PMT-24V150W1AHA [DELTA]
PMT Panel Mount Power Supply;型号: | PMT-24V150W1AHA |
厂家: | DELTA ELECTRONICS, INC. |
描述: | PMT Panel Mount Power Supply |
文件: | 总13页 (文件大小:1841K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
PMT
Highlights & Features
–
–
–
–
–
Conforms to harmonic current IEC/EN 61000-3-2, Class A
Selectable AC Switch (90-132Vac, 180-264Vac)
High MTBF > 700,000 hrs. as per Telcordia SR-332
Versatile configuration options (Enclosed, L Frame)
Versatile connector options (Terminal Block, Front Face,
Harness)
Safety Standards
CB Certified for worldwide use
Model Number:
PMT-24V150W1A☐☐
Unit Weight:
0.48 kg
Dimensions (L x W x D): 178 x 97 x 38 mm
General Description
The new PMT series of panel mount power supplies is the latest offering from one of the world’s largest power supply manufacturers
and solution providers - Delta. The product offers a wide operating temperature range from -10°C to +70°C and can withstand shock
and vibration requirements (in accordance to IEC 60068-2-27 and IEC 60068-2-6 respectively). In addition to features like overvoltage
and overload protections, Delta’s PMT series of panel mount power supplies is unlike many other brands in the same price level. The
PMT series is designed for cost competitive markets without compromising the quality of the components and product specifications.
The series of products has an expected life time of 10 years. This versatile series has three different connector options (Terminal Block,
Front Face and Harness) and can also be converted into L Frame (PML) type of power supplies to satisfy different application needs.
Model Information
PMT Panel Mount Power Supply
Model Number
Input Voltage Range
Output
Voltage
Output Current
PMT-24V150W1A☐☐
90-132Vac, 180-264Vac
(Selectable by Switch)
24Vdc
6.50A
Model Numbering
CC Code
PM
24V
□ –
150W
1
A
□
□
Panel Mount Product Type Output Voltage Output Power Single Phase No PFC
Connector Type
Blank – Without
T – Enclosed
L – L Frame*
A – Terminal Block connector cover
G – Front Face*
H – Harness*
A – With connector
cover
*Options
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
1
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
Input Current
100-120Vac, 200-240Vac (Selectable by Switch)
90-132Vac, 180-264Vac (Selectable by Switch)
50-60Hz
47-63Hz
< 3.00A @ 115Vac, < 2.00A @ 230Vac
89.0% typ. @ 230Vac
< 45A @ 230Vac
Efficiency at 100% Load
Max Inrush Current (Cold Start)
Leakage Current
< 1mA @ 240Vac
Output Ratings / Characteristics
Nominal Output Voltage
Output Voltage Tolerance
Output Voltage Adjustment Range
Output Current
24Vdc
± 1% (initial set point tolerance from factory)
22.8-27.6Vdc
6.50A
Output Power
156W
Line Regulation
± 0.5% typ. (@ 100-132Vac & 200-264Vac)
± 0.5% typ. (@ 100-132Vac & 200-264Vac )
< 120mVpp
Load Regulation
PARD (20MHz)
Rise Time
< 30ms @ 115Vac, < 20ms @ 230Vac (100% load)
< 1200ms @ 115Vac, < 800ms @ 230Vac (100% load)
> 20ms @ 115Vac, > 24ms @ 230Vac
± 5% @ 0-100% load
Start-up Time
Hold-up Time
Dynamic Response (Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
8,000µF Max
Mechanical
Case Chassis
Case Cover
Aluminium
SGCC
Dimensions (L x W x D)
Unit Weight
178 x 97 x 38 mm
0.48 kg
Indicator
Green LED (DC OK)
Convection
Cooling System
Terminal
M3.5 x 7 Pins (Rated 300V/15A)
M3.5 x 7 Pins (Rated 300V/20A)
PM☐-24V150W1AA☐
PM☐-24V150W1AG☐
PM☐-24V150W1AH☐
I/P (JWT): A3963WV2-5P-A
O/P (JWT): A3963WV2-7P-U
AWG 22-12
Wire
PM☐-24V150W1AA☐ / PM☐-24V150W1AG☐
PM☐-24V150W1AH☐
AWG 22-18 (For the recommended Housing and
Terminal, please refer to the Table on Page 7)
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
2
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
Environment
Surrounding Air Temperature
Power De-rating
Operating -10°C to +70°C
Storage -25°C to +85°C
> 50°C de-rate power by 2.5% / °C
< 100Vac de-rate power by 3% / 1V
Operating Humidity
5 to 95% RH (Non-Condensing)
Operating Altitude
0 to 5,000 Meters
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine: 50G for a duration of 11ms,
3 times per direction, 18 times in total
Vibration (Non-Operating)
Pollution Degree
IEC 60068-2-6, Random: 5Hz to 500Hz @ 2.09Grms,
20 min per axis for all X, Y, Z direction
2
Protections
Overvoltage
115-135%, Hicc-up Mode, Non-Latching
(Auto-Recovery)
Overload / Overcurrent
Over Temperature
Short Circuit
110-150%, Hicc-up Mode, Non-Latching
(Auto-Recovery)
Hicc-up Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Hicc-up Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Class I with PE* connection
Protection Against Shock
*PE: Primary Earth
Reliability Data
MTBF
> 700,000 hrs. as per Telcordia SR-332
I/P: 100Vac, O/P: 100% load, Ta: 35°C
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
Safety Standards / Directives
Electrical Safety
TUV Bauart to EN 60950-1, UL/cUL recognized to
UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme
to IEC 60950-1, CCC to GB4943
CE
In conformance with EMC Directive 2004/108/EC and
Low Voltage Directive 2006/95/EC
Material and Parts
Galvanic Isolation
RoHS Directive 2011/65/EU Compliant
Input to Output 3.0KVac
Input to Ground 1.5KVac
Output to Ground 0.5KVac
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
3
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
EMC
EMC / Emissions
Immunity to
CISPR 22, EN 55022, FCC Title 47: Class B
Electrostatic Discharge
IEC 61000-4-2 Level 4 Criteria A1)
Air Discharge: 15kV
Contact Discharge: 8kV
Radiated Field
IEC 61000-4-3 Level 2 Criteria A1)
80MHz-1GHz, 3V/M with 1kHz tone / 80% modulation
Electrical Fast Transient / Burst
Surge
IEC 61000-4-4 Level 2 Criteria A1)
2kV
IEC 61000-4-5 Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
Conducted
IEC 61000-4-6 Level 2 Criteria A1)
150kHz-80MHz, 3Vrms
Power Frequency Magnetic Fields
Voltage Dips
IEC 61000-4-8 Criteria A1)
1A/Meter
IEC 61000-4-11 100% dip; 1 cycle (20ms); Self Recoverable
Harmonic Current Emission
IEC/EN 61000-3-2, Class A
IEC/EN 61000-3-3
Voltage Fluctuation and Flicker
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
Block Diagram
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
4
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
Device Description
PMT-24V150W1AA☐: Terminal Block
PMT-24V150W1AG☐: Front Face
PMT-24V150W1AH☐: Harness
1) Input & Output terminal block connector
2) DC voltage adjustment potentiometer
3) DC OK control LED (Green)
4) AC selectable switch
Dimensions
L x W x D: 178 x 97 x 38 mm
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
5
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
Engineering Data
De-rating
Note
1. Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
2. If the output capacity is not reduced when the
surrounding air temperature >70°C, the
device will run into Over Temperature
Protection. When activated, the output
voltage will go into bouncing mode and will
recover
when
the
surrounding
air
temperature is lowered or the load is reduced
as far as necessary to keep the device in
working condition.
3. In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance of 20mm with adjacent units
while the device is in operation.
4. Depending
on
the
surrounding
air
temperature and output load delivered by the
power supply, the device can be very hot!
5. If the device has to be mounted in any other
orientation, please do not hesitate to contact
info@deltapsu.com for more details.
Fig. 1 De-rating for Vertical and Horizontal Mounting Orientation
> 50°C de-rate power by 2.5% / °C
Output De-rating VS. Input Voltage
No output power de-rating for the input
voltage from 100Vac to 132Vac & 200Vac to
264Vac
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
6
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
Assembly & Installation
Mounting holes for power supply assembly onto the mounting surface.
Ⓐ
Ⓑ
Ⓒ
The power supply shall be mounted on minimum 2 mounting holes using M3 screw minimum 5mm length.
This surface belongs to customer’s end system or panel where the power supply is mounted.
Connector
Fig. 2.3 Side Mounting (Horizontal)
Fig. 2.1 Side Mounting (Vertical)
Fig. 2.2 Base Mounting (Vertical)
–
–
PM☐-24V150W1AA☐ / PM☐-24V150W1AG☐: Use flexible cable (stranded or solid) of AWG No. 22-12. The torque at the
connector shall not exceed 13Kgf.cm. The insulation stripping length should not exceed 0.275” or 7mm.
PM☐-24V150W1AH☐: Use flexible cable (stranded or solid) of AWG No. 22-18. Please refer to Table 1 for the recommended
Housing and Terminal.
Table 1
Connector (Board Mounting)
A3963WV2-5P-A
Housing
Terminal
Input (JWT)
A3963H02-5P
A3963H02-7P
A3963T0P-2
Output (JWT)
A3963WV2-7P-U
Improper Installations
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
7
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
Installation of Mounting Accessories
Fig. 3 Mounting Hole Locations
With reference to Fig. 3, the device should be mounted on a sturdy heat conducting surface with minimum of 4 mounting
holes for base mounting or 3 mounting holes for side mounting. Use M3 screws only.
Only use M3 screw ≤ 2.5mm through the base and side mounting holes.
This is to keep a safe distance between the screw and internal components.
Recommended mounting tightening torque: 4~7Kgf.cm.
Safety Instructions
–
–
Must select correct AC input voltage before turning on (Refer to the “Device Description” on Page 5).
To ensure sufficient convection cooling, always maintain a safety distance of ≥ 20mm from all ventilated surfaces while the device
is in operation.
–
–
The device is not recommended to be placed on low thermal conductive surfaces, for example, plastics.
Note that the enclosure of the device can become very hot depending on the ambient temperature and load of the power supply.
Do not touch the device while it is in operation or immediately after power is turned OFF. Risk of burning!
Do not touch the terminals while power is being supplied. Risk of electric shock.
Prevent any foreign metal, particles or conductors to enter the device through the openings during installation. It can cause: -
Electric shock; Safety Hazard; Fire; Product failure.
–
–
–
–
The power supply must be mounted by metal screws onto a grounded metal surface. It is also highly recommended that the Earth
terminal on the connector be connected to the grounded metal surface.
Warning (For Standard Terminal Block and Front Face Terminal Block products): When connecting the device, secure Earth
connection before connecting L and N. When disconnecting the device, remove L and N connections before removing the Earth
connection.
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
8
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
Functions
Start-up Time
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its set value.
Hold-up Time
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time
required for the output to reach 95% of its set value, after the input voltage is removed.
■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Inrush Current
Dynamic Response
Inrush current is the peak, instantaneous, input current measured
and, occurs when the input voltage is first applied. For AC input
voltages, the maximum peak value of inrush current will occur
during the first half cycle of the applied AC voltage. This peak
value decreases exponentially during subsequent cycles of AC
voltage.
The power supply output voltage will remains within ±5% of its
steady state value, when subjected to a dynamic load from 0 to
100% of its rated current.
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
9
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
Overload & Overcurrent Protections
Overvoltage Protection
The power supply’s Overload (OLP) and Overcurrent (OCP)
Protections will be activated when output current exceeds 110-
150% of IO (Max load). In such occurrence, the VO will start to
droop and once the power supply has reached its maximum
power limit, the protection is activated and the power supply will
go into “Hiccup mode” (Auto-Recovery). The power supply will
recover once the fault condition of the OLP and OCP is removed
and IO is back within the specifications.
The power supply’s overvoltage circuit will be activated when its
internal feedback circuit fails. The output voltage shall not exceed
its specifications defined on Page 3 under “Protections”.
Over Temperature Protection
As mentioned above, the power supply also has Over
Temperature Protection (OTP). In the event of a higher operating
temperature at 100% load, the power supply will run into OTP
when the operating temperature is beyond what is recommended
in the de-rating graph. When activated, the output voltage will go
into bouncing mode until the temperature drops to its normal
operating temperature as recommended in the de-rating graph.
It is not recommended to prolong the duration of IO when it is
<110-150% but >100%, since it may cause damage to the PSU.
Short Circuit Protection
The power supply’s output OLP/OCP function also provides
protection against short circuits. When a short circuit is applied,
the output current will operate in “Hiccup mode”, as shown in the
illustration in the OLP/OCP section on this page. The power
supply will return to normal operation after the short circuit is
removed.
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
10
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
Operating Mode
Fig. 3
Redundancy / Parallel Operation Connection Diagram
Redundancy Operation
In order to ensure proper redundancy operation for the power supply unit (PSU), ensure that the output voltage difference between the
two units is kept at 0.45~0.50V for 24V supplies. Follow simple steps given below to verify:
Step 1.
Measure output voltage of PSU 1 and PSU 2. If PSU 1 is the master unit, then VO of PSU 1 must be higher than PSU 2. In order to set
the output voltage, connect the power supply to 50% load and set the PSU 1 and PSU 2 output voltage.
Step 2.
Connect the right DRR module, 20A as per the system requirement to the power supply units PSU 1 and PSU 2 at Vin 1 & Vin
respectively.
2
Step 3.
Connect the system load from Vout. Please note that output voltage Vout from DRR module will be = VO (output voltage of power
supply) – Vdrop* (in DRR module).
Parallel Operation
These DRR modules can also be used for Parallel function in order to increase the output power by N+1 (e.g. 2.5A + 2.5A = 5A or 2.5A
+ 2.5A + 2.5A = 7.5A) or current sharing, and thus increasing the power supply and system reliability. Though the
PMT-24V150W1A☐☐ is not designed for current sharing, a good current sharing between two power supplies can be achieved by
following simple steps as below (Refer to Fig. 3 for the Connection Diagram).
Step 3.
Step 1.
Connect PSU 1 and PSU 2 with the DRR-20A module and
Set output load condition for both supplies at 50% and measure
measure at Vin 1 & Vin 2 to verify the voltage difference. Ensure
the voltages are within ±25mV.
the output voltages.
Step 2.
Step 4.
Adjust output voltages to the same level or within ±25mV
difference.
Output voltage from DRR module Vout will be = VO (output
voltage of power supply) – Vdrop* (in DRR module).
*Vdrop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current and surrounding air temperature.
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
11
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
24V 150W 1 Phase / PMT-24V150W1A□□
Others
Delta RoHS Compliant
Restriction of the usage of hazardous substances
The European directive 2011/65/EU limits the maximum impurity level of homogeneous materials such as lead,
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in
electrical and electronic equipment”.
This product conforms to this standard.
PFC – Norm EN 61000-3-2
Line Current Harmonic content
Typically, the input current waveform is not sinusodial due to the periodical peak charging of the input capacitor.
In industrial environment, complying with EN 61000-3-2 is only necessary under special conditions. Complying
to this standard can have some technical drawbacks, such as lower efficiency as well as some commercial
aspects such as higher purchasing costs. Frequently, the user does not profit from fulfilling this standard,
therefore, it is important to know whether it is mandatory to meet this standard for a specific application.
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (February 2014, Rev. 01)
12
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Delta:
PMT-24V150W1AA
相关型号:
©2020 ICPDF网 联系我们和版权申明