B84143-B120-R11 [EPCOS]
3-Line Filters for Converters and Power Electronics; 三线过滤器,转换器和电力电子型号: | B84143-B120-R11 |
厂家: | EPCOS |
描述: | 3-Line Filters for Converters and Power Electronics |
文件: | 总10页 (文件大小:256K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
3-Line Filters
B84143-B*-R110
B84143-B*-R112
for Converters and Power Electronics
Power line filters for three-phase systems
Rated voltage 480/275 and
520/300 V~, 50/60 Hz
Rated current 8 to 200 A
Construction
ꢀ Three-line filter
ꢀ Metal case
ꢀ Book size
Features
ꢀ Very high insertion loss
ꢀ Low leakage current
ꢀ Optimized footprint saves space
ꢀ Litz wires on the load side reduce mounting time
ꢀ Low weight
ꢀ Degree of protection: IP 201)
ꢀ Design based on
EN 133 200, UL 1283, CSA 22.2 No.8 1986
ꢀ Optimized for long motor cables
and operation under full load
ꢀ UL and CSA approval pending
Applications
ꢀ Frequency converters for motor drives, e.g.
– elevators
– pumps
– traction systems
– conveyor systems
– HVAC systems (heating, ventilation and air conditioning)
ꢀ Wind farms
ꢀ Power supplies
Terminals
ꢀ Line: Safe-to-touch terminal blocks
ꢀ Load: Litz wires
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current,
rated temperature, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
1) In accordance with IEC 60529:1989; EN 60529:1991; DIN VDE 0470-1
246 03/01
3-Line Filters
B84143-B*-R110
B84143-B*-R112
for Converters and Power Electronics
Typical circuit diagrams
B84143-B8 … B16-R110
LINE
L1
LOAD
L1’
L2
L3
L2’
L3’
SSB1526-A
B84143-B25 … B200-R11*
LINE
L1
LOAD
L1’
L2
L3
L2’
L3’
SSB1527-I
247 03/01
3-Line Filters
B84143-B*-R110
B84143-B*-R112
for Converters and Power Electronics
Technical data
Rated voltage VR
480/275 V~, 50/60 Hz (type -R110)
520/300 V~, 50/60 Hz (type -R112)
Rated current IR
Test voltage VP
Referred to 40 °C ambient temperature
1770 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
Overload capability
1,5 · IR for 3 min per hour or
2,5 · IR for 30 s per hour
Leakage current Ileak
at 480 V~, 50 Hz
Climatic category
25/100/21 (– 25 °C/+ 100 °C/21 days damp heat test)
in accordance with EN 60068-1
Characteristics and ordering codes
IR
Terminal cross section
Ileak
typ1)
Rtyp
Approx.
weight
Ordering code
line side:
load side:
terminal blocks litz wires
A
mm2
mm2
1,5
2,5
4
mA
mΩ
26
kg
8
4
< 14
< 14
< 14
< 14
< 14
< 14
< 14
< 14
< 14
< 14
1,5
1,5
2,7
3,2
3,7
4,3
7,7
8,3
9,7
13,5
B84143-B8-R110
B84143-B16-R110
B84143-B25-R11*
B84143-B36-R11*
B84143-B50-R11*
B84143-B66-R11*
B84143-B90-R11*
B84143-B120-R11*
B84143-B150-R11*
B84143-B200-R11*
16
25
4
13
6
10
36
6
6
6,5
4,3
2,7
2,0
1,4
0,9
0,5
50
16
25
25
50
50
95
10
16
25
35
35
70
66
90
120
150
200
Compilation of ordering code
Replace the asterisk * by the code number for the required version:
0 = 480 / 275 V
2 = 520 / 300 V
1) At rated operation
248 03/01
3-Line Filters
B84143-B*-R110
B84143-B*-R112
for Converters and Power Electronics
Dimensional drawings
B84143-B8-R110, B84143-B16-R110
300 10
50
200
Terminal
Litz wire
it
blocks 4 mm2
L3’
L2’
L1’
PE
Wire end ferrule
Litz wire markings
PE
M6 x 25
230
215 0,5
L1
L2
L3
Marking
LINE
LOAD
SSB1291-1
B84143-B25-R11*, B84143-B36-R11*
60
250
400 10
rm
Te inal
Litzwire
blocks 6 mm2
L3’
L2’
L1’
PE
Wire end ferrule
Litz wire markings
PE
M6 x 25
280
265 0,5
L1
L2
L3
Marking
LINE
LOAD
SSB1292-9
249 03/01
3-Line Filters
B84143-B*-R110
B84143-B*-R112
for Converters and Power Electronics
B84143-B50-R11*
60
300
500 10
Litz wire
Terminal
blocks 16 mm2
L3’
L2’
L1’
PE
PE
M6 x 25
Wire end ferrule
Litz wire markings
330
315 0,5
L1
L2
L3
Marking
LINE
LOAD
SSB1293-H
B84143-B66-R11*
80
300
500 10
Terminal
Litz wire
blocks 25 mm2
L3’
L2’
L1’
PE
Wire end ferrule
Litz wire markings
PE
M10 x 35
330
315 0,5
L1
L2
L3
Marking
LINE LOAD
SSB1562-6
250 03/01
3-Line Filters
B84143-B*-R110
B84143-B*-R112
for Converters and Power Electronics
B84143-B90-R11*
80
300
500 10
Terminal
Litz wire
blocks 25 mm2
L3’
L2’
L1’
PE
Wire end ferrule
PE M10 x 35
Litz wire markings
330
315 0,5
L1
L2
L3
Marking
LINE LOAD
SSB1546-P
B84143-B120-R11*, B84143-B150-R11*
90
350
500 10
Te inal
rm-
Litz wire
t
blocks
50 mm2
L3’
L2’
L1’
PE
PE
M10 x 35
W e end ferrule
ir
Litz wire markings
380
365 0,5
L1
L2
L3
Marking
LINE LOAD
SSB1561-X
251 03/01
3-Line Filters
B84143-B*-R110
B84143-B*-R112
for Converters and Power Electronics
B84143-B200-R11*
Terminal blocks 95 mm2
Litz wire Wire end ferrule
400
500 10
110
L1’
L2’
L3’
PE
PE
M10 x 35
Litz wire markings
430
415 0,5
L1
L2
L3
Marking
LINE LOAD
SSB1563-E
252 03/01
3-Line Filters
B84143-B*-R110
B84143-B*-R112
for Converters and Power Electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84143-B8-R110, B84143-B16-R110
B84143-B25-R11*, B84143-B36-R11*
SSB1528-R
SSB1529-Z
120
dB
120
dB
αe
αe
100
90
80
70
60
50
40
30
20
10
0
100
90
80
70
60
50
40
30
20
10
0
104
105
106
107
Hz 108
104
105
106
107
Hz 108
f
f
B84143-B50-R11*
B84143-B66-R11*
SSB1530-3
SSB1531-B
120
dB
120
dB
αe
αe
100
100
90
80
70
60
50
40
30
20
10
0
90
80
70
60
50
40
30
20
10
0
104
105
106
107
Hz 108
104
105
106
107
Hz 108
f
f
253 03/01
3-Line Filters
B84143-B*-R110
B84143-B*-R112
for Converters and Power Electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84143-B90-R11*, B84143-B120-R11*
B84143-B150-R11*, B84143-B200-R11*
SSB1533-S
SSB1532-J
120
dB
120
dB
αe
αe
100
90
80
70
60
50
40
30
20
10
0
100
90
80
70
60
50
40
30
20
10
0
104
105
106
107
Hz 108
104
105
106
107
Hz 108
f
f
254 03/01
Herausgegeben von EPCOS AG
Marketing Kommunikation, Postfach 80 17 09, 81617 München, DEUTSCHLAND
EPCOS AG 2000. Alle Rechte vorbehalten. Vervielfältigung, Veröffentlichung, Verbreitung und
Verwertung dieser Broschüre und ihres Inhalts ohne ausdrückliche Genehmigung der EPCOS AG
nicht gestattet.
Mit den Angaben in dieser Broschüre werden die Bauelemente spezifiziert, keine Eigenschaften
zugesichert. Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen
für Erzeugnisse und Leistungen der Elektroindustrie, soweit nichts anderes vereinbart wird.
Diese Broschüre ersetzt die vorige Ausgabe.
Fragen über Technik, Preise und Liefermöglichkeiten richten Sie bitte an den Ihnen nächstgele-
genen Vertrieb der EPCOS AG oder an unsere Vertriebsgesellschaften im Ausland.
Bauelemente können aufgrund technischer Erfordernisse Gefahrstoffe enthalten. Auskünfte
darüber bitten wir unter Angabe des betreffenden Typs ebenfalls über die zuständige Vertriebsge-
sellschaft einzuholen.
Published by EPCOS AG
Marketing Communications, P.O. Box 80 17 09, 81617 Munich, GERMANY
EPCOS AG 2000. All Rights Reserved. Reproduction, publication and dissemination of this bro-
chure and the information contained therein without EPCOS’ prior express consent is prohibited.
The information contained in this brochure describes the type of component and shall not be con-
sidered as guaranteed characteristics. Purchase orders are subject to the General Conditions for
the Supply of Products and Services of the Electrical and Electronics Industry recommended by the
ZVEI (German Electrical and Electronic Manufacturers’ Association), unless otherwise agreed.
This brochure replaces the previous edition.
For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or
the international Representatives.
Due to technical requirements components may contain dangerous substances. For information on
the type in question please also contact one of our Sales Offices.
1
相关型号:
©2020 ICPDF网 联系我们和版权申明