Power-D-Box Printed Circuit Board Version for 2216/REF16  
Description  
The Power-D-Box® based on a printed circuit board is a compact  
power distribution system, designed as a 19" 2U rack made of  
aluminium profiles with anodised front plate. It accommodates the  
plug-in type thermal-magnetic circuit breakers type 2216 as well  
as the electronic circuit protectors type REF16. 30 single pole ways  
are available as a redundant or non-redundant system. The integral  
group signalling works as series connection of the make contacts.  
The entire internal circuitry is designed as a printed circuit board.  
The unprotected pole is also being patched in the distribution.  
Connection is by means of terminals directly on the circuit board or  
via additional terminals on a rear-side symmetrical rail. Status indica-  
tion (green LED) coupled with one relay output per group is available  
as an option. Upon request it is also possible to add the junction of  
two redundant entry lines via decoupling diodes.  
®
Power-D-Box for 2216 and REF16  
Order numbering code  
Technical Data  
Type No.  
PDB-P-L 19“ Power-D-Box® with pcb, positive pole protected  
19“ Power-D-Box®  
length: 84 HP (426.72 mm)  
height: 2 U (88.90 mm)  
depth: 150 mm version A0/R0  
250 mm version A3/R3  
Suitable types  
2216  
thermal-magnetic circuit breaker  
REF16 electronic overcurrent protector (DC 24 V only)  
Supply and load terminals on pcb  
30A0 1 x 30 types, non-redundant  
30R0 2 x 15 types, redundant  
Supply and load terminals on pcb  
30A3SW 1 x 30 types, non-redundant  
30R3SW 2 x 15 types, redundant  
Signalling, terminals on pcb  
B1 make contacts connected in series  
B7 make contacts connected in  
series, with voltage monitoring  
(DC 24 V only)  
Material:  
aluminium, partly anodised  
Rated voltage:  
Supply:  
AC 50 V; DC 50 V; DC 24 V with REF16  
M6 terminal studs for ring cable lug  
(version A0 / R0)  
spring-loaded terminal 35 mm²  
(version A3/R3)  
max. 50 A per group  
Load terminals:  
Group signalling:  
30 ways 1-pole protected (version A0 / A3)  
2 x 15 ways 1-pole protected (version R0 / R3)  
spring-loaded terminals 2.5 mm²  
I
max. = 16 A (depending on circuit breaker rating,  
Signalling, terminals on  
symmetrical rail  
B1GR make contacts connected  
in series  
please observe derating factor)  
Make contacts connected in series  
(all versions) per group  
spring-loaded terminal 2.5 mm², Imax = 0.5 A  
B7GR make contacts connected  
in series, with voltage  
Grounding of enclosure: via M6 terminal studs on inner housing side  
in the event of redundancy (R0 / R3) doubled  
monitoring (DC 24 V only)  
Options  
D de-coupling diodes (version R3)  
available on request  
Ambient temperature  
range:  
0 … 50 °C  
Benefits  
PDB-P-L- 2216- 30R4SW - B1GR-D  
ordering example  
lReduced wiring time through printed circuit board design  
lSmall installation depth of 150 mm or 250 mm for the use in  
small-sized installation sites  
lRemoveable front plate with captive screw technology and  
printed-on marking  
l30 slots for thermal-magnetic circuit breakers or electronic  
overcurrent protectors in a Power-D-Box®  
lRedundant design optional with 2 x 15 ways  
lCircuit breakers can be plugged in later (also with the system live)  
lScrew terminals directly on pc board (plus and minus pole),  
additional terminals optionally on a rear-side rail.  
6
lLine entry for cables up to 35 mm² (16 mm² when redundant)  
lLine entry up to 2 x 50 A (redundant)  
lLoad terminals for cables up to 2.5 mm²  
lLoad terminals up to 16 A (10 A with electronic protection)  
lGroup signalling through integral potential-free auxiliary  
contacts, make contacts connected in series  
lSignalling available separately per group in the event of redundancy  
lIntegral cable grip rail behind the terminals  
lCover against live parts by means of a perforated sheet on top  
lInterchangeable flanges for 19“ or ETSI mounting  
lBlanking piece for empty slots enclosed (30 pcs)  
lCustomer-specific versions, e.g. with back-up fuses,  
de-coupling diodes, separate circuits, AC and/or DC,  
customised marking etc., are available upon request.  
1646  
www.e-t-a.de  
1
®
Power-D-Box Printed Circuit Board Version for 2216/REF16  
Versions and terminal designs  
Version for  
supply terminals  
terminals on cable size  
load terminals  
signalling  
Circuit Breaker Type 2216  
tightening  
torque  
cable size  
2.5 mm2  
2.5 mm2  
2.5 mm2  
2.5 mm2  
tightening  
cable size  
2.5 mm2  
2.5 mm2  
2.5 mm2  
2.5 mm2  
tightening  
torque  
torque  
PDB-P-L-2216-30A0-B1  
printed circuit  
board  
M6  
3.7 – 4.3  
Nm  
spring force  
spring force  
PDB-P-L-2216-30R0-B1  
printed circuit  
board  
M6  
3.7 – 4.3  
Nm  
spring force  
spring force  
spring force  
spring force  
spring force  
spring force  
PDB-P-L-2216-30A3SW-B1GR  
PDB-P-L-2216-30R3SW-B1GR  
symmetrical  
rail  
35 mm2  
35 mm2  
spring force  
symmetrical  
rail  
spring force  
Overcurrent Protector Type REF16  
PDB-P-L-REF16-30A0-B1  
printed circuit  
board  
M6  
M6  
3.7 – 4.3  
Nm  
2.5 mm2  
2.5 mm2  
2.5 mm2  
2.5 mm2  
spring force  
spring force  
spring force  
spring force  
2.5 mm2  
2.5 mm2  
2.5 mm2  
2.5 mm2  
spring force  
spring force  
spring force  
spring force  
PDB-P-L-REF16-30R0-B1  
PDB-P-L-REF16-30A3SW-B1GR  
PDB-P-L-REF16-30R3SW-B1GR  
Ground studs  
printed circuit  
board  
3.7 – 4.3  
Nm  
symmetrical  
rail  
35 mm2  
35 mm2  
M6  
spring force  
spring force  
3.7 - 4.3 Nm  
symmetrical  
rail  
Schematic diagram for version with 2216  
pcb  
terminals on pcb (A0 / R0)  
B
A
A+  
A+  
B+  
B+  
SiA  
SiA  
SiB  
SiB  
1
2
15  
1
2
15  
1
1
2
14 12  
1
14 12  
1
14 12  
1
14 12  
1
14 12  
14 12  
11  
11  
11  
11  
11  
11  
2
2
2
2
2
SiA  
A-  
SiA  
A-  
SiB  
B-  
SiB  
B-  
6
PE  
PE  
terminals on symmetrical rail (A3/R3)  
2
www.e-t-a.de  
1646  
®
Power-D-Box Printed Circuit Board Version for 2216/REF16  
Schematic diagram for REF16  
ꢊꢋꢌ  
ꢀꢁꢂꢃꢄꢅꢆꢇꢈ ꢉꢅ ꢊꢋꢌ ꢍꢎꢏ ꢐ ꢑꢏꢒ  
ꢎꢓ  
ꢎꢓ  
ꢜꢓ  
ꢜꢓ  
ꢘꢄꢎ  
ꢘꢄꢎ  
ꢘꢄꢜ  
ꢘꢄꢜ  
ꢙꢗ  
1
1ꢛ  
1
1ꢛ  
ꢕꢅꢖ  
ꢕꢅꢖ  
ꢘꢄꢜ  
ꢜꢝ  
ꢘꢄꢜ  
ꢜꢝ  
ꢘꢄꢎ  
ꢎꢝ  
ꢘꢄꢎ  
ꢎꢝ  
ꢢꢙ  
ꢢꢙ  
ꢀꢁꢂꢃꢄꢅꢆꢇꢈ ꢉꢅ ꢈꢣꢃꢃꢁꢀꢂꢄꢋꢆꢇ ꢂꢆꢄꢇ ꢍꢎꢠꢐꢑꢠꢒ  
Dimensions  
ꢀꢁewꢂ ꢃ ꢄꢁꢅeꢆꢂꢁꢇꢆꢂꢈ ꢄꢅꢆꢇꢈ ꢉꢊꢋꢌ ꢍꢎꢎ ꢉꢋꢅꢏꢊꢆꢇꢏ  
46ꢀ  
4ꢁꢂꢃ6  
6
1646  
www.e-t-a.de  
3
®
Power-D-Box Printed Circuit Board Version for 2216/REF16  
Dimensions of pcb  
ꢀꢁꢂ ꢃꢄew ꢆꢇꢈꢁꢉꢊꢋꢉꢌ ꢍꢃꢎꢉꢌꢏꢀ ꢋꢉ ꢂꢈꢀꢋꢊꢋꢈꢉ ꢐꢑꢒꢓꢔꢕ ꢖꢏꢗꢀꢋꢈꢉ ꢘꢙꢚꢛꢙ  
ꢅeaꢆ ꢃꢄew ꢖꢏꢗꢀꢋꢈꢉ ꢘꢙꢚꢛꢙ  
ꢀꢋꢌꢉꢎꢃꢃꢋꢉꢌ ꢘ  
ꢀꢋꢌꢉꢎꢃꢃꢋꢉꢌ ꢅ  
ꢀꢁꢂꢂꢃꢄ ꢘ  
ꢀꢁꢂꢂꢃꢄ ꢅ  
ꢠꢎꢡꢃꢏ ꢠꢃꢎꢇꢂ ꢗꢎꢋꢃ  
ꢃꢈꢎꢟ ꢊꢏꢗꢇꢋꢉꢎꢃꢀ ꢘ  
ꢃꢈꢎꢟ ꢊꢏꢗꢇꢋꢉꢎꢃꢀ ꢅ  
ꢀꢁꢂ ꢃꢄew ꢆꢋꢉꢊꢏꢗꢉꢎꢃ ꢜꢋꢗꢋꢉꢌ ꢉꢈꢊ ꢀꢝꢈꢜꢉꢔ ꢖꢏꢗꢀꢋꢈꢉ ꢘꢞꢚꢛꢞ  
ꢀꢋꢌꢉꢎꢃꢃꢋꢉꢌ ꢘ  
ꢀꢋꢌꢉꢎꢃꢃꢋꢉꢌ ꢅ  
ꢃꢈꢎꢟ ꢊꢏꢗꢇꢋꢉꢎꢃ ꢅ  
ꢀꢁꢂꢂꢃꢄ ꢘ  
ꢀꢁꢂꢂꢃꢄ ꢅ  
ꢃꢈꢎꢟ ꢊꢏꢗꢇꢋꢉꢎꢃꢀ ꢘ  
6
4
www.e-t-a.de  
1646  
®
Power-D-Box Printed Circuit Board Version for 2216/REF16  
Accessories  
Jumper:  
ꢀꢁaꢂꢃꢄꢂꢅ ꢆꢄeꢇe ꢈꢉꢊ ꢋꢉweꢊ-ꢌ-ꢀꢉꢍ  
ꢀꢁꢂꢃꢄꢅ ꢆꢆ16ꢇ ꢈꢉꢊ16ꢋ  
ꢎ ꢏꢐꢑ ꢒꢓꢏ ꢐꢔ  
for insertion in empty slots instead of circuit breakers for bridging  
the looped-through auxiliary contacts (series connection)  
SB-S21-P1-01-2-1A  
1ꢀꢁ1  
ꢂꢁꢂ  
ꢃꢀ  
1ꢆꢇꢙ  
11ꢛꢌꢜ  
14ꢛꢞꢜ  
ꢕꢉꢊ ꢊeꢖꢉꢗꢄꢂꢅ tꢘe ꢙꢁaꢂꢃꢄꢂꢅ ꢆꢄeꢇeꢚ  
ꢃꢌꢅꢍ ꢎꢏ ꢁꢍꢄ ꢅꢐꢑꢄꢒꢓꢑꢎꢔꢄꢑ ꢕꢅ ꢅꢍꢖꢒꢏ ꢗꢄꢘꢖꢒ  
6
All dimensions without tolerances are for reference only. E-T-A reserves the right change  
specifications at any time in the interest of improved design, performance and cost effective-  
ness, the right to make changes in these specifications without notice is reserved. Product  
markings may not be exactly as the ordering codes. Errors and omissions excepted.  
1646  
www.e-t-a.de  
5
6
6
www.e-t-a.de  
1646  

相关型号:

PDB-P-L-3600-30A0-B4

Flexible Power-D-Box
ETAL

PDB-P-L-3600-30A3SW-B4GR

Flexible Power-D-Box
ETAL