FRS-R-11/4 [EATON]

Fusetron™ 600 V Class RK5 FRS-R — 600 Vac/300 Vdc, 1/10-60 A, dual element, time-delay fuses;
FRS-R-11/4
型号: FRS-R-11/4
厂家: Eaton All Rights Reserved.    Eaton All Rights Reserved.
描述:

Fusetron™ 600 V Class RK5 FRS-R — 600 Vac/300 Vdc, 1/10-60 A, dual element, time-delay fuses

电路保护
文件: 总4页 (文件大小:910K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Effective August 2018  
Supersedes May 2016  
Technical Data 1017  
Fusetron™ 600 V Class RK5 FRS-R — 600 Vac/300 Vdc,  
1/10-60 A, dual element, time-delay fuses  
Catalog numbers (amps)  
FRS-R-1/10  
FRS-R-1/8  
FRS-R-1 8/10  
FRS-R-2  
FRS-R-8*  
FRS-R-9*  
FRS-R-15/100  
FRS-R-2/10  
FRS-R-1/4  
FRS-R-2 1/4  
FRS-R-2 1/2  
FRS-R-2 8/10  
FRS-R-3  
FRS-R-10*  
FRS-R-12*  
FRS-R-15*  
FRS-R-17 1/2*  
FRS-R-20*  
FRS-R-25*  
FRS-R-30*  
FRS-R-35*  
FRS-R-40*  
FRS-R-45*  
FRS-R-50*  
FRS-R-60*  
FRS-R-3/10  
FRS-R-4/10  
FRS-R-1/2  
FRS-R-3 2/10  
FRS-R-3 1/2  
FRS-R-4  
FRS-R-6/10  
FRS-R-8/10  
FRS-R-1  
FRS-R-4 1/2  
FRS-R-5  
FRS-R-1 1/8  
FRS-R-1 1/4  
FRS-R-1 4/10  
FRS-R-1 1/2  
FRS-R-1 6/10  
FRS-R-5 6/10  
FRS-R-6*  
FRS-R-6 1/4*  
FRS-R-7*  
Catalog symbols:  
•ꢀ  
FRS-R-7 1/2*  
FRS-R-(amp) (non-indicating)  
FRS-R-(amp)ID (indicating)  
* Open fuse indication available by inserting the suffix “ID.”  
E.g., FRS-R-15ID. 35 to 60 amp indicating fuses are not  
Vdc rated.  
•ꢀ  
Description:  
Carton quantity  
Advanced protection, energy efficient Class RK5  
dual-element, current-limiting, time-delay fuses  
with optional open fuse indication on select  
ratings. Time-delay — 10 second (minimum) at  
500% of rated current.  
•ꢀ  
10  
Features and benefits  
•ꢀ  
Dual-element feature provides the best time-  
delay performance, allowing closer sizing and  
superior protection of motors and transformers  
Specifications:  
•ꢀ  
Closer sizing allows for smaller fuses and less  
costly switches  
Ratings  
•ꢀ  
Volts  
•ꢀ  
Class RK5 fuses with a 200 kA interrupting rat-  
ing for use in a broad range of applications  
•ꢀ 600 Vac, 300 Vdc (1/10-30 A)  
•ꢀ 600 Vac, 250 Vdc* (35-60 A)  
•ꢀ  
Provides motor overload, ground fault, and  
short-circuit protection  
•ꢀ  
Amps — 1/10-60 A  
•ꢀ  
Helps protect motors against burnout from  
overloads and single-phasing when sized prop-  
erly  
•ꢀ  
Interrupting rating  
•ꢀ 200 kA Vac RMS Sym  
•ꢀ 20 kA Vdc  
•ꢀ  
Dual-element fuses can be applied in circuits  
subject to temporary motor overloads and surge  
currents to provide both high performance  
short-circuit and overload protection  
* Indicating versions not Vdc rated.  
Agency Information  
UL® Listed, Std. 248-12, Class RK5,  
Guide JDDZ, File E4273  
•ꢀ  
Offers a 10-second time delay at 5 times the  
rated current  
•ꢀ  
•ꢀ  
CSA® Certified, C22.2 No. 248.12,  
The time-delay feature makes it possible to use  
•ꢀ  
fuse amp ratings that are much smaller than  
those of non-time delay fuses. Considerable  
cost savings occur by permitting the use of  
smaller size switches, panels, and fuses them-  
selves.  
Class 1422-02, File 53787  
•ꢀ  
CE  
•ꢀ  
Provides current limitation to help protect down-  
stream components from high fault currents.  
•ꢀ  
Gives motor running back-up protection to  
motors without extra costs.  
Technical Data 1017  
Effective August 2018  
Fusetron™ 600 V Class RK5 FRS-R — 600 Vac/300 Vdc,  
1/10-60 A, dual element, time-delay fuses  
Time-current curves - average melt  
1/10 to 8 amps  
Recommended fuse blocks  
Catalog no.  
AMP RATING  
Amps  
30  
1-Pole  
2-Pole  
3-Pole  
RM60030-1_  
RM60060-1_  
RM60030-2_  
RM60060-2_  
RM60030-3_  
RM60060-3_  
60  
For additional information on the 600 volt fuse blocks, see data  
sheet no. 10489.  
Fuse reducers for Class R fuses  
Desired fuse (case)  
Equipment fuse clips size  
Catalog no. (pairs)  
600 V  
60 A  
30 A  
30 A  
60 A  
60 A  
NO.663-R  
NO.216-R  
NO.616-R  
NO.626-R  
100 A  
200 A  
For additional information on Class R fuse reducers, see data sheet  
no. 1118.  
Dimensions — in  
5.5"  
( 0.0ꢁ1ꢀ  
5"  
( 0.0ꢁ1ꢀ  
1.06" ( 0.008ꢀ  
0.81" ( 0.008ꢀ  
1/10 to ꢁ0A  
ꢁ5 to 60A  
CURRENT IN AMPS  
2
Eaton.com/bussmannseries  
Fusetron™ 600 V Class RK5 FRS-R — 600 Vac/300 Vdc,  
1/10-60 A, dual element, time-delay fuses  
Technical Data 1017  
Effective August 2018  
Time-current curves - average melt  
10 to 60 amps  
Current-limitation curves  
B
400000  
300000  
AMP RATING  
200000  
100000  
90000  
80000  
70000  
60000  
50000  
40000  
30000  
20000  
60A  
30A  
10000  
9000  
8000  
7000  
6000  
5000  
4000  
3000  
A
2000  
1000  
Current-limiting effects  
Let-through current  
(apparent RMS symmetrical vs. fuse rating)  
Prosp. S.C.C.  
30 A  
1000  
1000  
1000  
2000  
2000  
2000  
2000  
2000  
2000  
2000  
3000  
3000  
3000  
3000  
3000  
4000  
60 A  
1000  
2000  
2000  
2000  
2000  
3000  
3000  
3000  
3000  
3000  
4000  
4000  
4000  
4000  
5000  
6000  
5000  
10,000  
15,000  
20,000  
25,000  
30,000  
35,000  
40,000  
50,000  
60,000  
70,000  
80,000  
90,000  
100,000  
150,000  
200,000  
CURRENT IN AMPS  
Eaton.com/bussmannseries  
3
Technical Data 1017  
Effective August 2018  
Fusetron™ 600 V Class RK5 FRS-R — 600 Vac/300 Vdc,  
1/10-60 A, dual element, time-delay fuses  
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are  
by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the  
end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit  
distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once  
a product has been selected, it should be tested by the user in all possible applications.  
Eaton  
1000 Eaton Boulevard  
Cleveland, OH 44122  
Eaton.com  
Bussmann Division  
114 Old State Road  
Ellisville, MO 63021  
United States  
Eaton.com/bussmannseries  
Eaton, Bussmann and Fusetron are valuable  
trademarks of Eaton in the U.S. and other  
countries. You are not permitted to use  
the Eaton trademarks without prior written  
consent of Eaton.  
Follow us on social media to get the  
latest product and support information.  
© 2018 Eaton  
All Rights Reserved  
Printed in USA  
CSA is a registered trademark of the Canadian  
Standards Group.  
Publication No. 1017 — BU-MC16054  
August 2018  
UL is a registered trademark of the  
Underwriters Laboratories, Inc.  
Eaton.com/bussmannseries  

相关型号:

FRS-R-11/8

Fusetron™ 600 V Class RK5, FRS-R — 600 Vac/300 Vdc, 1/10-60 A, dual element, time-delay fuses
COOPER

FRS-R-11/8

Fusetron™ 600 V Class RK5 FRS-R — 600 Vac/300 Vdc, 1/10-60 A, dual element, time-delay fuses
EATON

FRS-R-110

Electric Fuse, Time Delay Blow, 110A, 600VAC, 300VDC, 200000A (IR), Inline/holder,
COOPER

FRS-R-110_16

Fusetron™ 600 V Class RK5, FRS-R — 600 Vac/300 Vdc, 1/10-60 A, dual element, time-delay fuses
COOPER

FRS-R-112

FRS-R - 600Vac/300Vdc, 1/10-60A, Dual Element, Time-Delay Fuses
COOPER

FRS-R-114

FRS-R - 600Vac/300Vdc, 1/10-60A, Dual Element, Time-Delay Fuses
COOPER

FRS-R-118

FRS-R - 600Vac/300Vdc, 1/10-60A, Dual Element, Time-Delay Fuses
COOPER

FRS-R-12

Electric Fuse, Time Delay Blow, 12A, 600VAC, 250VDC, 200000A (IR), Inline/holder
COOPER

FRS-R-12

Fusetron™ 600 V Class RK5 FRS-R — 600 Vac/300 Vdc, 1/10-60 A, dual element, time-delay fuses
EATON

FRS-R-12*

Fusetron™ 600 V Class RK5, FRS-R — 600 Vac/300 Vdc, 1/10-60 A, dual element, time-delay fuses
COOPER

FRS-R-125

Electric Fuse, Time Delay Blow, 125A, 600VAC, 300VDC, 200000A (IR), Inline/holder
COOPER

FRS-R-12ID

Electric Fuse, Time Delay Blow, 12A, 600VAC, 250VDC, 200000A (IR), Inline/holder
COOPER