PMC-48V150W1BL [DELTA]

PMC Panel Mount Power Supply;
PMC-48V150W1BL
型号: PMC-48V150W1BL
厂家: DELTA ELECTRONICS, INC.    DELTA ELECTRONICS, INC.
描述:

PMC Panel Mount Power Supply

文件: 总12页 (文件大小:1516K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
48V 150W 1 Phase / PMC-48V150W1B□  
PMC  
Highlights & Features  
Universal AC input voltage range  
Full Aluminium casing for lightweight and corrosion resistant  
handling  
High PF > 0.99 @ 115Vac  
Conform to harmonic current IEC/EN 61000-3-2, Class A  
High MTBF > 700,000 hrs. as per Telcordia SR-332  
Overvoltage / Overcurrent / Over Temperature / Short Circuit  
Protections  
Versatile connector options:  
o
o
o
o
Terminal Block Connector  
IP20 Terminal Block Connector  
Front Face Connector  
Harness Connector  
Safety Standards  
CB Certified for worldwide use  
Model Number:  
PMC-48V150W1B  
Unit Weight:  
0.53 kg  
Dimensions (L x W x D): 178 x 97 x 38 mm  
General Description  
The new PMC-48V150W1Bis the latest offering from one of the world’s largest power supply manufacturers and solution providers -  
Delta. The product range offers a nominal output voltage of 48V, a wide temperature range from -10°C to +70°C and a highly  
dependable minimum holdup time. The state-of-the-art design is made to withstand harsh industrial environments. What makes the  
product stands out from the crowd is its lightweight full aluminum body design which can withstand shock and vibration according to  
IEC 60068-2. Delta’s Panel Mount Power Supply also offers overvoltage and overload protection. Using a wide input voltage range  
design, it is compatible worldwide. The input also includes DC operating voltage from 125-375Vdc. Best of all, this excellent design and  
quality does not come with a big price tag.  
Model Information  
PMC Panel Mount Power Supply  
Model Number  
Input Voltage Range  
Output  
Voltage  
Output Current  
PMC-48V150W1B☐  
85-264Vac (125-375Vdc)  
48Vdc  
3.125A  
Model Numbering  
C –  
48V  
PM  
150W  
1
B
Panel Mount  
Product Type  
C – Enclosed  
Output Voltage Output Power  
Single Phase  
With PFC  
Connector Type  
A – Terminal Block  
J – IP20 Terminal Block*  
L – Front Face*  
H – Harness*  
*Options  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (July 2013, Rev. 00)  
1
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
48V 150W 1 Phase / PMC-48V150W1B□  
Specifications  
Input Ratings / Characteristics  
Nominal Input Voltage  
Input Voltage Range  
Nominal Input Frequency  
Input Frequency Range  
Nominal DC Input Voltage  
DC Input Voltage Range*  
Input Current  
100-240Vac  
85-264Vac  
50-60Hz  
47-63Hz  
125-250Vdc  
125-375Vdc  
< 1.70A @ 115Vac, < 1.00A @ 230Vac  
> 89.0% @ 115Vac, > 91.0% @ 230Vac  
< 20A @ 115Vac, < 40A @ 230Vac  
> 0.99 @ 115Vac, > 0.92 @ 230Vac  
< 1.5mA @ 240Vac  
Efficiency at 100% Load  
Max Inrush Current  
Power Factor  
Leakage Current  
*Fulfills tested conditions  
Output Ratings / Characteristics  
Nominal Output Voltage  
Output Voltage Tolerance  
Output Voltage Adjustment Range  
Output Current  
48Vdc  
± 2% (initial set point tolerance from factory)  
44-53Vdc  
3.125A  
Output Power  
150W  
Line Regulation  
< 0.5% typ. (@ 85-264Vac, 100% load)  
< 1% typ. (@ 85-264Vac, 0-100% load)  
< 200mVpp  
Load Regulation  
PARD (20MHz)  
Rise Time  
< 30ms @ nominal input (100% load)  
< 3,000ms @ nominal input (100% load)  
> 30ms @ 115Vac & 230Vac (100% load)  
± 5% @ 0-100% load  
Start-up Time  
Hold-up Time  
Dynamic Response (Overshoot & Undershoot O/P Voltage)  
Start-up with Capacitive Loads  
2,000μF Max @ 25°C (CC and CR mode)  
1,000μF Max @ -10°C and 50°C (CC mode)  
2,000μF Max @ -10°C and 50°C (CR mode)  
Mechanical  
Case Chassis / Cover  
Dimensions (L x W x D)  
Unit Weight  
Aluminium  
178 x 97 x 38 mm  
0.53 kg  
Indicator  
Green LED (DC OK)  
Convection  
Cooling System  
Terminal  
M3.5 x 7 Pins (Rated 300V/15A)  
Wire  
PMC-48V150W1BA / PMC-48V150W1BL AWG 20-14  
AWG 20-12  
PMC-48V150W1BJ  
Noise (1 Meter from power supply)  
Sound Pressure Level (SPL) < 40dBA  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (July 2013, Rev. 00)  
2
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
48V 150W 1 Phase / PMC-48V150W1B□  
Environment  
Surrounding Air Temperature  
Operating -10°C to +70°C  
Storage -25°C to +85°C  
> 50°C de-rate power by 2.5% / °C  
Power De-rating  
Operating Humidity  
Operating Altitude  
< 95% RH (Non-Condensing)  
5,000 Meters  
Shock Test (Non-Operating)  
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,  
1 time per direction, 2 times in total  
Vibration (Non-Operating)  
Pollution Degree  
IEC 60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak);  
20 min per axis for all X, Y, Z direction  
2
Protections  
Overvoltage  
< 63V, SELV Output, Hicc-up Mode,  
Non-Latching (Auto-Recovery)  
Overload / Overcurrent  
Over Temperature  
Short Circuit  
> 120% of rated load current, Hicc-up Mode,  
Non-Latching (Auto-Recovery)  
< 75°C Surrounding Air Temperature @ 100% load,  
Non-Latching (Auto-Recovery)  
Hicc-up Mode, Non-Latching  
(Auto-Recovery when the fault is removed)  
Protection Against Shock  
Class I with PE* connection  
*PE: Primary Earth  
Reliability Data  
MTBF  
> 700,000 hrs. as per Telcordia SR-332  
Expected Cap Life Time  
10 years (115Vac & 230Vac, 50% load @ 40°C)  
Safety Standards / Directives  
Electrical Safety  
SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1  
and CSA C22.2 No. 60950-1, CB scheme to  
IEC 60950-1, CCC to GB4943  
CE  
In conformance with EMC Directive 2004/108/EC and  
Low Voltage Directive 2006/95/EC  
Material and Parts  
Galvanic Isolation  
RoHS Directive 2011/65/EU Compliant  
Input to Output 3.0KVac  
Input to Ground 1.5KVac  
Output to Ground 0.5KVac  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (July 2013, Rev. 00)  
3
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
48V 150W 1 Phase / PMC-48V150W1B□  
EMC  
EMC / Emissions  
Immunity to  
CISPR 22, EN 55022, FCC Title 47: Class B, GB9254  
EN 55024  
Electrostatic Discharge  
IEC 61000-4-2 Level 4 Criteria A1)  
Air Discharge: 15kV  
Contact Discharge: 8kV  
Radiated Field  
IEC 61000-4-3 Level 3 Criteria A1)  
80MHz-1GHz, 10V/M, 80% modulation (1kHz)  
Electrical Fast Transient / Burst  
Surge  
IEC 61000-4-4 Level 3 Criteria A1)  
2kV  
IEC 61000-4-5 Level 3 Criteria A1)  
Common Mode2): 2kV  
Differential Mode3): 1kV  
Conducted  
IEC 61000-4-6 Level 3 Criteria A1)  
150kHz-80MHz, 10Vrms  
Power Frequency Magnetic Fields  
Voltage Dips  
IEC 61000-4-8 Criteria A1)  
10A/Meter  
IEC 61000-4-11 100% dip; 1 cycle (20ms); Self Recoverable  
Low Energy Pulse Test (Ring Wave)  
IEC61000-4-12 Level 3 Criteria A1)  
Common Mode2): 2kV  
Differential Mode3): 1kV  
Harmonic Current Emission  
IEC/EN 61000-3-2, Class A  
IEC/EN 61000-3-3  
Voltage Fluctuation and Flicker  
1) Criteria A: Normal performance within the specification limits  
2) Asymmetrical: Common mode (Line to earth)  
3) Symmetrical: Differential mode (Line to line)  
Block Diagram  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (July 2013, Rev. 00)  
4
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
48V 150W 1 Phase / PMC-48V150W1B□  
Device Description  
PMC-48V150W1BA: Terminal Block  
PMC-48V150W1BJ: IP20 Terminal Block  
PMC-48V150W1BL: Front Face  
PMC-48V150W1BH: Harness  
1) Input & Output terminal block connector  
2) DC voltage adjustment potentiometer  
3) DC OK control LED (Green)  
Dimensions  
L x W x D: 178 x 97 x 38 mm (PMC-48V150W1BA: Terminal Block)  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (July 2013, Rev. 00)  
5
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
48V 150W 1 Phase / PMC-48V150W1B□  
Engineering Data  
De-rating  
Note  
1. Power supply components may degrade, or  
be damaged, when the power supply is  
continuously used outside the shaded region,  
refer to the graph shown in Fig. 1.  
2. If the output capacity is not reduced when  
surrounding air temperature >50C, the device  
will run into Over Temperature Protection.  
When activated, the output voltage will go  
into bouncing mode and will recover when  
the surrounding air temperature is lowered or  
the load is reduced as far as necessary to  
keep the device in working condition.  
3. In order for the device to function in the  
manner intended, it is also necessary to keep  
a safety distance of 20mm with adjacent units  
while the device is in operation.  
4. Depending  
on  
the  
surrounding  
air  
temperature and output load delivered by the  
power supply, the device can be very hot!  
5. If the device has to be mounted in any other  
orientation, please do not hesitate to contact  
info@deltapsu.com for more details.  
Fig. 1 De-rating for Vertical and Horizontal Mounting Orientation  
> 50°C de-rate power by 2.5% / °C  
Output De-rating VS. Input Voltage  
No output power de-rating across the entire  
input voltage range  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (July 2013, Rev. 00)  
6
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
48V 150W 1 Phase / PMC-48V150W1B□  
Assembly & Installation  
Mounting holes for power supply assembly onto the mounting surface.  
The power supply shall be mounted on minimum 2 mounting holes using M3 screw minimum 5mm length.  
This surface belongs to customer’s end system or panel where the power supply is mounted.  
Input / Output Connector  
Side Mounting  
Base Mounting (Vertical)  
Base Mounting (Vertical)  
Fig. 2  
Mounting Orientation  
PMC-48V150W1BA / PMC-48V150W1BL: Use flexible cable (stranded or solid) of AWG No. 20-14.  
PMC-48V150W1BJ: Use flexible cable (stranded or solid) of AWG No. 20-12.  
The torque at the Connector shall not exceed 13Kgf.cm. The insulation stripping length should not exceed 0.275” or 7mm.  
Installation of Mounting Accessories  
Only use M3 screw 6mm through the base mounting holes. This is to keep  
a safety distance between the screw and internal components.  
Recommended mounting tightening torque: 4~8Kgf.cm.  
Safety Instructions  
To ensure sufficient convection cooling, always maintain a safety distance of ≥ 20mm from all ventilated surfaces while the device  
is in operation.  
The device is not recommended to be placed on low thermal conductive surface, for example, plastics.  
Note that the enclosure of the device can become very hot depending on the ambient temperature and load of the power supply.  
Do not touch the device while it is in operation or immediately after power is turned OFF. Risk of burning!  
Do not touch the terminals while power is being supplied. Risk of electric shock.  
Prevent any foreign metal, particles or conductors from entering the device through the openings during installation. It may cause:  
Electric shock; Safety Hazard; Fire; Product failure  
Warning: When connecting the device, secure Earth connection before connecting L and N. When disconnecting the device,  
remove L and N connections before removing the Earth connection.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (July 2013, Rev. 00)  
7
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
48V 150W 1 Phase / PMC-48V150W1B□  
Functions  
Start-up Time  
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.  
Rise Time  
The time required for the output voltage to change from 10% to 90% of its set value.  
Hold-up Time  
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time  
required for the output to reach 95% of its set value, after the input voltage is removed.  
Graph illustrating the Start-up Time, Rise Time, and Hold-up Time  
Inrush Current  
Dynamic Response  
Inrush current is the peak, instantaneous, input current measured  
and, occurs when the input voltage is first applied. For AC input  
voltages, the maximum peak value of inrush current will occur  
during the first half cycle of the applied AC voltage. This peak  
value decreases exponentially during subsequent cycles of AC  
voltage.  
The power supply output voltage will remains within ±5% of its  
steady state value, when subjected to a dynamic load from 0 to  
100% of its rated current.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (July 2013, Rev. 00)  
8
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
48V 150W 1 Phase / PMC-48V150W1B□  
Overload & Overcurrent Protections  
Overvoltage Protection  
The power supply’s Overload (OLP) and Overcurrent (OCP)  
Protections will be activated when output current exceeds 120%  
of IO (Max load). In such occurrence, the VO will start to droop and  
once the power supply has reached its maximum power limit, the  
protection is activated and the power supply will go into “Hiccup  
mode” (Auto-Recovery). The power supply will recover once the  
fault condition of the OLP and OCP is removed and IO is back  
within the specifications.  
The power supply’s overvoltage circuit will be activated when its  
internal feedback circuit fails. The output voltage shall not exceed  
its specifications defined on Page 3 under “Protections”.  
Over Temperature Protection  
As mentioned above, the power supply also has Over  
Temperature Protection (OTP). In the event of a higher operating  
temperature at 100% load, the power supply will run into OTP  
when the operating temperature is beyond what is recommended  
in the de-rating graph. When activated, the output voltage will go  
into bouncing mode until the temperature drops to its normal  
operating temperature as recommended in the de-rating graph.  
It is not recommended to prolong the duration of IO when it is  
<120% but >100%, since it may cause damage to the PSU.  
Short Circuit Protection  
The power supply’s output OLP/OCP function also provides  
protection against short circuits. When a short circuit is applied,  
the output current will operate in “Hiccup mode”, as shown in the  
illustration in the OLP/OCP section on this page. The power  
supply will return to normal operation after the short circuit is  
removed.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (July 2013, Rev. 00)  
9
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
48V 150W 1 Phase / PMC-48V150W1B□  
Operating Mode  
Fig. 3  
Redundancy / Parallel Operation Connection Diagram  
Redundancy Operation  
In order to ensure proper redundancy operation for the power supply unit (PSU), ensure that the output voltage difference between the  
two units is kept at 0.90~1.00V for 48V supplies. Follow simple steps given below to verify:  
Step 1.  
Measure output voltage of PSU 1 and PSU 2. If PSU 1 is the master unit, then VO of PSU 1 must be higher than PSU 2. In order to set  
the output voltage, connect the power supply to 50% load and set the PSU 1 and PSU 2 output voltage.  
Step 2.  
Connect the right DRR module, 20A as per the system requirement to the power supply units PSU 1 and PSU 2 at Vin 1 & Vin  
respectively.  
2
Step 3.  
Connect the system load from Vout. Please note that output voltage Vout from DRR module will be = VO (output voltage of power  
supply) – Vdrop* (in DRR module).  
Parallel Operation  
These DRR modules can also be used for Parallel function in order to increase the output power by N+1 (e.g. 2.5A + 2.5A = 5A or 2.5A  
+ 2.5A + 2.5A = 7.5A) or current sharing, and thus increasing the power supply and system reliability. Though the  
PMC-48V150W1Bis not designed for current sharing, a good current sharing between two power supplies can be achieved by  
following simple steps as below (Refer to Fig. 3 for the Connection Diagram).  
Step 3.  
Step 1.  
Connect PSU 1 and PSU 2 with the DRR-20A module and  
Set output load condition for both supplies at 50% and measure  
measure at Vin 1 & Vin 2 to verify the voltage difference. Ensure  
the voltages are within ±25mV.  
the output voltages.  
Step 2.  
Step 4.  
Adjust output voltages to the same level or within ±25mV  
difference.  
Output voltage from DRR module Vout will be = VO (output  
voltage of power supply) – Vdrop* (in DRR module).  
*Vdrop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current and surrounding air temperature.  
All parameters are specified at 25°C ambient unless otherwise noted.  
10  
www.DeltaPSU.com (July 2013, Rev. 00)  
TECHNICAL DATASHEET  
PMC Panel Mount Power Supply  
48V 150W 1 Phase / PMC-48V150W1B□  
Others  
Delta RoHS Compliant  
Restriction of the usage of hazardous substances  
The European directive 2011/65/EU limits the maximum impurity level of homogeneous materials such as lead,  
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and  
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in  
electrical and electronic equipment”.  
This product conforms to this standard.  
PFC – Norm EN 61000-3-2  
Line Current Harmonic content  
Typically, the input current waveform is not sinusodial due to the periodical peak charging of the input capacitor.  
In industrial environment, complying with EN 61000-3-2 is only necessary under special conditions. Complying  
to this standard can have some technical drawbacks, such as lower efficiency as well as some commercial  
aspects such as higher purchasing costs. Frequently, the user does not profit from fulfilling this standard,  
therefore, it is important to know whether it is mandatory to meet this standard for a specific application.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (July 2013, Rev. 00)  
11  
Mouser Electronics  
Authorized Distributor  
Click to View Pricing, Inventory, Delivery & Lifecycle Information:  
Delta:  
PMC-48V150W1BA  

相关型号:

PMC-5001

High Power Reed Switch
PIC

PMC-5002

High Power Reed Switch
PIC

PMC-5025

Power Form C Switch
PIC

PMC-5025E

Latching Reed Switch
PIC

PMC-DSPV100W1A

Dual 24V/5V 100W 1 Phase
DELTA

PMC-GPIB

GPIB Interface for PCI Mezzanine Bus
NI

PMC01C024

Timers Multifunction
CARLOGAVAZZI

PMC01C115

Timers Multifunction
CARLOGAVAZZI

PMC01C230

Timers Multifunction
CARLOGAVAZZI

PMC01C724

Timers Multifunction
CARLOGAVAZZI

PMC01D024

Timers Multifunction
CARLOGAVAZZI

PMC01D115

Timers Multifunction
CARLOGAVAZZI