4. All specifications are measured at Ta=25°C, nominal input voltage, and rated output load unless otherwise specified.  
PART NUMBER KEY  
PDRC-75 - XX  
Base Number  
Output Voltage  
cui.com  
Additional Resources: Product Page  
CUI Inc SERIES: PDRC-75 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY  
date 06/17/2019 page 2 of 6  
INPUT  
parameter  
conditions/description  
min  
typ  
max  
units  
90  
120  
264  
375  
Vac  
Vdc  
voltage  
frequency  
47  
63  
Hz  
at 90 Vac, full load  
5 Vdc output model  
12, 15 output model  
24 Vdc output model  
1.5  
1.7  
2.2  
A
A
A
current  
at 115 Vac, full load  
at 230 Vac, full load  
30  
60  
A
A
inrush current  
leakage current  
input to output  
0.25  
mA  
OUTPUT  
parameter  
conditions/description  
min  
typ  
max  
3,500  
±1  
units  
µF  
capacitive load  
initial set point accuracy  
line regulation  
load regulation  
at Vi nom, full load  
%
at full load, V in min to V in max  
±1  
%
at Vi nom, 0~100% load  
±1  
%
via built in trim pot, 0.8 A load  
5 Vdc output model  
12 Vdc output model  
15 Vdc output model  
24 Vdc output model  
5
12  
13.5  
24  
5.5  
14  
16.5  
28  
Vdc  
Vdc  
Vdc  
Vdc  
Vdc  
adjustability  
24 Vdc output model (PDRC-75-24-2)  
20  
24.2  
5 Vdc output model (5.5 Vdc)  
10.5  
5.1  
4.5  
3.6  
3.7  
A
A
A
A
A
12 Vdc output model (14.0 Vdc)  
15 Vdc output model (16.5 Vdc)  
24 Vdc output model (28.0 Vdc)  
24 Vdc output model (PDRC-75-24-2) (24.2 Vdc)  
rated continuous loading at  
max trim voltage  
at Vi nom, full load  
at Vi nom, full load with max capacitive load  
1.0  
1.5  
s
s
start-up time  
rise time  
at Vi nom, full load  
at Vi nom, full load with max capacitive load  
150  
500  
ms  
ms  
5, 12 Vdc output models  
at 115 Vac, full load  
at 230 Vac, full load  
16  
60  
ms  
ms  
hold-up time  
15, 24 Vdc output models  
at 115 Vac, full load  
at 230 Vac, full load  
12  
60  
ms  
ms  
fall time  
at Vi nom, full load  
150  
2
ms  
ms  
transient recovery time  
switching frequency  
temperature coefficient  
at Vi nom, 100~50% load  
at Vi nom, full load  
35  
45  
kHz  
±0.03  
%/°C  
at Vi nom, full load, for 1 second  
5 Vdc output model  
12 Vdc output model  
15 Vdc output model  
24 Vdc output model  
7.5  
18  
22  
35  
Vdc  
Vdc  
Vdc  
Vdc  
power back immunity  
5 Vdc output model  
12 Vdc output model  
15 Vdc output model  
24 Vdc output model  
3.5  
9.0  
11.0  
19.2  
4.5  
Vdc  
Vdc  
Vdc  
Vdc  
DC ON indicator threshold at  
start-up (GREEN)  
10.8  
13.5  
21.6  
5 Vdc output model  
12 Vdc output model  
15 Vdc output model  
24 Vdc output model  
3.5  
9.0  
11.0  
19.2  
4.5  
Vdc  
Vdc  
Vdc  
Vdc  
DC LOW indicator threshold  
after start-up (RED)  
10.8  
13.5  
21.6  
cui.com  
Additional Resources: Product Page  
CUI Inc SERIES: PDRC-75 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY  
date 06/17/2019 page 3 of 6  
PROTECTIONS  
parameter  
conditions/description  
min  
typ  
max  
units  
at Vi nom, full load, auto recovery  
5 Vdc output model  
12 Vdc output model  
15 Vdc output model  
24 Vdc output model  
5.75  
15  
18  
30  
24.5  
6.5  
16.5  
20  
33  
25.5  
Vdc  
Vdc  
Vdc  
Vdc  
Vdc  
over voltage protection  
24 Vdc output model (PDRC-75-24-2)  
fold forward (see curve)  
24 Vdc output model (PDRC-75-24-2)  
all other models  
over current protection  
102  
110  
108  
150  
%
%
short circuit protection  
fold forward  
SAFETY & COMPLIANCE  
parameter  
conditions/description  
input to output for 1 minute  
input to output at 500 Vdc  
min  
typ  
max  
units  
3,000  
4,242  
Vac  
Vdc  
isolation voltage  
isolation resistance  
safety approvals5  
safety class  
100  
MΩ  
UL 508, UL 1310, UL 60950-1, EN 60950-1  
ISA 12.12.01 (Class I, Div 2, Groups A~D)  
class I  
EN 55032 Class B, EN 55024, ENV 50204,  
EN 61204-3, EN 61000-3-2, EN 61000-3-3,  
EN 61000-6-2, EN 61000-6-3, EN 61000-4-2,  
EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,  
EN 61000-4-6, EN 61000-4-8, EN 61000-4-11  
EMI/EMC  
pollution degree  
2
degree of protection  
IP20  
as per Bellcore Issue 6 at 40 °C, GB  
5 Vdc output model  
12 Vdc output model  
15 Vdc output model  
24 Vdc output model  
610,000  
578,000  
581,000  
554,000  
583,000  
hours  
hours  
hours  
hours  
hours  
MTBF  
24 Vdc output model (PDRC-75-24-2)  
RoHS  
yes  
Notes:  
5. Model PDRC-75-24-2 is only model that is UL 1310 certified.  
6. The power supply is considered a component which will be installed into final equipment. The final equipment still must be tested to meet the necessary EMC directives.  
ENVIRONMENTAL  
parameter  
conditions/description  
min  
-40  
-40  
20  
typ  
max  
71  
units  
°C  
operating temperature  
storage temperature  
humidity  
see derating curves  
85  
°C  
non-condensing  
95  
%
altitude  
IEC 60068-2-13  
4,850  
m
meets IEC 60068-2-6 (Mounting on rail: 10~500  
Hz, 2 G, along X,Y,Z axis, for 60 minutes on each  
axis)  
vibration  
meets IEC 60068-2-27 (15 G, 11 ms, 3 axis, 6  
faces, 3 times for each face)  
shock  
cui.com  
Additional Resources: Product Page  
CUI Inc SERIES: PDRC-75 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY  
date 06/17/2019 page 4 of 6  
MECHANICAL  
parameter  
dimensions  
conditions/description  
min  
typ  
max  
units  
91.00 x 90.00 x 57.00 (3.58 x 3.54 x 2.24 inches)  
plastic  
mm  
material  
weight  
380  
g
cooling  
natural convection  
input/output connector  
accepts 24~12 AWG wire  
MECHANICAL DRAWING  
units: mm [inch]  
tolerance:  
X≤30.00: ±0.30 [±0.01]  
30.00<X≤120.00: ±0.50 [±0.02]  
unless otherwise noted  
TERMINAL  
CONNECTIONS  
TERMINAL  
Function  
1
2
3
4
5
6
V-  
V-  
V+  
V+  
L
N
INSTALLATION  
DIN RAIL  
Cable  
TS35/7.5 or TS35/15  
flexible/solid, copper conductors  
only, 60/75°C  
24~12 AWG  
Wire Range  
(0.2~2.5 mm2)  
Strip Length  
Screw Torque  
Position  
7 mm  
6 lb·in  
Vertical  
Natural convection, 25 mm  
Cooling  
clearance on all sides  
cui.com  
Additional Resources: Product Page  
CUI Inc SERIES: PDRC-75 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY  
date 06/17/2019 page 5 of 6  
DERATING CURVES  
Temperature Derating Curve  
(Output Load vs. Ambient Tempearature)  
100  
5 Vdc output model  
all other models  
80  
75  
62.5  
40  
20  
-40  
0
20  
30  
40  
56  
61  
80  
71  
Ambient Temperature (°C)  
EFFICIENCY CURVES  
PDRC-75-24 Efficiency Curve  
(Efficiency vs. Load Current)  
Load Current (%)  
CURRENT LIMITED CURVE  
PDRC-75-24 Typical Over Current Protection Curve  
(Output Voltage vs. Time)  
(%)  
cui.com  
Additional Resources: Product Page  
CUI Inc SERIES: PDRC-75 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY  
date 06/17/2019 page 6 of 6  
REVISION HISTORY  
rev.  
description  
date  
1.0  
initial release  
06/17/2019  
The revision history provided is for informational purposes only and is believed to be accurate.  
Headquarters  
20050 SW 112th Ave.  
Tualatin, OR 97062  
800.275.4899  
Fax 503.612.2383  
cui.com  
techsupport@cui.com  
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.  
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is  
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.  
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a  
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.  

相关型号:

PDRC-75-5

AC-DC DIN RAIL POWER SUPPLY
CUI

PDRK-15

DIN Rail Mounting Kit For Modular Chassis Mount, 15W AC/DC Power Supplies
MPD

PDRP-1001

Deluge - Preaction Control Panel
SYSTEMSENSOR

PDRP-1002

Agent Release Control System
SYSTEMSENSOR

PDRP-1002E

Agent Release Control System
SYSTEMSENSOR

PDRP-2001

Deluge Preaction Control Panel
SYSTEMSENSOR

PDRV8243HDGQQ1

DRV8243-Q1 Automotive H-Bridge Driver with Integrated Current Sense and Diagnostics
TI

PDRV8243HRXYQ1

DRV8243-Q1 Automotive H-Bridge Driver with Integrated Current Sense and Diagnostics
TI

PDRV8243SDGQQ1

DRV8243-Q1 Automotive H-Bridge Driver with Integrated Current Sense and Diagnostics
TI

PDRV8243SRXYQ1

DRV8243-Q1 Automotive H-Bridge Driver with Integrated Current Sense and Diagnostics
TI

PDRV8244HDGQQ1

DRV8244-Q1 Automotive H-Bridge Driver with Integrated Current Sense and Diagnostics
TI

PDRV8244HRYJQ1

DRV8244-Q1 Automotive H-Bridge Driver with Integrated Current Sense and Diagnostics
TI