VHK200W-DIN [CUI]

DC-DC CONVERTER;
VHK200W-DIN
型号: VHK200W-DIN
厂家: CUI INC    CUI INC
描述:

DC-DC CONVERTER

DC-DC转换器
文件: 总7页 (文件大小:691K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
For more information, please visit the product page.  
date 06/16/2014  
page 1 of 7  
SERIES: VHK200W-DIN DESCRIPTION: DC-DC CONVERTER  
FEATURES  
• up to 200 W isolated output  
• rugged metal enclosure with integrated heat sink  
• 4:1 input range (10~36 Vdc, 18~75 Vdc)  
• single output from 12~48 Vdc  
• 1,500 Vdc isolation  
• over current, over temperature, over voltage,  
and short circuit protections  
• remote on/off  
• efficiency up to 88%  
• comes with DIN-rail mount  
input  
voltage  
range  
(Vdc)  
output  
voltage  
output  
current  
max  
(A)  
output  
power  
max  
(W)  
ripple  
efficiency  
MODEL  
and noise1  
max  
(mVp-p)  
typ  
(%)  
(Vdc)  
12  
VHK200W-Q24-S12-DIN  
VHK200W-Q24-S15-DIN  
VHK200W-Q24-S24-DIN  
VHK200W-Q24-S28-DIN  
VHK200W-Q24-S48-DIN  
VHK200W-Q48-S12-DIN  
VHK200W-Q48-S15-DIN  
VHK200W-Q48-S24-DIN  
VHK200W-Q48-S28-DIN  
VHK200W-Q48-S48-DIN  
10 ~ 36  
10 ~ 36  
10 ~ 36  
10 ~ 36  
10 ~ 36  
18 ~ 75  
18 ~ 75  
18 ~ 75  
18 ~ 75  
18 ~ 75  
16.7  
13.3  
8.3  
200  
200  
200  
200  
200  
200  
200  
200  
200  
200  
150  
150  
240  
280  
480  
150  
150  
240  
280  
480  
84  
84  
84  
87  
87  
86  
86  
86  
87  
88  
15  
24  
28  
7.14  
4.2  
48  
12  
16.7  
13.3  
8.3  
15  
24  
28  
7.14  
4.2  
48  
Note:  
1. Ripple and noise are measured at full load, 20 MHz BW with 10µF tantalum capacitor and 1µF ceramic capacitor across output. The 48 Vdc output models require a 10uF  
aluminum capacitor and 1uF ceramic capacitor across the output.  
2.ꢀAnꢀexternalꢀinputꢀcapacitorꢀofꢀ470μFꢀforꢀ24ꢀVdcꢀinputꢀmodelsꢀandꢀ47μFꢀforꢀ48ꢀVdcꢀinputꢀmodelsꢀisꢀrecommendedꢀtoꢀreduceꢀinputꢀrippleꢀvoltage.  
PART NUMBER KEY  
VHK200W - QXX - SXX X - DIN  
Output Voltage  
Mounting Type  
DIN = DIN-rail mount  
Input Voltage  
Remote On/Off Control  
"blank" = positive logic  
N = negative logic  
Base Number  
cui.com  
For more information, please visit the product page.  
CUI Inc SERIES: VHK200W-DIN DESCRIPTION: DC-DC CONVERTER  
date 06/16/2014 page 2 of 7  
INPUT  
parameter  
conditions/description  
min  
typ  
max  
units  
24 Vdc input models  
48 Vdc input models  
10  
18  
24  
48  
36  
75  
Vdc  
Vdc  
operating input voltage  
power up  
24 Vdc input  
9.5  
8.5  
Vdc  
Vdc  
power down  
under voltage shutdown  
power up  
48 Vdc input  
17  
16  
Vdc  
Vdc  
power down  
models ON (>3.5 Vdc or open circuit)  
positive logic  
models OFF (0~1.2 Vdc)  
CTRL1  
models ON (0~1.2 Vdc)  
negative logic  
models OFF (>3.5 Vdc or open circuit)  
filter  
piꢀfilter  
40A time delay fuse for 24 Vin models,  
20A time delay fuse for 48 Vin models  
input fuse  
Note:  
1. Open collector refer to -Vin  
OUTPUT  
parameter  
conditions/description  
min  
typ  
max  
units  
12, 15, & 24 V output models  
28 V output models  
48 V output models  
2,200  
2,200  
2,200  
μF  
μF  
μF  
maximum capacitive load  
100  
47  
line regulation2  
load regulation2  
measured from low line to high line  
measured from zero load to full load  
±0.2  
±0.2  
±1.5  
%
%
voltage accuracy  
adjustability  
%
±10  
250  
%
switching frequency  
transient response  
temperatureꢀcoefficient  
kHz  
µs  
25% step load change  
500  
±0.03  
%/°C  
Note:ꢀ  
2.ꢀAꢀ100ꢀμFꢀaluminumꢀcapacitorꢀisꢀrequiredꢀonꢀtheꢀoutputꢀforꢀtheꢀ28ꢀVdcꢀoutputꢀmodels.ꢀAꢀ47ꢀμFꢀaluminumꢀcapacitorꢀisꢀrequiredꢀonꢀtheꢀoutputꢀforꢀ48ꢀVdcꢀoutputꢀmodels.  
PROTECTIONS  
parameter  
conditions/description  
continuous  
min  
typ  
max  
units  
short circuit protection  
over current protection  
over voltage protection  
over temperature protection  
at 90% output voltage  
110  
115  
160  
140  
%
%
°C  
shutdown  
110  
SAFETY AND COMPLIANCE  
parameter  
conditions/description  
min  
1,500  
10  
typ  
max  
units  
Vdc  
for 1 minute: input to output; input to case;  
output to case  
isolation voltage  
isolation resistance  
RoHS  
MΩ  
2011/65/EU (CE)  
ENVIRONMENTAL  
parameter  
conditions/description  
min  
-40  
-55  
typ  
max  
85  
units  
°C  
operating temperature  
storage temperature  
see derating curve  
105  
°C  
cui.com  
For more information, please visit the product page.  
CUI Inc SERIES: VHK200W-DIN DESCRIPTION: DC-DC CONVERTER  
date 06/16/2014 page 3 of 7  
MECHANICAL  
parameter  
dimensions  
conditions/description  
min  
typ  
max  
units  
4.23 x 4.01 x 2.07 (107.5 x 101.8 x 52.6 mm)  
steel and aluminum extrusion  
inch  
case material  
weight  
651  
g
MECHANICAL DRAWING  
units: inch[mm]  
tolerance: X.XX = ±0.02[±0.5]  
X.XXX = ±0.010[±0.25]  
0.18 4.5  
wire range: 22~12 AWG  
screw size: #6-32  
mounts to TS35 rails  
5
9
1
4
PIN CONNECTIONS  
PIN  
1
FUNCTION  
+Vin  
-Vin  
2
3
REM  
CASE  
+Vo  
4
5
6
+S  
0.67 17.0  
2.76 70.0  
0.07 1.8  
7
TRIM  
-S  
4.09 104.0  
4.23 107.5  
8
9
-Vo  
Top View  
1.38 35.0  
2 - DIN RAIL CLIP  
Back View  
Front View  
Side View  
1.91 48.5  
INPUT  
OUTPUT  
Bottom View  
cui.com  
For more information, please visit the product page.  
CUI Inc SERIES: VHK200W-DIN DESCRIPTION: DC-DC CONVERTER  
date 06/16/2014 page 4 of 7  
DERATING CURVES  
VHK200W Power Derating Curves At Nominal Input  
120%  
Natural  
Convection  
100%  
80%  
60%  
40%  
20%  
0.5 m/S  
(100LFM)  
1.0 m/S  
(200LFM)  
1.5 m/S  
(300LFM)  
2.0 m/S  
(400LFM)  
2.5 m/S  
(500LFM)  
3.0 m/S  
(600LFM)  
3.5 m/S  
(700LFM)  
0%  
-40  
15  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
Ambient Temperature - degrees C  
TEST CONFIGURATION  
Figure 1  
Table 1  
To Oscilloscope  
L1  
External components  
for 24 Vdc input models  
1.2μH  
+Vin  
+Vo  
+
L1  
Vin  
Cin  
R-Load  
Cin  
470μF,ꢀESRꢀ<ꢀ0.2Ωꢀatꢀ100ꢀKHz  
for 48 Vdc input models  
12μH  
-
-Vin  
-Vo  
L1  
Cin  
47μF,ꢀESRꢀ<ꢀ0.7Ωꢀatꢀ100ꢀKHz  
Note:ꢀ  
Inputꢀreflected-rippleꢀcurrentꢀisꢀmeasuredꢀwithꢀanꢀinductorꢀL1ꢀtoꢀsimulateꢀsourceꢀimpedance.  
cui.com  
For more information, please visit the product page.  
CUI Inc SERIES: VHK200W-DIN DESCRIPTION: DC-DC CONVERTER  
date 06/16/2014 page 5 of 7  
EMC RECOMMENDED CIRCUITS  
EN55022 CLASS A  
Figure 2  
Recommended Circuit for EN55022 Class A  
(forLall212, 15, 24, & 28 Vdc output models)  
L1  
+Vin  
+Vo  
+Vin  
+Vo  
-Vo  
+S  
C1  
C2  
C3  
DC/DC Converter  
-S  
-Vin  
-Vo  
-Vin  
CASE  
C4  
Figure 3  
Recommended Circuit for EN55022 Class A  
(for all 48 Vdc output models)  
CY1  
L1  
+Vin  
+Vo  
+S  
+Vin  
+Vo  
-Vo  
C1  
C2  
C3  
DC/DC Converter  
-S  
-Vin  
-Vo  
-Vin  
CY2  
Table 2  
Class A Recommended Components  
Model  
C11  
C21  
C31  
CY12  
CY22  
L1  
L2  
VHK200W-Q24-S12  
VHK200W-Q24-S15  
VHK200W-Q24-S24  
VHK200W-Q24-S28  
VHK200W-Q24-S48  
VHK200W-Q48-S12  
VHK200W-Q48-S15  
VHK200W-Q48-S24  
VHK200W-Q48-S28  
VHK200W-Q48-S48  
120ꢀμF/100ꢀV  
47ꢀμF/100ꢀV  
100ꢀμF/100ꢀV  
100ꢀμF/100ꢀV  
100ꢀμF/100ꢀV  
82ꢀμF/100ꢀV  
82ꢀμF/100ꢀV  
82ꢀμF/100ꢀV  
150ꢀμF/100ꢀV  
100ꢀμF/100ꢀV  
120ꢀμF/100ꢀV  
47ꢀμF/100ꢀV  
100ꢀμF/100ꢀV  
100ꢀμF/100ꢀV  
100ꢀμF/100ꢀV  
82ꢀμF/100ꢀV  
82ꢀμF/100ꢀV  
82ꢀμF/100ꢀV  
150ꢀμF/100ꢀV  
100ꢀμF/100ꢀV  
NC  
NC  
NC  
0.5 mH  
0.5 mH  
0.5 mH  
0.5 mH  
1.0 mH  
0.5 mH  
0.5 mH  
0.7 mH  
0.5 mH  
1.0 mH  
SHORT  
SHORT  
SHORT  
SHORT  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
100ꢀμF/100ꢀV  
680 pF/2 KV  
680 pF/2 KV  
NC  
NC  
NC  
SHORT  
SHORT  
SHORT  
SHORT  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
NC  
100ꢀμF/100ꢀV  
680 pF/2 KV  
680 pF/2 KV  
Notes:  
1. Aluminum capacitors.  
2. Ceramic capacitors.  
cui.com  
For more information, please visit the product page.  
CUI Inc SERIES: VHK200W-DIN DESCRIPTION: DC-DC CONVERTER  
date 06/16/2014 page 6 of 7  
APPLICATION NOTES  
1. Output Voltage Trimming  
Leave open if not used.  
Figure 4  
Application Circuit for Trim pin  
+Vo  
+Sense  
+Vin  
R trim-up  
Trim up  
R-Load  
Trim  
-Sense  
-Vo  
-Vin  
+Vo  
+Sense  
+Vin  
Trim  
Trim down  
R-Load  
R trim-down  
-Sense  
-Vo  
-Vin  
Formula for Trim Resistor  
∆% = ( Vo, nom - Vo )100  
Vo, nom  
Trim-Up Formula  
Trim-Down Formula  
(for all 12, 15, 24, & 281 Vdc Output Models)  
(for all 12, 15, 24, & 281 Vdc Output Models)  
5.11VO, nom(100 + ∆%) 511  
511  
∆%  
R
trim - up = (  
-
- 10.22)(KΩ)  
R
trim - down = (  
- 10.22)(KΩ)  
∆%  
1.225 x ∆%  
Trim-Up Formula  
(for all 48 Vdc Output Models)  
Trim-Down Formula  
(for all 48 Vdc Output Models)  
20VO, nom(100 + ∆%) 2000  
2000  
∆%  
R
trim - up = (  
-
- 40)(KΩ)  
R
trim - down = (  
- 40)(KΩ)  
1.225 x ∆%  
∆%  
Note:  
Rtrim-upꢀisꢀtheꢀexternalꢀresistorꢀinꢀKΩ  
Rtrim-downꢀisꢀtheꢀexternalꢀresistorꢀinꢀKΩ  
VO, nom is the nominal output voltage  
VO is the desired output voltage  
Notes:  
1. For the 28 Vdc output models, a minimum input voltage of 10.8 Vdc is required to trim the 24 Vdc input models up 10%, and a minimum input voltage of 19 Vdc is  
required to trim the 48 Vdc input models up 10%.  
2.ꢀAllꢀspecificationsꢀareꢀmeasuredꢀatꢀTa=25°C,ꢀnominalꢀinputꢀvoltageꢀandꢀfullꢀoutputꢀloadꢀunlessꢀotherwiseꢀspecified.  
cui.com  
For more information, please visit the product page.  
CUI Inc SERIES: VHK200W-DIN DESCRIPTION: DC-DC CONVERTER  
date 06/16/2014 page 7 of 7  
REVISION HISTORY  
rev.  
description  
date  
1.0  
initial release  
12/16/2013  
06/16/2014  
1.01  
changed DIN-rail mount  
The revision history provided is for informational purposes only and is believed to be accurate.  
Headquarters  
20050 SW 112th Ave.  
Tualatin, OR 97062  
800.275.4899  
Fax 503.612.2383  
cui.com  
techsupport@cui.com  
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.  
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is  
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.  
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a  
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.  

相关型号:

VHK200W-Q24-S12

chassis mount dc-dc converter
CUI

VHK200W-Q24-S12-DIN

12 Vdc, 16.7 A, 200 W DIN, 10~36 Vdc Input Range
CUI

VHK200W-Q24-S15

chassis mount dc-dc converter
CUI

VHK200W-Q24-S15-DIN

DC-DC CONVERTER
CUI

VHK200W-Q24-S24

chassis mount dc-dc converter
CUI

VHK200W-Q24-S24-DIN

24 Vdc, 8.3 A, 200 W DIN, 10~36 Vdc Input Range
CUI

VHK200W-Q24-S28

chassis mount dc-dc converter
CUI

VHK200W-Q24-S28-DIN

DC-DC CONVERTER
CUI

VHK200W-Q24-S48

chassis mount dc-dc converter
CUI

VHK200W-Q24-S48-DIN

DC-DC CONVERTER
CUI

VHK200W-Q48-S12

chassis mount dc-dc converter
CUI

VHK200W-Q48-S12-DIN

DC-DC CONVERTER
CUI