LM10A [CYNERGY3]
For smaller tanks and restricted space;型号: | LM10A |
厂家: | Cynergy3 Co |
描述: | For smaller tanks and restricted space |
文件: | 总2页 (文件大小:1864K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
LM Series
This is suitable for use in water, industrial wastewater and sewage, that can have wide
variations of temperature. This small design of switch is for use in more confined spaces, where
there isnotenoughroom for thelarger FFSMCtype.
The rounded body design and floating attitude prevents accumulation of solids on the body.
The switch has additional internal ballast, to bring the centre of gravity and rotation close to the
cable entrypoint.
The switching element is a self cleaning type, that makes the complete switch insensitive to
humidity and condensation, allowing this type to operate in widely fluctuating temperatures. The
switchcontacts are rated at 10Amp resistive.
Supplied, asstandard, with5metres cable and adjustable counterweight.
Technical Specifications
Contact Form
LM10A
N/O
LM10B
N/C
High Density Polyethylene
0 / +55
LM10C
C/O
Material
Temp Range
°C
°F
+ 32 / +131
• For smaller tanks and
Cable (standard length 5m)
Standard cable covering
U cable option for Fuel oils
Max. working pressure
With protective earth
no earth
restricted space
PVC
Polyurethane
10 bar
• Use in sewer and
industrial waste
water
Electrical Specifications
Power Rating
Switching Voltage
Switching Current Max. Resistive
Switching Current Max. Inductive
Max
AC : 750 VA DC : 180W
AC : 250 V DC : 110 V
10 A
Max
• Shape avoids
“ragging”, in sewer
systems
AC : 4A DC : 1 A
It is necessary to use an auxiliary relay, when switching pump motors or any loads that are not
purely resistive.
• Unaffected by
suspended solids
MECHANICAL
• Operates in Turbulent
Fluids
47
15°
Off - On
Differential
Cynergy3 Components Ltd
7 Cobham Road
On - Off
129
15°
Ferndown Industrial Estate
Wimborne
Dorset BH21 7PE
Tel: +44 (0) 1202 897969
Minimum Cable Pivot
75
length 120mm
sales@cynergy3.com
ISO 9001CERTIFIED
www.cynergy3.com
© 2011 Cynergy3 Components, All Rights Reserved.
Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
LM Series
Part Numbering System
LM 10 A U 10
Cable length in mtrs:
Series
Blank = 5M standard
Max. current
Cable covering:
Contact Form
A = n/o
Blank = PVC
U = Polyurethane
N = Neoprene
S = Silicone
B = n/c
C = c/o
Installation
cable entrance
cable
differential
external
counterweight
tie
pipe
wiring diagram
wiring diagram
for filling pump
for emptying pump
brown
brown
black
blue
brown
brown
blue
black
pump - off
pump - on
level drop
level drop
pump - off
pump - on
ISO 9001CERTIFIED
www.cynergy3.com
© 2011 Cynergy3 Components, All Rights Reserved.
Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.