Effective June 2017  
Supersedes June 2014  
Technical Data 10250  
TCP70  
70 Vdc Telecom fuses  
HALOGEN  
Agency information  
HF  
Pb  
•ꢀ  
cURus Recognized Guide JDXY2, JDXY8,  
File E19180  
FREE  
Part number system/ordering  
BK1/ TCP70-  
5
-R  
•ꢀ  
•ꢀ  
•ꢀ  
•ꢀ  
BK1/ = 1000 fuses packed in a cardboard carton  
TCP70- = Fuse series  
5 = Amp rating  
-R = RoHS compliant  
Applications  
•ꢀ  
Telecommunication DC voltage circuits  
Product features:  
Designed to UL 248 and UL 248-14  
Halogen free, lead free, RoHS compliant  
Special design telecom circuit protection  
devices  
High inrush current withstanding  
capability reduces nuisance openings  
Fuseclip assembly method  
Rugged ceramic construction  
Excellent environmental integrity  
One time positive disconnect  
Economical solution with breaking  
characteristics similar to a circuit breaker  
Technical Data 10250  
TCP70  
70VdcTelecom fuses  
Effective June 2017  
Product specifications  
Voltage  
Rating  
(Vdc)  
Current  
Rating  
(A)  
Interrupting  
Rating  
Typical Cold  
Resistance  
(mΩ)2  
Typical  
Voltage Drop  
(mV)  
Typical  
Fuse Marking  
Color  
Pre-Arcing I2t  
(A2s)3  
Part Number  
TCP70-5-R  
(A)1  
(text)  
70  
5
2500  
2500  
2500  
2500  
2500  
34.5  
20.1  
10.5  
6.3  
235  
165  
148  
138  
84  
50  
48  
Red  
Purple  
Green  
Blue  
TCP70-6-R  
70  
6
TCP70-10-R  
TCP70-15-R  
TCP70-30-R  
70  
10  
15  
30  
165  
460  
4400  
70  
70  
2.05  
Black  
1. DC Interrupting Rating (Measured at rated voltage, time constant of less than 50 microseconds, battery source).  
2. DC Cold Resistance are measured at <10% of rated current in ambient temperature of +20 °C.  
3. Typical Pre-arcing I2t (A2s) are measured at 10In and rated current.  
Electrical characteristics  
% of Amp Rating  
100%  
Opening Time  
4 hours minimum  
<60 min  
150%  
200%  
<2 min  
Environmental Data  
Operating temperature range: -55 °C to +125 °C (see derating curve)  
Altitude: <2000 m above sea level  
Humidity: 90% at +20 °C, 50% at +40 °C non-condensing  
Reliability  
Thermal shock test — MIL-STD-202G Method 107 G air-to-air, 100 cycles  
Temperature cycling — JESD22 Method A104, Condition B, 100 cycles  
Mechanical shock test — MIL-STD-002 Method 213B, 50g  
Mechanical vibration test — MIL-STD-202, Method 204D, condition D, 20 g, 10-500 Hz.  
Packaging  
1000 fuses packed into a cardboard carton. Order with part number prefix BK1/. E.g., BK1/TCP70-5-R  
Recommended PCB fuseclips  
1Axxxx Series for 6.3 mm (1/4”) fuses - see data sheet # 2131.  
Dimensions - mm  
Construction  
Not to scale  
25.2 ꢀ.ꢁ  
5.6 ꢀ.ꢁ  
+ꢀ.2  
6.ꢁ  
- ꢀ.ꢀ  
1
2
3
4 5  
1. Tin-plated copper cap  
2. Ceramic tube  
4. Filler  
5. Eyelet  
3. Fuse element wire  
2
www.eaton.com/electronics  
Technical Data 10250  
TCP70  
70VdcTelecom fuses  
Effective June 2017  
Time-current curves  
100,000  
10,000  
1000  
100  
10  
5A  
6A  
10A  
15A  
1
30A  
0.1  
0.01  
0.001  
0.0001  
1
10  
100  
1000  
10000  
Current in Amps  
3
Technical Data  
TCP70  
70VdcTelecom fuses  
10250  
Effective June 2017  
I2t (A2s) Curves  
100,000,000  
10,000,000  
1,000,000  
100,000  
5A  
6A  
10A  
15A  
10,000  
1000  
30A  
100  
10  
0.0001 0.001 0.01  
0.1  
1.0  
10  
100  
1000 10,000 100,000  
Time in Seconds  
4
www.eaton.com/electronics  
TCP70  
70VdcTelecom fuses  
Technical Data 10250  
Effective June 2017  
Thermal derating curve  
1.2  
1.1  
1.0  
0.9  
0.8  
0.7  
0.6  
-40 -30 -20 -10  
0
10 20 30 40 50 60 70 80 90 100 110 120 130  
Ambient Temperature (°C)  
Life Support Policy: Eaton does not authorize the use of any of its products for use in life support devices or systems without the express written  
approval of an officer of the Compan . Life support systems are devices which support or sustain life, and whose failure to perform, when properly  
used in accordance with instructions for use provided in the labeling, can be reasonably expected to result in significant inju y to the user.  
Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also  
reserves the right to change or update, without notice, any technical information contained in this bulletin.  
Eaton  
Electronics Division  
1000 Eaton Boulevard  
Cleveland, OH 44122  
United States  
www.eaton.com/electronics  
© 2017 Eaton  
All Rights Reserved  
Printed in USA  
Publication No. 10250 BU-SB14404  
June 2017  
Eaton is a registered trademark.  
All other trademarks are property  
of their respective owners.  

相关型号:

TCP70-10-R

70Vdc Telecom fuses

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
COOPER

TCP70-10-R

70 Vdc Telecom fuses

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
EATON

TCP70-15-R

70Vdc Telecom fuses

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
COOPER

TCP70-15-R

70 Vdc Telecom fuses

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
EATON

TCP70-30-R

70Vdc Telecom fuses

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
COOPER

TCP70-30-R

70 Vdc Telecom fuses

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
EATON

TCP70-5-R

70Vdc Telecom fuses

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
COOPER

TCP70-5-R

70 Vdc Telecom fuses

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
EATON

TCP70-6-R

70Vdc Telecom fuses

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
COOPER

TCP70-6-R

70 Vdc Telecom fuses

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
EATON

TCP8500

Moulded Type Straight Plugs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HOSIDEN

TCP8510

Moulded Type Straight Plugs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HOSIDEN