DRP024V480W1BN [DELTA]
CliQ II DIN Rail Power Supply;型号: | DRP024V480W1BN |
厂家: | DELTA ELECTRONICS, INC. |
描述: | CliQ II DIN Rail Power Supply |
文件: | 总12页 (文件大小:735K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
Highlights & Features
–
–
–
–
–
–
–
–
–
–
Reliable design, with expected life of 10 years
Compact, rugged design for ease of handling and installation
With Conformal Coating on PCBA (DRP024V480W1BN)
Class I, Div 2 Hazardous Locations (DRP024V480W1BA)
IP20 Compliant
Meets worldwide safety requirements
RoHS Directive 2011/65/EU Compliant
Worldwide AC input range without power de-rating
Overvoltage / Overcurrent / Over Temperature Protections
150% Power Boost (steady state peak load) for 5 seconds
Safety Standards
CB Certified for worldwide use
Model Number:
DRP024V480W1B□
Unit Weight:
1.37 kg
Dimensions (L x W x D): 121 x 144 x 118.6 mm
General Description
The CliQ II-1Phase 24V 480W is part of the CliQ II series of DIN Rail power supplies from one of the world’s largest power supply
manufacturers and solution providers - Delta. This product provides an adjustable output capable of operating from input voltages at 85-
264Vac, and a wide temperature range of -25°C to 75°C. With a compact, rugged aluminium case that meets shock and vibration
requirements (in accordance to IEC60068-2-27 and IEC60068-2-6 respectively), and conformal-coated PCB assembly, this state of the
art design is well suited to a broad variety of industrial applications worldwide.
Model Information
CliQ DIN Rail Power Supply
Model Number
Input Voltage Range
Output
Voltage
Output Current
85-264Vac (120-375Vdc)
24Vdc
20A
DRP024V480W1B□
Model Numbering
DRP
P
024V
480W
1
B
□
DIN Rail
Power Supply
Output Voltage
Output Power
Single Phase
CliQ II Series
A - Metal Case,
with Class I, Div 2
N - Metal Case,
without Class I, Div 2
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
1
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
Nominal DC Input Voltage
DC Input Voltage Range
Input Current
100-240Vac
85-264Vac
50-60Hz
47-63Hz
125-250Vdc
120-375Vdc
< 5.00A @ 115Vac, < 3.00A @ 230Vac
> 90.0% @ 115Vac & 230Vac
< 35A @ 115Vac & 230Vac
> 0.96 @ 115Vac, > 0.89 @ 230Vac
< 3mA @ 240Vac
Efficiency
Max Inrush Current
Power Factor
Leakage Current
Output Ratings / Characteristics
Nominal Output Voltage
Output Voltage Tolerance
Output Voltage Adjustment Range
Output Current
24Vdc
± 2% (initial set point tolerance)
22-28Vdc
20A
Output Power
480W
Line Regulation
< 0.5% typ. (@ 85-264Vac input, 100% input)
< 1% typ. (@ 85-264Vac input, 0-100% input)
< 50mVpp / <150mVpp @ 25°C
Load Regulation
Residual Ripple / PARD (20MHz)
RiseTime
< 100ms @ nominal input (100% load, 25°C)
< 1000ms @ nominal input (100% load, 25°C)
> 20ms @ 115Vac & 230Vac (100% load, 25°C)
± 5% @ 10-100% load
Start-up Time
Hold-up Time
Dynamic Response (Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
10,000µF Max
Mechanical
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
2
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
Case Cover
Aluminium
Dimensions (L x W x D)
Unit Weight
121 x 144 x 118.6 mm
1.37 kg
Indicator
Green LED (DC OK)
Cooling System
Terminal
Convection
Input M3 x 3 Pins (Rated 300V/30A)
Output M3 x 4 Pins (Rated 300V/30A)
Wire
AWG 18-10
AWG 18-10
Input
Output
Mounting Rail
Standard TS35 DIN Rail in accordance with EN60715
Environment
Surrounding Air Temperature
Operating -25°C to +75°C
Storage -25°C to +85°C
> 50°C de-rate power by 2.5% / °C
> 70°C to 75°C de-rate power by 5% / °C
Power De-rating
Operating Humidity
< 95% RH (Non-Condensing)
Operating Altitude
2,000 Meters
Shock Test (Non-Operating)
Vibration (Non-Operating)
IEC60068-2-27, 30G (300m/S²) for a duration of 18ms
IEC60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak);
60 min per axis for all X, Y, Z direction
Bump
IEC60068-2-29; 11ms / 10gn
2
Pollution Degree
Protections
Overvoltage
<32V +10%, SELV Output, Hicc-up Mode,
Non-Latching (Auto-Recovery)
Overload / Overcurrent
Over Temperature
Short Circuit
> 200% of rated load current, Hicc-up Mode,
Non-Latching (Auto-Recovery)
< 80°C Surrounding Air Temperature @ 100% load,
Non-Latching (Auto-Recovery)
Hicc-up Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Degree of Protection
IP20
Protection Against Shock
Class I without PE* connection
*PE: Primary Earth
Reliability Data
MTBF
> 500,000 hrs. as per Telcordia SR-332
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
3
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
Safety Standards / Directives
Electronic Equipment in Power Installations
Electrical Safety
EN50718 / IEC62103
SIQ to EN60950-1, UL/cUL recognized to UL60950-1,
CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01,
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX (For DRP024V060W1BA)
CSA to CSA C22.2 No. 213-M1987, ANSI / ISA
12.12.01:2007 (Class I, Division 2, Group A, B, C, D, T4)
EN60079-0:2009, EN60079-15:2010
(
II 3G Ex nA nC IIc T4 Gc)
II 3G ATEX 94/9/EC; (For DRP024V060W1BA)
IECEX Test Report
Certificate No. ESP 12 ATEX 1 491 X;
For IEC60079-0, IEC60079-15
CE
In conformance with EMC Directive 2004/108/EC and
Low Voltage Directive 2006/95/EC
For DRP024V480W1BA:
In conformance with Equipment for explosive
atmospheres (ATEX) directive 94/9/EC
Material and Parts
Galvanic Isolation
RoHS Directive 2011/65/EU Compliant
Input to Output 4.0KVac
Input to Ground 1.5KVac
Output to Ground 1.5KVac
EMC
EMC / Emissions
CISPR22, EN55022, EN55011, FCC Title 47: Class B
Component Power Supply for General Use
Immunity to
EN61204-3
Electrostatic Discharge
EN61000-4-2 Level 4 Criteria A1)
Air Discharge: 15kV
Contact Discharge: 8kV
Radiated Field
EN61000-4-3 Level 3 Criteria A1)
80MHz–1GHz, 10V/M with 1kHz tone / 80% modulation
Electrical Fast Transient / Burst
Surge
EN61000-4-4 Level 3 Criteria A1)
2kV
IEC6100-4-5 Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
Conducted
EN61000-4-6 Level 3 Criteria A1)
150kHz-80MHz, 10Vrms
Power Frequency Magnetic Fields
Voltage Dips
EN61000-4-8 Level 3 Criteria A1)
10A/Meter
EN61000-4-11 Level 3 Criteria A1)
100% dip; 1 cycle (20ms); Self Recoverable
Low Energy Pulse Test (Ring Wave)
IEC61000-4-12 Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
4
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
Block Diagram
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
5
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
Device Description
1) Input terminal block connector
2) Output terminal block connector
3) DC voltage adjustment potentiometer
4) DC OK control LED (Green)
5) Universal mounting rail system
Dimensions
L x W x D: 121 x 144 x 118.6 mm
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
6
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
Engineering Data
De-rating
Note
1. Power supply components may degrade, or be
damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.1.
2. If the output capacity is not reduced when
surrounding air temperature >50°C, the device
will run into Over Temperature Protection.
When activated, the output voltage will go
into bouncing mode and will recover when the
surrounding air temperature is lowered or the
load is reduced as far as necessary to keep
the device in working condition.
3. If the device has to be mounted in any other
orientation, please do not hesitate to contact
info@deltapsu.com for more details.
4. In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance of 20mm with adjacent units
while the device is in operation.
5. Depending on the surrounding air temperature
and output load delivered by the power
Fig. 1.1 De-rating for Vertical Mounting Orientation
> 50°C de-rate power by 2.5% / °C
supply, the device housing can be very hot!
> 70°C to 75°C de-rate power by 5% / °C
Output De-rating VS. Input Voltage
■No output power de-rating across the entire input
voltage range
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
7
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
Assembly & Installation
The power supply unit (PSU) can be mounted on 35mm DIN rails in accordance with EN60715. The device should be installed with input
terminal blocks at the bottom.
Each device is delivered ready to install.
Mounting
Dismounting
Fig. 2.1 Mounting
Fig. 2.2 Dismounting
To uninstall, pull or slide down the latch as shown in Fig. 2.2.
Then slide the PSU in the opposite direction, relase the latch
and pull out the PSU from the rail.
Snap on the DIN rail as shown in Fig. 2.1:
1. Tilt the unit upwards and insert it onto the DIN rail.
2. Push downwards until stopped.
3. Press against the bottom front side for locking.
4. Shake the unit slightly to ensure that it is secured.
Safety Instructions
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
8
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
–
–
–
ALWAYS switch mains of input power OFF before connecting and
disconnecting the input voltage to the unit. If mains are not turned OFF,
there is risk of explosion / severe damage.
To guarantee sufficient convection cooling, keep a distance of
50mm above and below the device as well as a lateral distance of
20mm to other units.
Note that the enclosure of the device can become very hot depending on
the surrounding air temperature and load of the power supply. Risk of
burns!
–
–
–
Only plug in and unplug connectors when power is turned off!
DO NOT insert any objects into the unit.
Hazardous voltages may be present for up to 5 minutes after the input
mains voltage is disconnected. Do not touch the unit during this time.
The power supplies unit must be installed in an IP54 enclosure.
The power supplies are built in units and must be installed in a cabinet or
room (condensation free environment and indoor location) that is
relatively free of conductive contaminants.
–
–
Functions
■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Start-up Time
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its set value.
Hold-up Time
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time required
for the output to reach 95% of its set value, after the input voltage is removed.
Inrush current is the peak, instantaneous, input current measured
and, occurs when the input voltage is first applied. For AC input
Inrush Current
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
9
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
voltages, the maximum peak value of inrush current will occur The power supply’s overvoltage circuit will be activated when its
during the first half cycle of the applied AC voltage. This peak internal feedback circuit fails. The output voltage shall not exceed
value decreases exponentially during subsequent cycles of AC its specifications defined on Page 3 under “Protections”.
voltage.
Surge Load
It is the reserve power available constantly that allows reliable
startup of loads with high inrush current. After the output has
reached its steady state set value, the power supply can support
surge loads of up to 150% of maximum rated load (Io Max), for a
maximum duration of 5 seconds. The maximum allowed rate of
load change is 0.1amps per microseconds, and the voltage can
vary ±5% from the set value during the duration of the surge load.
Step Load Response
The power supply output voltage will remains within ±5% of its
steady state value, when subjected to a dynamic load from 10 to
100% of its rated current.
Overload & Overcurrent Protections
The power supply’s Overload (OLP) and Over current (OCP)
Protections will be activated when output current exceeds 150% of
IO (Max load). In such occurrence, the VO will start to droop and
once the power supply has reached its maximum power limit, the
protection is activated and the power supply will go into “Hiccup
mode” (Auto-Recovery). The power supply will recover once the
fault condition of the OLP and OCP is removed and IO is back
within the specifications.
Overvoltage Protection
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
10
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
persists for an extended duration and the output current is below
the overload trigger point but >100% load. In the event of a higher
operating condition at 100% load, the power supply will run into
OTP when the surrounding air temperature is >80°C. When
activated, the output voltage will go into bouncing mode until the
operating surrounding air temperature drops to 50°C or output
capacity is reduced as recommended in the derating graph.
Short Circuit Protection
The power supply’s output OLP/OCP function also provides
protection against short circuits. When a short circuit is applied,
the output current will operate in “Hiccup mode”, as shown in the
illustration in the OLP/OCP section on this page. The power
supply will return to normal operation after the short circuit is
removed.
Additionally, if the IO is <150% but >100% for a prolong period of
time (depending on the load), the Over Temperature Protection
(OTP) will be activated due to high temperature on critical
components. The power supply will then go into “Hiccup mode”
until the fault is removed.
Over Temperature Protection
As mentioned above, the power supply also has Over Temperature
Protection (OTP). This is activated when the overload condition
Operating Mode
Redundancy Operation
In order to ensure proper redundancy
operation for the power supply unit
(PSU), ensure that the output voltage
difference between the two units is kept
at 0.450~0.50V for 24V supplies. Follow
simple steps given below to verify:
Step 1.
Measure output voltage of PSU 1 and
PSU 2. If PSU 1 is the master unit, then
Vo of PSU 1 must be higher than PSU 2.
In order to set the output voltage, connect
the power supply to 50% load and set the
PSU 1 and PSU 2 output voltage.
Step 2.
Connect the right DRR module, 20A as
per the system requirement to the power
supply units PSU 1 and PSU 2 at Vin 1 &
Vin 2 respectively.
Fig. 3.1 Redundancy / Parallel Operation Connection Diagram
Step 3.
Connect the system load from Vout
.
Please note that output voltage Vout from
DRR module will be = VO (output voltage
*Vdrop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current
and surrounding air temperature.
of power supply)
module).
– Vdrop* (in DRR
Parallel Operation
All parameters are specified at 25°C ambient unless otherwise noted.
These DRR modules can also be used for Parallel function in order to increase the output power by N+1 (e.g. 2.5A + 2.5A = 5A or 2.5A
11
www.DeltaPSU.com (September 2013, Rev. 03)
+ 2.5A + 2.5A = 7.5A) or current sharing, and thus increasing the power supply and system reliability. Though the DRP024V060W1BA
is not designed for current sharing, a good current sharing between two power supplies can be achieved by following simple steps as
below (Refer to Fig. 4.1 for the Connection Diagram).
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B□
Others
Delta RoHS Compliant
Restriction of the usage of hazardous substances
The European directive 2011/65/EC limits the maximum impurity level of homogeneous materials such as lead,
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in
electrical and electronic equipment”.
This product conforms to this standard.
Conformal Coating
The Protective Coating Technology
Delta Electronics Group has designed the perfect dipping technique which penetrates everywhere including
under device, and prevents leakage. The conformal coating dipping can be applied to PCBs or circuit board.
The coating preserves the performance of precision electronic primarily by preventing ionizable contaminants
such as salt from reaching circuit nodes, where the material slumps around sharp edges. This can be a problem
especially in highly conversing atmosphere.
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
12
相关型号: