VMS-200-12-CNF [CUI]
Chassis Mount Power Supply, 12 Vdc, 16.67 A, 200 W;型号: | VMS-200-12-CNF |
厂家: | CUI INC |
描述: | Chassis Mount Power Supply, 12 Vdc, 16.67 A, 200 W |
文件: | 总10页 (文件大小:1259K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
For more information, please visit the product page.
date 12/12/2017
page 1 of 10
SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
FEATURES
• compact 2 x 4” high power-density design (CNF version is 2.4 x 4.6”)
• universal input range
• efficiencies up to 93.5%
• 4th edition medical safeties
• fan output (+12 Vdc)
• over voltage, over current, over temperature and short circuit protections
• covered and open-frame configurations
output
voltage
output
current
max
output
power1
max
ripple
efficiency3
MODEL
and noise2
max
typ
(Vdc)
12
(A)
(W)
(mVp-p)
(%)
VMS-200-12
VMS-200-24
VMS-200-48
16.67
8.33
4.17
200
200
200
150
240
480
92
93.5
93
24
48
Notes:
1. Maximum output power of 200 W with 10 CFM forced air or baseplate cooling, 180 W at 220 Vac with convection cooling.
2. At full load, nominal input, 20 MHz bandwidth oscilloscope, output terminated with 47 μF aluminum electrolytic and 0.1 μF ceramic capacitors.
3. At full load, 25°C, 230 Vac input.
4. All specifications are measured at Ta=25°C, nominal input voltage, and 75% rated output load unless otherwise specified.
PART NUMBER KEY
VMS-200 - XX - XXX
Base Number
Output Voltage
Chassis:
“blank” = open-frame
CNF = covered
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/12/2017 │ page 2 of 10
INPUT
parameter
voltage
conditions/description
min
90
typ
max
264
60
units
Vac
Hz
frequency
47
under voltage shutdown
current
69
83
Vac
A
at 100 Vac, full load
at 240 Vac, 25°C, cold start
at 264 Vac
2.5
100
0.3
inrush current
leakage current
A
mA
leakage current (enclosure/
patient)
0.1
mA
W
power factor correction
meets EN 61000-3-2
no load power consumption
0.3
OUTPUT
parameter
conditions/description
min
typ
max
units
at 115/230 Vac, full load
12 Vdc output models
24 Vdc output models
48 Vdc output models
16,400
8,570
1,270
μF
μF
μF
output capacitance
initial set point accuracy
line regulation
at 60% load, 25°C
high line to low line at full load
at 60%±40% load
at 115 Vac
±2
±0.5
±1
%
%
load regulation
%
hold-up time
10
ms
switching frequency
temperature coefficient
85
kHz
%/°C
±0.05
open-frame: 12 Vdc / 300 mA
covered: 12 Vdc / 500 mA
fan output
LED
indicates when power is on
PROTECTIONS
parameter
conditions/description
min
typ
max
units
recycle ac input to restart
12 Vdc output models
24 Vdc ouput models
48 Vdc output models
16
31
56
Vdc
Vdc
Vdc
over voltage protection
over current protection
short circuit protection
hiccup, auto recovery
hiccup, auto recovery
130
150
180
%
SAFETY & COMPLIANCE
parameter
conditions/description
min
typ
max
units
input to output for 1 minute
input to earth ground for 1 minute
output to earth ground for 1 minute
4,000
1,500
1,500
Vac
Vac
Vac
isolation voltage
isolation resistance
safety approvals
100
MΩ
UL/cUL 60601-1 (3.1 edition), IEC 60601-1 (3.1 edition), EN 60601-1 (3.1 edition)
Class I & II
safety class
EMI/EMC
EN 60601-1-2 (4th edition)
conducted disturbance
radiated disturbance1
harmonic current emissions
EN 55011, FCC CFR 47 Part 18, Class B
EN 55011, FCC CFR 47 Part 18, Class B
IEC 61000-3-2:2014, Class A, Class D
Notes:
1. Need an external 1 mH choke at input for Class II type to pass EN 55011 Class B.
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/12/2017 │ page 3 of 10
(
)
SAFETY & COMPLIANCE CONTINUED
parameter
conditions/description
min
typ
max
units
voltage fluctuations & flicker
IEC 61000-3-3:2013, Criteria A
radio-frequency, continuous
radiated disturbance
IEC 61000-4-3:2010, Criteria A
electrical fast transient (EFT)
IEC 61000-4-4:2012, ±0.5 kV, ±1 kV, ±2 kV, Criteria A
surge
IEC 61000-4-5:2014, L-N: ±0.5 kV, ±1 kV, L-PE, N-PE: ±0.5 kV, ±1 kV, ±2 kV, Criteria A
conducted disturbances,
induced by RF fields
IEC 61000-4-6:2013, Criteria A
power frequency magnetic field IEC 61000-4-8:2009, Criteria A
voltage dips
voltage interruptions
MTBF
IEC 61000-4-11:2004, dip: 30% 500 ms, dip: 60% 100 ms, dip >95% 10 ms, Criteria A
IEC 61000-4-11:2004, >95% 5,000 ms, Criteria B
as per MIL-HDBK-217F, at full load, 25°C
2011/65/EU
279,000
hours
RoHS
ENVIRONMENTAL
parameter
conditions/description
min
-20
-40
typ
max
80
units
°C
operating temperature
storage temperature
operating humidity
storage humidity
see derating curves
85
°C
non-condensing
non-condensing
93
%
93
%
DERATING CURVES
VMS-200 Output Power vs. Input Voltage
(Natural Convection)
VMS-200-CNF Output Power vs. Input Voltage
(Natural Convection)
220
200
180
160
220
200
180
160
140
120
100
80
140
120
100
80
60
40
60
40
20
0
20
0
90
110
130
150
170
190
210
230
250
90
110
130
150
170
190
210
230
250
Input Voltage (Vac)
Input Voltage (Vac)
VMS-200 Output Power vs. Ambient Temperature
VMS-200-CNF Output Power vs. Ambient Temperature
(Natural Convection)
(Natural Convection)
200
180
160
200
180
160
Input voltage 200~264 Vac
Input voltage 90~190 Vac
Input voltage 100~264 Vac
Input voltage 90 Vac
140
120
100
140
120
100
80
60
40
20
0
80
60
40
20
0
-20 -10
0
10 20 30 40 50 60 70 80
Ambient Temperature (°C)
-20 -10
0
10 20 30 40 50 60 70 80
Ambient Temperature (°C)
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/12/2017 │ page 4 of 10
DERATING CURVES (CONTINUED)
VMS-200 Output Power vs. Ambient Temperature
(200W with 10 CFM air flow)
100
VMS-200-CNF Output Power vs. Ambient Temperature
(200W with 10 CFM air flow)
100
80
80
60
40
60
40
20
0
20
0
-20 -10
0
10 20 30 40 50 60 70 80
Ambient Temperature (°C)
-20 -10
0
10 20 30 40 50 60 70 80
Ambient Temperature (°C)
VMS-200 Output Power vs. Ambient Temperature
(at 115/230 Vac, baseplate cooling, natural convection)
250
VMS-200-CNF Output Power vs. Ambient Temperature
(at 115/230 Vac, baseplate cooling, natural convection)
250
200
200
150
100
150
100
50
0
50
0
-20 -10
0
10 20 30 40 50 60 70 80
Ambient Temperature (°C)
-20 -10
0
10 20 30 40 50 60 70 80
Ambient Temperature (°C)
EFFICIENCY CURVES
12 Vdc Output Efficiency Curve
(at 25°C)
24 Vdc Output Efficiency Curve
(at 25°C)
95
90
85
80
75
70
95
90
85
80
75
70
90 Vac
90 Vac
115 Vac
230 Vac
264 Vac
115 Vac
230 Vac
264 Vac
10
20
30
40
50
60
70
80
90
100
10
20
30
40
50
60
70
80
90
100
Current Load (%)
Current Load (%)
48 Vdc Output Efficiency Curve
(at 25°C)
95
90
85
80
75
70
90 Vac
115 Vac
230 Vac
264 Vac
10
20
30
40
50
60
70
80
90
100
Current Load (%)
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/12/2017 │ page 5 of 10
MECHANICAL
parameter
conditions/description
min
typ
max
units
VMS-200 models: 4.000 x 2.000 x 1.480 (101.60 x 50.80 x 37.60 mm)
VMS-200-CNF models: 4.606 x 2.441 x 1.575 (117.00 x 62.00 x 40.00 mm)
inch
inch
dimensions
VMS-200 models
VMS-200-CNF models
253
314
g
g
weight
cooling
external fan or baseplate cooling
CN1 mates with JST housing VHR series, JST SVH-21/41T-P1.1
series crimp terminal or equivalent
CN1 input connector
output terminals
fan connector
+Vo & -Vo terminals are M3 screws
fan mates with JST housing PHR-R5500 series, JST R5503-PT
series crimp terminal or equivalent
MECHANICAL DRAWING
Open-frame
units: inch [mm]
tolerance: ±0.020 [±0.50]
4.000 101.60
3.701 94.00
CN1
PIN
1
Function
ACL
0.150 3.80
2
-
PE
PE
3
ACN
FAN
+Vo
PIN
1
Function
FAN V+
FAN V-
ACN
ACL
-Vo
2
PE
Air flow
direction
GBO
10CFM
FAN V+
FAN V-
LED
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/12/2017 │ page 6 of 10
MECHANICAL DRAWING (CONTINUED)
Covered
units: inch [mm]
tolerance: ±0.020 [±0.50]
4.606 117.00
CN1
PIN
1
Function
ACL
2
-
+Vo
-Vo
3
ACN
ACN
ACL
FAN
PIN
1
Function
FAN V+
FAN V-
Air flow
direction
2
GBO
10CFM
0.236 6.00
FAN V+
FAN V-
LED
0.157 4.00
4.29 109.00
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/12/2017 │ page 7 of 10
EMI RECOMMENDATION
To Meet EN 55011 Class B, Class II
VMS-200
VMS-200-CNF
Table 1
Duplex Winding/
Specification
Inductance
1 mH
Manufacturers
VAKOS
Turns
T16*10*5C
TEX-E Ø0.65/11T
R12
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/12/2017 │ page 8 of 10
INSTALLATION INSRUCTIONS
The VMS-200 series has (4) 3.2 mm diameter mounting holes that can be used in (4) types of installations.
Type 1
Type 2
Mounting from top with spacers (VMS-200 models)
Mounting from bottom (VMS-200-CNF models)
Spacer: 5.5 mm diameter max, 5 mm high minimum
Screw Size: (4) M3X0.5 (head & washer OD not to exceed
6 mm)
Screw Size: (4) M3X0.5
Mounting torque: 3 kgf-cm
Mounting torque: 3 kgf-cm
Type 3 (External Baseplate Cooling)
Type 4 (External Baseplate Cooling)
Mounting from top with spacers (VMS-200 models)
Mounting from bottom (VMS-200-CNF models)
Heat Sink: 280 x 100 x 10 mm
Heat Sink: 280 x 100 x 10 mm
Screw Size: (4) M3X0.5
Mounting torque: 3 kgf-cm
Spacer: 5.5 mm diameter max, 5 mm high minimum
Screw Size: (4) M3X0.5 (head & washer OD not to exceed
6 mm)
Mounting torque: 3 kgf-cm
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/12/2017 │ page 9 of 10
INSTALLATION INSRUCTIONS (CONTINUED)
Output Terminals
Mate with round or Y terminals
Terminal Size: (2) M3
Torque: 3 kgf-cm
Output Connectors
with M3 Screws*2
3(kgf-cm)
or
Mounting Clearance
Allow at least 4 mm side clearance and 5 mm height clearance. If clearances aren’t met, the isolation and withstand
specifications may not be met.
Protective Earth
PE should be connected to the earth (ground) terminal of the apparatus otherwise conducted noise and output noise will
increase.
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/12/2017 │ page 10 of 10
REVISION HISTORY
rev.
description
date
1.0
initial release
12/12/2017
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
techsupport@cui.com
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.